Use and Care Manual
CORE Lighting Controls
v. Controls shall incorporate power-failure memory. Should power be interrupted and subsequently
returned, the lights or fans will come back on to the same levels set prior to the power interruption.
Restoration to some other default level is not acceptable.
w. Controls shall not be susceptible to damage or loss of memory due to static discharge.
x. Controls shall operate in an ambient temperature range of 0°C (32°F) to 40°C (104°F).
y. 3-Way controls shall wire using conventional 3-way and 4-way wire runs.
2. Incandescent & Magnetic Low Voltage (MLV) Transformer Dimmers
a. Provide unit operating as single-pole/3-way incandescent/magnetic low voltage dimmers in 600
Watts (RF9534-N) and 1000 Watts (RF9536-N) capacities. Units shall require neutral connection.
b. Provide unit operating as single-pole/3-way incandescent dimmers in 600 Watts (RF9534) and 1000
Watts (RF9536) capacities. Eco-saver feature will only allow for a maximum light output of 85%. Units
shall not require neutral connection.
c. Dimmer shall be capable of being wired as either a single-pole or configured as a 3-way device.
3. Electronic (Solid State) Low Voltage (ELV) Transformer Dimmers
a. Provide ELV dimmers for direct control of up to 600 watts (RF9535-N) and 1000 watts (RF9537-N)
of electronic low voltage load. Units shall require a neutral connection.
b. Dimmer shall be capable of being wired as either a single-pole or 3-way device.
c. Dimmers shall contain circuitry specifically designed to control the input of electronic (solid state)
low voltage transformers.
d. Dimmers shall be designed to withstand a short, per UL 1472 section 5.10, between load hot and
either neutral or ground without damage to the dimmer.
4. Fluorescent Dimming Ballast Dimmers
a. Provide 1000W (RF9537-N) programmable ELV/Fluorescent dimmer for direct control of fluorescent
dimming ballasts up to the manufacturers specified rating.
b. Dimmer shall be designed to operate the following ballasts:
1) Advance Mark 10® Powerline
2) Advance Ambistar®
3) Tu-Wire™ High Performance Dimming Ballasts (5% 2-wire)
c. Dimmer shall be capable of being wired as either a single-pole or configured as a 3-way device.
B. ASPIRE RF Accessories
1. ASPIRE RF Switch Components
a. Switches shall provide on/off control of any 120 VAC load up to 15A.
b. Switches shall be cULus Listed as general-use AC switches
c. Switches (RF9501) shall be wired as either a single-pole or configured as /multi-location
configuration with up to 5 Accessories (RF9517)
d. Non-neutral 8A switch (RF9518) shall be available wired as either a single-pole or in a multi-
location configuration with up to 3 Remotes (RF9520).
e. Accessory switches shall be available in both RF (RF9517) and Non-RF (RF9520) configurations.
2. ASPIRE RF Receptacle Components
a. All receptacles shall be cULus Listed and NOM approved.
b. Receptacles shall be two-pole, three wire ground and rated for 15A at 125VAC. All receptacles shall
be NEMA configuration type 5-15R.
c. Receptacles shall be available in duplex, single outlet control (RFTR9505-T) models.
d. All receptacles shall provide compliance with the 2008 NEC® section 406.11 specification that
states all receptacles installed in dwelling units must be tamper resistant.
3. ASPIRE Telephone Jack and Cable TV Jack Components
a. Contractor shall provide an appropriate barrier (partition) to isolate jack from high-voltage wiring
when ganged with a dimmer, fan-speed control, switch, or receptacle. This complies with NEC Articles
800-3 and 820-13.