Cut Sheet

7
Technical Data TD01005025E
Effective June 2010
Eaton’s SPD Series for mounting external to
electrical distribution equipment
EATON CORPORATION www.eaton.com
Table 22. 50 kA Unit VPR (Cat. No. Ends with 1N or 1P)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 700 1200 700 1200
208Y and 220Y 700 1200 700 1200
400Y and 480Y 1200 2000 1000 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 2000 N/A 2500
600D N/A 2500 N/A 2500
240H 700 1200 700 1200
Table 23. 80–100 kA Unit VPR (Cat. No. Ends with 1N or 1P)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 700 800 700 1200
208Y and 220Y 700 800 700 1200
400Y and 480Y 1200 1200 1000 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 2000 N/A 2500
600D N/A 2500 N/A 2500
240H 700 800 700 1200
Table 24. 120–200 kA Unit VPR (Cat. No. Ends with 1N or 1P)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 700 800 700 1200
208Y and 220Y 700 800 700 1200
400Y and 480Y 1200 1200 1000 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 2000 N/A 2500
600D N/A 2500 N/A 2500
240H 700 800 700 1200
Table 25. 250–300 kA Unit VPR (Cat. No. Ends with 1N or 1P)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 700 800 700 1200
208Y and 220Y 700 800 700 1200
400Y and 480Y 1200 1200 1200 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 1800 N/A 2000
600D N/A 2500 N/A 2500
240H 700 800 700 1200
Table 26. 400 kA Unit VPR (Cat. No. Ends with 1N or 1P)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 700 800 700 1200
208Y and 220Y 700 800 700 1200
400Y and 480Y 1200 1200 1200 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 1800 N/A 2000
600D N/A 2500 N/A 2500
240H 700 800 700 1200
Table 27. 50 kA Unit VPR (Cat. No. Ends with 2N, 2P, 3N, or 3P)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 900 1500 700 1500
208Y and 220Y 900 1500 700 1500
400Y and 480Y 1200 2000 1000 2500
600Y 1500 1500 1500 2500
240D N/A 1000 N/A 1000
480D N/A 2500 N/A 2500
600D N/A 3000 N/A 2500
240H 900 1500 700 1500
Table 28. 80–100 kA Unit VPR (Cat. No. Ends with 2N, 2P, 3N, or 3P)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 900 900 700 1500
208Y and 220Y 900 900 700 1500
400Y and 480Y 1200 1200 1000 2500
600Y 1500 1500 1500 2500
240D N/A 1000 N/A 1000
480D N/A 2500 N/A 2500
600D N/A 3000 N/A 2500
240H 900 900 700 1500
Table 29. 120–200 kA Unit VPR (Cat. No. Ends with 2N, 2P, 3N, or 3P)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 900 900 700 1500
208Y and 220Y 900 900 700 1500
400Y and 480Y 1200 1200 1000 2500
600Y 1500 1500 1500 2500
240D N/A 1000 N/A 1000
480D N/A 2500 N/A 2500
600D N/A 2500 N/A 2500
240H 900 900 700 1500
Table 30. 250300 kA Unit VPR (Cat. No. Ends with 2N, 2P, 3N, or 3P)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 800 900 700 1500
208Y and 220Y 800 900 700 1500
400Y and 480Y 1200 1200 1000 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 2000 N/A 2000
600D N/A 2500 N/A 2500
240H 800 900 700 1500
Table 31. 400 kA Unit VPR (Cat. No. Ends with 2N, 2P, 3N, or 3P)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 800 900 700 1500
208Y and 220Y 800 900 700 1500
400Y and 480Y 1200 1200 1000 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 2000 N/A 2000
600D N/A 2500 N/A 2500
240H 800 900 700 1500
VPR data for units in a NEMA 4 or 4X enclosure without an internal disconnect (catalog number ends with N or P)