Technical data

CA05001001K For more information visit: www.EatonElectrical.ca
51
PLC, I/O & Communications Products
February 2007
IT. Connect
Starter Network Adapters (SNAP) (D77B Series) — DeviceNet SNAP
DeviceNet Starter Network
Adapter Product (DSNAP)
Product Description
The Cutler-Hammer
®
DeviceNet Starter
Network Adapter Product (DSNAP)
from Eaton’s electrical business is a
front-mount device that serves as a
single node on DeviceNet, providing
communication capability, control and
monitoring to Intelligent Technologies
(IT.) Electromechanical Starters, as
well as the S751 and S752 Soft Start,
as listed in Tables 68 70.
The IT. DSNAP has an optional HANDS/
OFF/AUTO (HOA) module that enables
the starter to be operated in hand
mode; even if the DSNAP is not pow-
ered. The HOA option is used for cus-
tomers who need the extra security of
manual control in conjunction with the
communication capabilities of
DeviceNet.
With the addition of a D64 zero
sequence CT, the DSNAP can be
enabled to detect ground faults for
added protection.
Features
Communication to DeviceNet con-
suming one DeviceNet MAC ID
Manually set MAC ID and baud rate;
configuration using a software
application is not required for nor-
mal operation
Advanced configuration using
CH Studio
Includes pre-wired starter intercon-
nect cable and terminal adapter
Comprehensive Motor Data and
Control
RMS average current
% of operating FLA
% thermal memory
Integral contact position detection
Operating status and fault codes
At speed (soft starters)
START/STOP control
RUN/FORWARD-REVERSE control
Trip Reset
Extended Starter Capabilities
Ground fault detection (with
accessory)
Fault log
Overcurrent warning (adjustable)
Undercurrent warning (adjustable)
Figure 67. Typical DSNAP Application
Catalogue Number D77B-DSNAP-
X3
IT. Starter
with
DSNAP
DeviceNet
Table 68. IEC SNAP Connectivity
Table 69. NEMA SNAP Connectivity
Table 70. S751/S752 SNAP Connectivity
Application Description
In a typical application, the DSNAP
front mounts to an IT. starter or soft
start. The DSNAP connects directly to
DeviceNet, allowing for control and
monitoring of the starter/soft start. A
PC or PLC serves as the central control
and scans the DSNAP for motor con-
trol and monitoring information. The
HOA module provides for the ability
to locate operators on the panel for
manual operation.
IEC E101, E501
Frame Size Continuous
Ampacity
Rating
45 mm B 18 Amp
25 Amp
32 Amp
54 mm C 40 Amp
50 Amp
76 mm D 65 Amp
85 Amp
100 Amp
105 mm E 125 Amp
160 Amp
200 Amp
140 mm F 250 Amp
315 Amp
420 Amp
NEMA N101, N501
Size Continuous Ampacity
Rating
00 9
0 18
1 27
2 45
3 90
4 135
5 270
S751/S752 Soft Start
54 mm All Sizes