EZ operating modes
For more information visit: www.EatonElectrical.comMN05013003E 63
EZ operating modes EZ has two operating modes - RUN and STOP.
In RUN mode EZ continuously processes a stored circuit
diagram until you select STOP or disconnect the power. The
circuit diagram, parameters and the EZ settings are retained
in the event of a power failure. All you will have to do is reset
the real-time clock after the back-up time has elapsed. Circuit
diagram entry is only possible in STOP mode.
When a memory card with a circuit diagram is fitted in an EZ
model with an LCD display, this circuit diagram will not start
automatically if there is circuit diagram in the device. The
circuit diagram must first be transferred from the memory card
to the EZ unit.
In RUN mode EZ-X models load the circuit diagram on the
memory card automatically and run it immediately.
Caution!
In RUN mode EZ will immediately run the saved circuit
diagram in the unit when the power supply is switched on.
This will happen unless STOP mode was set as startup
mode. In RUN mode outputs are activated according to the
switch logic of the circuit diagram.