Specifications
53www.eaton.com/powerquality 1.800.356.5794
January 1, 2012
9130 RACK MODELS BATTERY BACKUP TIMES (in minutes) @ 0.7 Power Factor*
Internal
VA/Watts Batteries +1EBM +2 EBMs +3 EBMs +4 EBMs
PW9130L700R-XL2U
700/490 14 55 102 148 175
525/368 20 77 140 179 239
350/245 32 124 189 282 414
175/123 64 200 395 552 739
PW9130L1000R-XL2U
1000/700 10 40 73 108 149
750/525 13 58 101 152 219
500/350 24 85 172 249 304
250/175 48 190 310 451 569
PW9130G1000R-XL2U / PW9130i1000R-XL2U
1000/700 10 40 78 110 150
750/525 13 55 103 151 223
500/350 22 82 186 250 312
250/175 47 190 328 431 584
PW9130L1500R-XL2U
1500/1050 7 34 63 88 135
1125/788 11 44 84 129 210
750/525 18 79 148 207 267
375/263 38 167 278 475 540
PW9130i1500R-XL2U
1500/1050 7 32 61 98 128
1125/788 11 47 83 126 195
750/525 18 81 143 208 262
375/263 38 171 298 416 564
PW9130L2000R-XL2U
2000/1400 9 45 86 124 163
1500/1050 14 66 115 165 225
1000/700 26 101 185 251 343
500/350 52 197 353 481 629
PW9130i2000R-XL2U
2000/1400 9 46 83 118 163
1500/1050 13 64 118 170 221
1000/700 25 95 190 242 345
500/350 53 205 346 488 625
PW9130L2500R-XL2U
2500/2250 7 31 59 87 119
1875/1688 10 43 81 121 154
1250/1125 17 65 120 163 203
625/563 40 145 228 363 491
PW9130L3000R-XL2U
3000/2100 5 25 48 72 100
2250/1575 8 37 72 102 137
1500/1050 13 60 100 165 223
750/525 34 138 228 326 438
PW9130G3000R-XL2U / PW9130G3000R-XL2UEU / PW9130i3000R-XL2U
3000/2100 6 25 45 68 96
2250/1575 8 34 70 96 130
1500/1050 14 62 92 156 211
750/525 34 130 212 355 442
*Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc. The 9130 has a 0.9 power factor, but runtimes are shown here at 0.7 power factor for
easy comparison against competitors' products, which have a 0.7 power factor.
EATON 9130 UPS RACKMOUNT
Powerware series (continued)
View interactive runtime graphs
at www.eaton.com/9130rm