Connecting the inputs
For more information visit: www.EatonElectrical.comMN05013003E 49
20 mA sensor
4 to 20 mA (0 to 20 mA) sensors can be connected easily
without any problem using an external 500 resistor.
Figure 22: Connection 0 (4) to 20 mA sensor output, analog input
Analog sensor
The following values apply:
4 mA = 1.9 V
10 mA = 4.8 V
20 mA = 9.5 V
(Based on U = R × I = 478 × 10 mA ~ 4.8 V).
Connecting high-speed counters and frequency
generators
High-speed counter signals and frequencies on the EZ-DA
and EZ-DC can be counted accurately on inputs I1 to I4
independently of the cycle time. These inputs are permanently
assigned to counters.
The following applies:
I1 = C13 high-speed up/down counter
I2 = C14 high-speed up/down counter
L01
F1
L01
500
4...20 mA
I7+...V
0 V0 V
DC : +24 V
DA : +12 V
EZ500_700.book Page 49 Tuesday, May 3, 2005 5:15 PM