User manual
Connecting the power supply
For more information visit: www.EatonElectrical.comMN05013003E 35
Supplying DC units
Supplying DC basic units
EZ…-DA-RC(X), EZ…-DC-R(RC,RCX)
Figure 6: Power supply on the DC basic units
Applies to EZ-AC devices with a power supply greater
than 24 V AC:
• The voltage terminals for phase L and neutral conductor
N have been reversed.
• This enables the EZ interface (for memory card or PC
connection) to have the full connection voltage of the
phase conductor (100 to 240 V AC).
• There is a danger of electric shock if the connection at the
EZ interface is not properly connected or if conductive
objects are inserted into the socket.
Attention!
A short current surge will be produced when switching on
for the first time. Do not switch on EZ by means of reed
contacts since these may burn or melt.
+...V
0 V0 V
L01⫺
F1
L01
⫹
DC : +24 V
DA : +12 V
EZ500_700.book Page 35 Tuesday, May 3, 2005 5:15 PM