EZ500_700.book Page 1 Tuesday, May 3, 2005 5:15 PM EZ500/700 Series User Manual April 2005 Re-Order from OmegamationTM 1-888-55-66342 1-888-55-OMEGA omegamation.com MN05013003E For more information visit: www.EatonElectrical.
EZ500_700.
EZ500_700.book Page I Tuesday, May 3, 2005 5:15 PM Warning! Dangerous electrical voltage! Before commencing the installation • Disconnect the power supply of the device. • Ensure that devices cannot be accidentally restarted. • Verify isolation from the supply. • Short circuit to earth. • Cover or enclose neighboring units that are live. • Follow the engineering instructions (AWA) of the device concerned.
EZ500_700.book Page II Tuesday, May 3, 2005 5:15 PM • Devices that are designed for mounting in housings or control cabinets must only be operated and controlled after they have been installed with the housing closed. Desktop or portable units must only be operated and controlled in enclosed housings.
EZ500_700.
EZ500_700.
EZ500_700.
EZ500_700.
EZ500_700.
EZ500_700.
EZ500_700.book Page 7 Tuesday, May 3, 2005 5:15 PM 6 7 MN05013003E Inside EZ EZ circuit diagram cycle – EZ operation and effects on circuit diagram creation Delay times for inputs and outputs – Delay times with EZ-DA and EZ-DC basic units – Delay time with EZ-AB, EZ-AC basic units – Delay times for the analog inputs of EZ-AB, EZ-DA and EZ-DC Monitoring of short-circuit/overload with EZ..-D.-T..
EZ500_700.book Page 8 Tuesday, May 3, 2005 5:15 PM 8 Appendix Dimensions Technical Data – General – Special approvals – Power supply – Inputs – Relay outputs – Transistor outputs List of the function relays – Usable contacts – Available function relays – Names of relays – Names of function relay – Name of function block inputs (constants, operands) – Memory card attributes 255 255 258 258 260 261 262 268 270 273 273 274 275 275 Glossary 277 Index 281 For more information visit: www.EatonElectrical.
EZ500_700.book Page 9 Tuesday, May 3, 2005 5:15 PM About This Manual This manual describes the installation, commissioning and programming (circuit diagram generation) of the EZ500 and EZ700 control relay. Specialist electrical training is needed for commissioning and creating circuit diagrams. When active components such as motors or pressure cylinders are controlled, parts of the system can be damaged and persons put at risk if the device is connected or programmed incorrectly.
EZ500_700.book Page 10 Tuesday, May 3, 2005 5:15 PM About This Manual EZ-E for EZ2.._RE, EZ618-AC-RE, EZ618-DC-RE and EZ620-DC-TE EZSoft for EZSoftBasic and EZSoft Writing conventions Symbols used in this manual have the following meanings: X indicates actions to be taken. Attention! Warns of a hazardous situation that could result in damage to the product or components. Caution! Warns of the possibility of serious damage and slight injury.
EZ500_700.book Page 11 Tuesday, May 3, 2005 5:15 PM 1 Target readership EZ EZ must only be installed and connected up by trained electricians or other persons who are familiar with the installation of electrical equipment. Specialist electrical training is needed for commissioning and creating circuit diagrams. When active components such as motors or pressure cylinders are controlled, parts of the system can be damaged and persons put at risk if EZ is connected or programmed incorrectly.
EZ500_700.book Page 12 Tuesday, May 3, 2005 5:15 PM EZ Overview 2 3 4 1 2 5 10 POW 6 BUS POWER COM-ERR 7 ADR ERR 8 MS NS Figure 1: 12 9 EZ basic units and expansion devices For more information visit: www.EatonElectrical.
EZ500_700.book Page 13 Tuesday, May 3, 2005 5:15 PM Overview Legend for figure 1: EZ500 basic unit EZ700 I/O expansion EZ202-RE output expansion EZ200-EZ coupling device EZ-LINK-DS data connector EZ204-DP PROFIBUS-DP slave gateway EZ205-ASI AS-Interface slave gateway EZ221-CO CANopen gateway EZ222-DN DeviceNet gateway EZ700 basic unit EZ is an electronic control relay with logic functions, timer, counter and time switch functions.
EZ500_700.book Page 14 Tuesday, May 3, 2005 5:15 PM EZ If you prefer to wire up EZ from a PC, then use EZSoft. EZSoft allows you to create and test your circuit diagram on the PC. EZSoft is also used to print out your circuit diagram in DIN, ANSI or EZ format. 14 For more information visit: www.EatonElectrical.
EZ500_700.book Page 15 Tuesday, May 3, 2005 5:15 PM Overview Models EZ basic units at a glance 햲 DEL 햳 ALT 햸 햴 햵 ESC DEL OK ALT 햶 ESC Figure 2: MN05013003E OK 햷 Models Power supply Inputs Status LED Buttons Interface socket for memory card or PC connection Outputs LCD display For more information visit: www.EatonElectrical.
EZ500_700.book Page 16 Tuesday, May 3, 2005 5:15 PM EZ EZ basic units with stand-alone EZD-80.., EZD-CP4-500 HMI unit 1 2 3 4 3 Figure 3: 16 Overview with stand-alone HMI unit EZ500 basic units EZ700 basic units EZD device Power supply/communication module with EZD-CP4-500 interface cable For more information visit: www.EatonElectrical.
EZ500_700.book Page 17 Tuesday, May 3, 2005 5:15 PM Overview Type reference EZ x xx -xx-x x x LCD display: X = No display Time switch: C = Available; E = Expansion Output type: R = Relay (max. 8 A) T = Transistor (0.
