User manual
For more information visit: www.EatonElectrical.com
Installation
MN05013003E44
Table 3: EZ-DC input signals
Table 4: EZ-DA input signals
Connecting EZ DC analog inputs
The EZ-AB, EZ-DA and EZ-DC basic units are provided with
analog inputs. Inputs I7 and I8, and if present I11 and I12, can
be used to connect analog voltages ranging from 0 V to 10 V.
A simple additional circuit also allows the analog evaluation of
currents from 0 to 20 mA. The analog input signals are
converted to 10-bit digital signals.
The following applies:
• 0 V DC corresponds to a digital 0.
• 5 V DC corresponds to a digital value of 512.
• 10 V DC corresponds to a digital value of 1023.
Input signal voltage range Input current
OFF signal ON signal
EZ500/
EZ700
I1 to I6 0 to 5 V 15 to 28.8 V 3.3 mA at 24 V DC
I7, I8 greater than 8 V DC 2.2 mA at 24 V
EZ700 I9, I10
15 to 28.8 V 3.3 mA at 24 V DC
I11, I12
greater than 8 V DC 2.2 mA at 24 V
EZ600 R1 to
R12
15 to 28.8 V 3.3 mA at 24 V DC
Input signal voltage range Input current
OFF signal ON signal
EZ500/
EZ700
I1 to I6 0 to 4 V DC 8 to 15.6 V DC 3.3 mA at 12 V
I7, I8
1.1 mA at 12 V
EZ700 I9, I10
3.3 mA at 12 V
I11, I12
1.1 mA at 12 V
EZ500_700.book Page 44 Tuesday, May 3, 2005 5:15 PM