Inputs/Outputs, EZ700/800/EZD Operating Mode
MN05013001E36
“Inputs 3 bytes” module:
operating mode, S1 – S8
The normal PROFIBUS-DP master data exchange with the
EZ204-DP slave is via input data bytes 0, 1, 2.
Requirement:
The “Inputs, 3 bytes” module must have been selected.
The master reads bytes 0, 1, 2 for the following data:
Table 1: Byte 0: Operating mode
Example:
Byte Meaning Value
0 Scan the operating mode
J Table 1
1 Scan status of the EZ outputs S1 to
S8
J Table 2
2 Not assigned
00
hex
J
The output data and control commands can now only be
used if you have selected the appropriate modules as well.
EZ/EZD operating mode Bit
7 6 5 4 3 2 1 0
Stop/Run
with debounce 0 0 0 1 0 0 0 0/1
without debounce 0 0 1 0 0 0 0 0/1
Value 21
hex
EZ/EZD is in Run mode and is working with input
debounce.