Specifications
66
EATON CORPORATION Reference Guide & Pricebook
January 1, 2012
EX RT BATTERY BACKUP TIMES (in minutes)*
Load (VA/Watts) Base Battery Module +1 EBM +2 EBMs +3 EBMs +4 EBMs +5 EBMs
EXRTG5000-XL6U / EXRTL5000-XL9U
500/400 170 358 540 740 892 1220
1000/800 91 170 260 355 505 540
1500/1200 49 110 170 240 290 355
2000/1600 33 84 120 170 235 260
2500/2000 25 60 100 122 170 225
3000/2400 21 46 75 110 135 170
3500/2800 16 39 64 95 119 140
4000/3200 13 31 57 84 105 120
4500/3600 11 27 52 68 92 110
5000/4000 9 25 45 60 84 100
EXRTG7000-XL6U / EXRTL7000-XL9U
700/490 121 266 447 578 756 889
1400/890 57 125 203 244 364 453
2100/1470 37 80 124 185 245 287
2800/1960 28 61 101 128 169 232
3500/2450 21 53 83 108 132 164
4200/2940 15 37 66 90 110 133
4900/3430 12 30 55 75 98 118
5600/3920 10 24 45 61 77 102
6300/4410 8 22 38 53 69 86
7000/4900 7 20 32 45 57 72
EXRTG11000-XL6U / EXRTL11000-XL9U
1100/800 90 191 293 392 525 637
2200/1600 40 93 143 199 261 312
3300/2400 25 61 96 135 172 201
4400/3200 18 43 71 99 120 142
5500/4000 14 30 53 84 102 113
6600/4800 11 24 44 60 86 102
7700/5600 9 20 34 51 67 87
8800/6400 7 17 27 43 56 68
9900/7200 6 15 24 35 48 60
11000/8000 5 14 22 30 42 53
* Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
EATON EX RT UPS
Pulsar series (continued)
View interactive runtime graphs at www.eaton.com/ex-rt