Firmware Manual
9000X AF Drives
7-10 For more information visit: www.eaton.com
MN04004001E
August 2010
Pump and Fan Control Application
Parameter Lists
On the next pages you will find the lists of parameters within the respective parameter
groups. The parameter descriptions are given in Chapter 8.
Column explanations:
Monitoring Values (Control Keypad: Menu M8)
The monitoring values are the actual values of parameters and signals as well as statuses
and measurements. Monitoring values cannot be edited.
See 9000X AF Drives User Manual, Chapter 5 for more information. Note that the monitoring
values V1.18 to V1.23 are available in the PFC control application only.
Table 7-2: Monitoring Values
Code = Location indication on the keypad; Shows the operator the present
parameter number
Parameter = Name of parameter
Min. = Minimum value of parameter
Max. = Maximum value of parameter
Unit = Unit of parameter value; Given if available
Default = Value preset by factory
Cust = User’s customized setting
ID = ID number of the parameter for reference to Chapter 8
= Parameter value can only be changed after the drive has been stopped
= Programmed using terminal to function (TTF) method. See Page 6-3.
Code Parameter Unit ID Description
V1.1 Output frequency Hz 1 Output frequency to motor
V1.2 Frequency reference Hz 25 Frequency reference to motor control
V1.3 Motor speed rpm 2 Motor speed in rpm
V1.4 Motor current A 3
V1.5 Motor torque % 4 In % of Motor nominal torque
V1.6 Motor power % 5 Motor shaft power
V1.7 Motor voltage V 6
V1.8 DC link voltage V 7
V1.9 Unit temperature ∞C 8 Heatsink temperature
V1.10 Motor temperature % 9 Calculated motor temperature
V1.11 Analog input 1 V/mA 13 AI1 input value
V1.12 Analog input 2 V/mA 14 AI2 input value
V1.13 DIN1, DIN2, DIN3 15 Digital input statuses
V1.14 DIN4, DIN5, DIN6 16 Digital input statuses
V1.15 Analog I
out
mA 26 AO1
V1.16 Analog input 3 V/mA 27 AI3 input value