User manual
Expanding EZ700
For more information visit: www.EatonElectrical.comMN05013003E 239
Example 3: Automatic reset of error signal
The circuit diagram functions in the same way as Example 2.
In addition the marker M16 is reset every 60 seconds by
timing relay T8 (on-delayed, 60 s). Should I16 remain at 1,
M16 will continue to be set. Q1 is set briefly to 1 until I16
switches off again.
Expanding EZ700 You can expand EZ700 with EZ618-..-RE, EZ202-RE or
EZ620-D.-TE modules locally or use the EZ200-EZ coupling
module for remote expansion.
For this first install the units and connect the inputs and
outputs (
J chapter “Installation”, page 29).
You process the inputs of the expansion devices as contacts
in the EZ circuit diagram in the same way as you process the
inputs of the basic unit. The input contacts are assigned the
operand identifiers R1 to R12.
R15 and R16 are the group fault alarms of the transistor
expansion unit (
J section “Monitoring of short-circuit/
overload with EZ..-D.-T..”, page 238).
The outputs are processed as relay coils or contacts like the
outputs in the basic unit. The output relays are S1 to S8.
The following bus modules can also be connected:
• EZ205-ASI (AS-Interface),
• EZ204-DP (PROFIBUS-DP),
• EZ221-CO (CANopen) or
• EZ222-DN (DeviceNet).
I1-m16----ÄQ1
I16-------SM16
M16-------TT8
T8-------RM16
M16-------ÄQ4
J
EZ618-..-RE provides the outputs S1 to S6. The other
outputs S7, S8 can be used as markers.
EZ500_700.book Page 239 Tuesday, May 3, 2005 5:15 PM