Cut Sheet
5
Technical Data TD01005025E
Effective June 2010
Eaton’s SPD Series for mounting external to
electrical distribution equipment
EATON CORPORATION www.eaton.com
Table 2. 50 kA Unit VPR (Cat. No. Ends with 1K or 1L)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 700 1200 700 1200
208Y and 220Y 700 1200 700 1200
400Y and 480Y 1200 2000 1200 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 2000 N/A 2500
600D N/A 2500 N/A 2500
240H 700 1200 700 1200
Table 3. 80–100 kA Unit VPR (Cat. No. Ends with 1K or 1L)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 700 700 700 1200
208Y and 220Y 700 700 700 1200
400Y and 480Y 1200 1200 1200 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 2000 N/A 2500
600D N/A 2500 N/A 2500
240H 700 700 700 1200
Table 4. 120–200 kA Unit VPR (Cat. No. Ends with 1K or 1L)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 700 700 700 1200
208Y and 220Y 700 700 700 1200
400Y and 480Y 1200 1200 1200 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 2000 N/A 2500
600D N/A 2500 N/A 2500
240H 700 700 700 1200
Table 5. 250–300 kA Unit VPR (Cat. No. Ends with 1K or 1L)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 700 700 700 1000
208Y and 220Y 700 700 700 1000
400Y and 480Y 1200 1200 1200 1800
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 1800 N/A 2000
600D N/A 2500 N/A 2500
240H 700 700 700 1000
Table 6. 400 kA Unit VPR (Cat. No. Ends with 1K or 1L)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 700 700 700 1000
208Y and 220Y 700 700 700 1000
400Y and 480Y 1200 1200 1200 1800
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 1800 N/A 2000
600D N/A 2500 N/A 2500
240H 700 700 700 1000
Table 7. 50 kA Unit VPR (Cat. No. Ends with 2K, 2L, 3K, or 3L)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 700 1200 700 1200
208Y and 220Y 700 1200 700 1200
400Y and 480Y 1200 2000 1200 2500
600Y 1500 1500 1500 2500
240D N/A 1000 N/A 1000
480D N/A 2500 N/A 2500
600D N/A 3000 N/A 2500
240H 700 1200 700 1200
Table 8. 80–100 kA Unit VPR (Cat. No. Ends with 2K, 2L, 3K, or 3L)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 700 800 700 1200
208Y and 220Y 700 800 700 1200
400Y and 480Y 1200 1200 1200 2500
600Y 1500 1500 1500 2500
240D N/A 1000 N/A 1000
480D N/A 2500 N/A 2500
600D N/A 3000 N/A 2500
240H 700 800 700 1200
Table 9. 120–200 kA Unit VPR (Cat. No. Ends with 2K, 2L, 3K, or 3L)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 600 800 600 1000
208Y and 220Y 600 800 600 1000
400Y and 480Y 1200 1200 1200 1800
600Y 1500 1500 1500 2500
240D N/A 1000 N/A 1000
480D N/A 2500 N/A 2500
600D N/A 2500 N/A 2500
240H 700 800 700 1200
Table 10. 250–300 kA Unit VPR (Cat. No. Ends with 2K, 2L, 3K, or 3L)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 600 800 600 1000
208Y and 220Y 600 800 600 1000
400Y and 480Y 1000 1200 1000 1800
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 1800 N/A 2000
600D N/A 2500 N/A 2500
240H 600 800 600 1000
Table 11. 400 kA Unit VPR (Cat. No. Ends with 2K, 2L, 3K, or 3L)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 600 700 600 1000
208Y and 220Y 600 700 600 1000
400Y and 480Y 1000 1200 1000 1800
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 1800 N/A 2000
600D N/A 2500 N/A 2500
240H 600 800 600 1000
VPR data for units in a NEMA 1 enclosure without an internal disconnect (catalog number ends with K or L)