Datasheet

Residual ripple and switching peaks < 50 mVpp / < 150 mVpp
Can be switched in parallel for redundancy, with O ring diode (PSG480R24RM/PSG960R24RM)
General characteristics
Housing Aluminium
Status indication green LED for "DC OK"
MTBF (mean time between failures) > 1,000,000 h
Height mm 121
Width mm 32
Depth mm 125
Weight kg 0.37
Terminations Screw terminal, pluggable
Stripping length mm 7
Terminal capacity
flexible with ferrules/solid
mm
2
0.32 - 3.3 mm² (AWG 22 -12)
Tightening torque Nm 0.5
Ambient air temperature range °C
Operation °C -20 - +80 (> 50 °C derating)
Storage, transport ϑ °C
Storage ϑ °C -25 - +85
damp heat < 95 % relative humidity at +25 °C, no condensation
Vibrations (IEC/EN 60068-2-6) 10 - 500 Hz at 30 m/s² (3 G max ) for 60 min. in X-axis, Y-axis, Z-axis directions
Mechanical shock resistance (IEC 60068-2-27) 30 g (300 m/s²) in all directions
Pollution degree 2
Climatic class (IEC) 3K3 according to EN 60721
Safety and safety features
Transient overvoltage protection Varistor
Current limitation at short-circuit I
Überstrom
= 150 % der max. Ausgangsleistung
Overvoltage protection Yes, against internal overvoltage
Insulation voltage
Input/Output 4 kV AC (type test), 3 kV AC (routine test)
Input/PE 1.5 kV AC (type test), 1.5 kV AC (routine test)
Output/PE 1.5 kV AC (type test), 500 V AC (routine test)
Degree of Protection IP20
Protection class Class I with PE connection
Standards
Electrical equipment of machines: IEC60204-1 (Overvoltage category III)
Equipping power installations with electronic apparatus: EN 50178/IEC 62103
Safety extra-low voltage: PELV (EN 60204), SELV (EN 60950)
Protection against electric shock: DIN 57100-410
CE: according to EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
RoHS-compliant: RoHS Directive 2011/65/EU
ITE: EN 55022, EN 61000-3-2, EN 61000-3-3, EN 55024
Industrial: EN 55011
Mains harmonics limitation: EN 601000-3-2
Electrical Safety (of IT equipment) : SIQ to EN60950-1, UL/c-UL recognized to UL
60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1
UL508
Class2: UL/c-UL recognized to UL1310 and CSA C22.2 No. 223 |
Component power supply unit for general use: EN61204-3
Approvals EAC
Design verification as per IEC/EN 61439
Technical data for design verification
Static heat dissipation, non-current-dependent P
vs
W 7.4
Operating ambient temperature min. °C -20
Operating ambient temperature max. °C 80
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
01/30/2020 Eaton 172891 ED2020 V64.0 EN 2 / 4