Firmware Manual
9000X AF Drives
7-12 For more information visit: www.eaton.com
MN04004001E
August 2010
Pump and Fan Control Application
Basic Parameters — G1.1 (Continued)
Code Parameter Min. Max. Unit Default Cust ID Note
P1.1.13
Local control
reference
0 7 4 173 0 = AI1
1 = AI2
2 = AI3
3 = AI4
4 = Keypad reference
5 = Fieldbus reference
6 = Motor potentiometer
7 = PID controller
P1.1.14
Remote control
reference
0 7 0 174 0 = AI1
1 = AI2
2 = AI3
3 = AI4
4 = Keypad reference
5 = Fieldbus reference
6 = Motor potentiometer
7 = PID controller
P1.1.15
PID controller
reference signal
(Place A)
0 6 4 332 0 = AI1
1 = AI2
2 = AI3
3 = AI4
4 = Keypad reference
5 = Fieldbus reference
6 = Motor potentiometer
P1.1.16 PID controller gain 0.0 1000.0 % 100.0 118
P1.1.17 PID controller I-time 0.00 320.00 s 1.00 119
P1.1.18 PID controller D-
time
0.00 10.00 s 0.00 132
P1.1.19 Sleep frequency P1.1.1 P1.1.2 Hz 10.00 1016
P1.1.20 Sleep delay 0 3600 s 30 1017
P1.1.21 Wake up limit 0.00 100.00 % 25.00 1018
P1.1.22 Wake up action 0 3 0 1019 0 = Wake-up when below wake
up level (P1.1.21)
1 = Wake-up at when above
wake up level (P1.1.21)
2 = Wake-up when below wake
up level (PID ref.)
3 = Wake-up when above wake
up level (PID ref.)
P1.1.23 Jogging speed
reference
0.00 P1.1.2 Hz 10.00 124