User manual

For more information visit: www.EatonElectrical.com
EZ800/EZD Control Commands
MN05013001E156
Example
The channel A parameters of 7-day time switch HW19 are to
be read.
Byte Meaning Value (hex), sent by
Master Slave
0 Toggle byte 81 80
1 Command: Read
92
Response: Read
successful
C2
2Type
1C 1C
3 Instance 13 13
4 Index 02 02
5Data 1
00 62
6Data 2 00 0B
7Data 3 00 7B
8Data 4 00 25
Bit
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Date 2 = 0B
hex
Date 1 = 62
hex
ON 0 0 0 0 1 0 1 1 0 1 1 0 0 0 1 0
Weekday Hour Minute
Switch-on time:
Weekday = 01
hex
.. Monday
Hour = 0D
hex
.. 1300 hours
Minute = 22
hex
.. 34 minutes
Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Date 4 = 25
hex
Date 3 = 7B
hex
OFF 0 0 1 0 0 1 0 1 0 1 1 1 1 0 1 1
Weekday Hour Minute
Switch-off time:
Weekday = 04
hex
.. Thursday
Hour = 15
hex
.. 2100 hours
Minute = 59
hex
.. 34 minutes