Instruction manual

5
Instruction Manual IM01005022E
Effective September 2013
Installation Instructions for Eaton Surge Protective
Device xxPHxxxxx and xxPVxxxxx
EATON www.eaton.com
Enclosure Mounting (Existing Aegis VL
applications)
CAUTION
THE INPUT AND OUTPUT TERMINAL LOCATIONS ARE NOT POSITIONED
ON THE SAME SIDE OF THE ENCLOSURE TOP COVER AS THE FORMER
AEGIS VL MODELS. ROUTE WIRING TO ACCOMMODATE THE NEW INPUT
AND OUTPUT TERMINAL LOCATIONS.
Aegis VL devices mounted to a DIN Rail using the attached DIN clip.
Remove the existing device from the DIN Rail by placing a screw
driver in slot on the DIN Clip (Output side at base), pulling the DIN
Clip out to release the enclosure from the DIN Rail. Now install the
Eaton PV device using the attached DIN clip mounted on the bottom
of the enclosure. Engage the Eaton PV base (Output side, enclo-
sure bottom) of the DIN Clip to the DIN Rail and compress DIN clip
spring by pushing the enclosure towards the Input terminal side of
the enclosure until the opposite side of the DIN Clip hook engages.
Then slowly release the spring pressure securing the Eaton PV
enclosure to the DIN Rail.
Wiring Instructions Eaton PV - Install an overcurrent protection
device on the input side of the Eaton PV. Wire the overcurrent pro-
tection device to the input terminal(s) of the Eaton PV. The terminals
are marked L, N, and G. Wire gauge should be selected to match
the amperage of the overcurrent protection device. Ensure that the
proper color wire is used (green or green/yellow – ground, white or
light blue – neutral, black and/or red – phase). Wire from the Eaton
PV output terminals to the input terminals of the protected load.
Tighten all input and output terminal connections to 9 lb-in. Install
terminal block covers by pressing into place on both the input and
output terminals. Recheck all connections. Restore power to the
electrical circuit. Check that the status indicator (Green LED) is illu-
minated.
Figure 4. PV Model Dimensions.
.