User manual
Read/write function block data
For more information visit: www.EatonElectrical.comMN05013001E 145
Data function blocks DB01 .. DB32
Telegram structure
Byte Meaning Value (hex), sent by
Master Slave
0 Toggle byte J page 94
1Command:
Read 92 –
Write B2 –
Response:
Read successful – C2
Write successful – C1
Command
rejected
– C0
2Type 1A 1A
3 Instance 01 – 20 01 – 20
4 Index J Table 79 J Table 79
5 – 8 Data 1 – 4
Read operation 00 depending on
index,
J Table 80
Write operation
depending on
index,
J Table 80
00