Cut Sheet

5
Technical Data TD01005006E
Effective August 2009
Eaton’s SPD Series for integration into
electrical distribution equipment
EATON CORPORATION www.eaton.com
Table 4. 50 kA Direct Bus Mounted Integrated Unit VPR
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 500 1000 500 1000
208Y and 220Y
400Y and 480Y
600Y
500
1000
1200
1000
2000
2500
500
1000
1200
1000
2000
2500
240D
480D
600D
N/A
N/A
N/A
1000
2000
2500
N/A
N/A
N/A
900
2000
2500
240H 500 1000 500 1000
Table 5. 80–100 kA Direct Bus Mounted Integrated Unit VPR
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 500 600 500 900
208Y and 220Y
400Y and 480Y
600Y
500
1000
1200
600
1200
1500
500
1000
1200
900
1800
2500
240D
480D
600D
N/A
N/A
N/A
1000
1800
2500
N/A
N/A
N/A
900
1800
2500
240H 500 600 500 900
Table 6. 120–200 kA Direct Bus Mounted Integrated Unit VPR
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 500 600 500 800
208Y and 220Y
400Y and 480Y
600Y
500
900
1200
600
1000
1200
500
900
1200
800
1800
2500
240D
480D
600D
N/A
N/A
N/A
900
1800
2500
N/A
N/A
N/A
900
1800
2500
240H 500 600 500 800
Table 7. 250–300 kA Circuit Breaker Interfaced Integrated Unit VPR
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 600
700 600 1000
208Y and 220Y
400Y and 480Y
600Y
600
1000
1500
700
1200
1500
600
900
1200
1000
1800
2500
240D
480D
600D
N/A
N/A
N/A
1000
1800
2500
N/A
N/A
N/A
1000
1800
2500
240H 600
700 600 1000
L-N VPR for 250–300 kA units containing the standard and standard with surge counter
feature packages is 600V. L-N VPR for units containing the basic feature package is 700V.
All other VPR numbers reported in all tables represent the VPR for all feature packages.
Table 8. 50 kA Circuit Breaker Interfaced Integrated Unit VPR
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 700 1200 700 1200
208Y and 220Y
400Y and 480Y
600Y
700
1200
1500
1200
2000
2500
700
1200
1500
1200
2000
2500
240D
480D
600D
N/A
N/A
N/A
1200
2000
2500
N/A
N/A
N/A
1200
2000
2500
240H 700 1200 700 1200
Table 9. 80–100 kA Circuit Breaker Interfaced Integrated Unit VPR
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 700 700 700 1000
208Y and 220Y
400Y and 480Y
600Y
700
1200
1500
700
1200
1500
700
1200
1500
1000
1800
2500
240D
480D
600D
N/A
N/A
N/A
1200
2000
2500
N/A
N/A
N/A
1200
2000
2500
240H 700 700 700 1000
Table 10. 120–200 kA Circuit Breaker Interfaced Integrated Unit VPR
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 700 700 600 1000
208Y and 220Y
400Y and 480Y
600Y
700
1000
1500
700
1200
1500
600
1000
1200
1000
1800
2500
240D
480D
600D
N/A
N/A
N/A
1000
2000
2500
N/A
N/A
N/A
1000
1800
2500
240H 700 700 600 1000
Table 11. 400 kA Circuit Breaker Interfaced Integrated Unit VPR
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 700 700 600 1000
208Y and 220Y
400Y and 480Y
600Y
700
1000
1500
700
1200
1500
600
900
1200
1000
1800
2500
240D
480D
600D
N/A
N/A
N/A
1000
1800
2500
N/A
N/A
N/A
1000
1800
2500
240H 700 700 600 1000
Performance data
ANSI/UL 1449 3rd Edition voltage protection ratings
Voltage protection rating (VPR) data is included for both direct bus mounted units (catalog number ending with ‘A’) and units interfaced to
the electrical assembly via a circuit breaker (catalog number ending with ‘B,’ ‘C,’ or ‘J’). Direct bus mounted units are available for installation
within Eaton PRL1a, 2a, 3a, and 3E panelboards only.