Specifications

61www.eaton.com/powerquality 1.800.356.5794
January 1, 2012
MX BATTERY BACKUP TIMES (in minutes @ .7 pf)
*
Load kW Internal Batteries +1 EBM +2 EBMs +3 EBMs
700 36 132 232 332
1050 23 87 156 225
1400 17 64 116 169
1750 13 50 91 134
2100 10 40 74 110
2450 8 33 62 93
2800 7 29 53 80
3150 6 25 47 70
3500 5 22 41 62
MX FRAME BATTERY BACKUP
TIMES (PARALLEL UPS, in minutes @ .7 pf, N+0)**
Load% Internal Batteries +1 EBM +2 EBMs +3 EBMs
20 36 132 232 332
30 23 87 156 225
40 17 64 116 169
50 13 50 91 134
60 10 40 74 110
70 8 33 62 93
80 7 29 53 80
90 6 25 47 70
10 5 22 41 62
* Backup times are approximate and vary with equipment, configuration, battery age, temperature, etc.
** For parallel systems, an EBM is required for each power module to reach data point. For example, a 20kVA system with four power modules would need four individual EBMs to reach 22 minutes at full
load.
EATON MX UPS
Pulsar series (continued)
View interactive runtime graphs at www.eaton.com/mx