Cut Sheet
6
Technical Data TD01005006E
Effective August 2009
Eaton’s SPD Series for integration into
electrical distribution equipment
EATON CORPORATION www.eaton.com
Specifi cations
Table 12. SPD Series Specifications
Description Specification
Surge capacity ratings available 50, 80, 100, 120, 160, 200, 250, 300, 400 kA per phase
Nominal discharge current (I
n
) 20 kA
Short circuit current rating (SCCR) 200 kA
SPD type Basic feature package = Type 1 (can also be used in Type 2 applications)
Standard and Standard with Surge Counter feature packages = Type 2
Single split phase voltages available 120/240
Three-phase Wye system voltages available 120/208, 127/220, 230/400, 277/480, 347/600
Three-phase Delta system voltages available 240, 480, 600
Input power frequency 50/60 Hz
Power consumption (basic units):
208Y, 220Y, 240S, 240D, and 240H voltage codes
400Y, 480Y, and 480D voltage codes
600Y and 600D voltage codes
0.5W
1.1W
1.3W
Power consumption (standard and standard with surge counter units):
208Y, 220Y, 240S, 240D, and 240H voltage codes
400Y, 480Y, and 480D basic voltage codes
600Y and 600D voltage codes
0.6W
1.7W
2.1W
Protection modes Single split phase . . . . . . . . . . . L-N, L-G, N-G, L-L
Three-phase Wye . . . . . . . . . . . L-N, L-G, N-G, L-L
Three-phase Delta . . . . . . . . . . L-G, L-L
Three-phase high-leg Delta . . . L-N, L-G, N-G, L-L
Maximum continuous operating voltage (MCOV):
240S, 208Y, 220Y, and 240H MCOV
400Y and 480Y MCOV
600Y MCOV
240D MCOV
480D MCOV
600D MCOV
150 L-N, 150 L-G, 150 N-G, 300 L-L
320 L-N, 320 L-G, 320 N-G, 640 L-L
420 L-N, 420 L-G, 420 N-G, 840 L-L
320 L-G, 320 L-L
640 L-G, 640 L-L
840 L-G, 840 L-L
Ports 1
Operating temperature –4°F through 122°F (–20°C through 50°C)
Operating humidity 5% through 95%, noncondensing
Operating altitude Up to 16,000 ft (5000m)
Seismic withstand capability Meets or exceeds the requirements specified in IBC 2006, CBC 2007, and UBC Zone 4
Weight 50–200 kA units approximately 3.5 lbs (1.6 kg)
250–400 kA units approximately 7.0 lbs (3.2 kg)
Form C relay contact ratings 150 Vdc or 125 Vac, 1A maximum
Form C relay contact logic Power ON, normal state—NO contact = open, NC contact = closed
Power OFF or fault state—NO contact = closed, NC contact = open
EMI/RFI filtering attenuation Up to 50 dB from 10 kHz to 100 MHz
Agency certifications and approvals UL 1449 3rd Edition recognized component for the U.S. and Canada
UL 1283 (Type 2 SPDs only)
Warranty 10 years