User manual
For more information visit: www.EatonElectrical.com
Appendix
MN05013003E270
UL/CSA
Transistor outputs
EZ-512-D.-T…, EZ620-DC-.E, EZ72…
Uninterrupted current at 240 V AC/24 V DC 10/8 A
AC Control Circuit Rating Codes
(Utilization category)
B300 Light Pilot Duty
Max. rated operational voltage
300 V AC
Max. thermal continuous current cos ϕ = 1 with B300
5 A
Maximum make/break capacity cos ϕ ≠ 1(Make/break) with
B300
3600/360 VA
DC Control Circuit Rating Codes
(Utilization category)
R300 Light Pilot Duty
Max. rated operational voltage
300 V DC
Max. thermal uninterrupted current with R300
1 A
Maximum make/break capacity with R300
28/28 VA
EZ512-D.-T… EZ620-DC-.E, EZ72…
Number of outputs 4 8
Contacts
Semiconductors Semiconductors
Rated voltage U
e
24 V DC 24 V DC
Permissible range
20.4 to 28.8 V DC 20.4 to 28.8 V DC
Residual ripple
5 % 5 %
Supply current
0 signal Normally 9 mA/max. 16 mA Normally 18 mA/max. 32 mA
1 signal
Normally 12 mA, max. 22 mA Normally 24 mA, max. 44 mA
Reverse polarity protection
Yes, caution! If voltage is applied to the outputs when the polarity of
the power supply is reversed, this will result in a short circuit.
Potential isolation to mains
supply, inputs
Yes Yes
Rated current I
e
on 1 signal max. 0.5 A DC max. 0.5 A DC
Lamp load
5 Watts without R
V
5 Watts without R
V
EZ500_700.book Page 270 Tuesday, May 3, 2005 5:15 PM