Instruction manual

7
Instruction Manual IM01005022E
Effective September 2013
Installation Instructions for Eaton Surge Protective
Device xxPHxxxxx and xxPVxxxxx
EATON www.eaton.com
Specifications
Table 3. Specifications
Application
Eaton PH
2W +G Grounded Systems
Eaton PV
2W +G Grounded Systems
Input Voltage 120V, 220V, 240Vac single-phase 120V, 220V, 240Vac single-phase
Amperage 3, 5, 10, 15, & 20 amperes 1, 3, 5 amperes
Frequency 50/60 Hz 50/60 Hz
Protection Modes L-N, L-G, & N-G L-N, L-G, & N-G
MCOV 150V & 275V 150V & 275V
Noise Attenuation (Normal Mode) 75dB @ 110 KHz 50dB @ 100 KHz
Filter Bandwidth 10 kHz to 100 MHz 10 kHz to 100 MHz
Total Peak Surge Current 30kA per mode 20kA per mode
Operating Temperature -40°F to +122°F (-40°C to +50°C) -40°F to +122°F (-40°C to +50°C)
Response Time Less than one nanosecond Less than one nanosecond
Agency Approvals UL 1449 3
rd
Edition, UL 1283 5
th
Edition, CSA UL 1449 3
rd
Edition, UL 1283 5
th
Edition , CSA
Warranty 10 years standard / 5 additional years if registered on-line ** 10 years standard / 5 additional years if registered on-line**
Form C Contacts Yes No
External Circuit Breaker* Eaton P/N: WMZT1C25 or equiv. 25 amp circuit breaker Eaton P/N: WMZT1C07 or equiv. 7 amp circuit breaker
RoHS Compliant Yes Yes
*External circuit breaker sold separately.
**Register products on-line at www.eaton.com/spd. Then click on “Warranty Registration”.
Diagnostics
The Eaton PH and PV are supplied with a green LED that will illumi-
nate and indicate power at the output terminals. If the green LED is
not illuminated, it indicates that power is not being supplied to the
device. The LED will not illuminate if there has been a utility power
failure, or an internal failure of the suppression components. If the
internal suppression components fail, a short circuit will result. The
short circuit will open the overcurrent device on the power supply,
removing power to the device. Whenever power is removed from
an Eaton PH or PV device the green LED will not illuminate and the
optional monitoring relay (Form C contact), if installed, will change
state.
Maintenance
Preventive Maintenance (Inspection and Cleaning) – Periodic
system inspections, cleaning, and connection checks are recom-
mended to ensure reliable system performance. There is no defined
schedule for preventive maintenance, as conditions will vary from
installation to installation.
Corrective Maintenance (Repair or Replacement) – the Eaton
PH and PV are designed to provide years of continuous service.
However, even the most reliable equipment may fail. In the unlikely
case that the LED monitor or remote monitoring (Form C contact)
indicates a failure, check the overcurrent protection on the power
supply. Replace or reset the overcurrent protection. If a problem
still exists, contact Eaton’s Surge Protection application support at:
1-800-809-2772, option 4, option 2.