Specifications
50
EATON CORPORATION Reference Guide & Pricebook
January 1, 2012
EX BATTERY BACKUP TIMES (in minutes)
(continued)
Load Standard
(VA/Watts) Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
EX 1500 / 1500 RT 2U
150/105 60 212 360 475 700
300/210 32 110 220 280 380
450/315 21 78 155 210 260
600/420 16 60 115 160 200
750/525 13 47 83 140 180
900/630 10 40 71 110 140
1050/735 8 34 60 90 118
1200/840 7 30 52 76 100
1350/945 6 27 48 70 90
1500/1050 5 24 42 62 80
EX 2200 RT 2U & 3U*
220/154 90 352 587 831 1216
440/308 48 200 340 470 650
660/462 30 130 225 320 450
880/616 22 100 170 260 350
1100/770 16 80 135 215 286
1320/924 13 62 110 180 240
1540/1078 10 50 95 150 200
1760/1232 8 42 80 125 170
1980/1386 7 36 65 110 152
2200/1540 6 30 51 83 134
EX 3000 RT 2U & 3U**
300/210 79 254 454 549 847
600/420 40 130 255 290 445
900/630 25 80 160 205 290
1200/840 18 60 120 162 230
1500/1050 14 48 102 129 187
1800/1260 12 38 82 103 150
2100/1470 9 32 72 86 125
2400/1680 7 27 58 73 100
2700/1890 6 22 50 64 82
3000/2100 5 18 36 47 70
EX 3000 RT 3U XL***
300/210 - 175 375 549 768
600/420 - 90 215 290 405
900/630 - 55 135 205 265
1200/840 - 42 102 162 212
1500/1050 - 34 88 129 173
1800/1260 - 26 70 103 138
2100/1470 - 23 63 86 116
2400/1680 - 20 51 73 93
2700/1890 - 16 44 64 76
3000/2100 - 13 31 47 65
* Output power rating = 1650W ** Standard configuration power rating = 2550W, with EBM = 2100W
*** Output power rating = 2150W up to 12 EBMs can be added for extended runtime of 196–1909 minutes
Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
The Eaton EX has a 0.9 power factor, but runtimes are shown here at 0.7 power factor for easy comparison against competitor's products, which have a 0.7 power factor.
EATON EX UPS