EZ500_700.
EZ500_700.book Page 19 Tuesday, May 3, 2005 5:15 PM Overview Selecting main and system menu Status display EZ500: 8 inputs, 4 outputs I .2..5..... P1.2 MO 02:00 RS ..34 . RUN MO .2 6.. Current selection flashes in the EZ menu Clock menu on devices with clock and No password PROGRAM... STOPå RUN PARAMETER INFO... SET CLOCK SECURITY... SYSTEM... LANGUAGE... 1st menu level 1st menu level Main menu EZ500 or EZ700 System menu SECURITY... SYSTEM... LANGUAGE...
EZ500_700.book Page 20 Tuesday, May 3, 2005 5:15 PM EZ Toggling between weekday, time display and date display (only on devices with clock) .2..5....... PMO 11:50 ..34 RUN .2..5....... P01.04.2004 ..34 RUN EZ Status display .2..5....... PMO 11:50 Q ..34..STOP Inputs Weekday/Time Outputs 1.......9... RS .2..5...... P01.04.2002 Q ..34..STOP EZ500: input 1 to 8, EZ700: input 1 to 12 AC P- MO 10:42 1.....7.
EZ500_700.book Page 21 Tuesday, May 3, 2005 5:15 PM Overview Advanced Status display 12...6.89... Retention/Debounce RE I AC P- 17.03.04 ST 123.5.78 RUN RE I AC DC GW ST AC expansion ok/P buttons Startup behavior : : : : : Retention switched on Debounce switched on AC expansion functioning correctly DC expansion functioning correctly Bus coupling module detected GW flashes: Only EZ200-EZ detected. I/O expansion not detected. 17.03.
EZ500_700.book Page 22 Tuesday, May 3, 2005 5:15 PM EZ Menu structure Main menu without password protection XYou access the main menu by pressing OK. STOP: Circuit diagram display Main menu PROGRAM....Æ STOP å RUN PARAMETER INFO... æ SET CLOCK.. PROGRAM... DELETE PROG CARD The arrows indicate that there are more than four menus. Circuit diagram Parameter display SAVE CANCEL PROGRAM... DELETE PROG CARD... PROGRAM... DELETE PROG CARD...
EZ500_700.book Page 23 Tuesday, May 3, 2005 5:15 PM Overview Main menu PROGRAM....Æ STOP RUN å PARAMETER INFO... æ SET CLOCK.. PROGRAM....Æ STOP RUN å PARAMETER... INFO... æ SET CLOCK.. PROGRAM....Æ STOP RUN å PARAMETER... INFO... æ SET CLOCK.. PROGRAM... STOP RUN Æ PARAMETER INFO... SET CLOCK.æ MN05013003E Parameter display T1 X T2 Ü C1 N O1 S + M:S + + + T1 X S + S1 10.000 S2 +0 T: Information display of the device DC TC LCD OS: 1.00.027 CRC: 02752 Display for date and time setting SET CLOCK..
EZ500_700.book Page 24 Tuesday, May 3, 2005 5:15 PM EZ Main menu Only one selection is possible. PROGRAM... STOP RUN Æ PARAMETER... INFO... SET CLOCK.æ SET CLOCK.. SUMMER TIME. SET CLOCK.. SUMMER TIME. SET CLOCK.. SUMMER TIME. SET CLOCK.. SUMMER TIME. 24 NONE RULE... EU GB US åÆ NONE RULE... EU GB US Æ æ æ SUMMER START SUMMER END AM WD: --Æ --DD.MM:00.00æ HH:MM:00:00 DIFF: 0:00 NONE RULE... EU GB US Æ å NONE RULE...
EZ500_700.book Page 25 Tuesday, May 3, 2005 5:15 PM Overview Main menu with password protection Main menu Unlocking EZ Password entry PASSWORD.. Æ STOP RUN å PARAMETER... INFO... æ SET CLOCK.. DELETE ALL Password Example: Password only on program Four wrong entries (if enabled) Status display PASSWORD... STOP RUN å Correct entry EZ System menu The System menu is accessed by simultaneously pressing DEL and ALT. Password setup System menu Password entry SECURITY... SYSTEM... LANGUAGE...
EZ500_700.book Page 26 Tuesday, May 3, 2005 5:15 PM EZ System menu SECURITY... SYSTEM... LANGUAGE... CONFIGURATOR DEBOUNCE å P-BUTTONS RUN MODE å CARD MODE SECURITY... SYSTEM... LANGUAGE... CONFIGURATOR ENGLISH Æ DEUTSCH å FRANCAIS ESPANOL æ ITALIANO PORTUGUES NEDERLANDS SVENSKA POLSKI TURKCE CESKY MAGYAR SECURITY... SYSTEM... LANGUAGE... CONFIGURATOR 26 Only one selection is possible. The further menus depend on the connected expansion device For more information visit: www.EatonElectrical.
EZ500_700.book Page 27 Tuesday, May 3, 2005 5:15 PM Overview Selecting or toggling between menu items Cursor Í Ú PROGRAM... STOP PARAMETER INFO Select or toggle Cursor display MN05013003E HH:MM DD.MM YEAR '4:23 17.03 2004 HH:MM DD.MM YEAR 14:23 17.03 2004 The cursor flashes. Full cursor Ê/: • Move cursor with ú í, • in circuit diagram also with Í Ú Value M/ M • Change position with ú í • Change values with Í Ú Flashing values/menus are shown in gray in this manual.
EZ500_700.book Page 28 Tuesday, May 3, 2005 5:15 PM EZ Setting values HH:MM DD.MM YEAR 14:23 17.03 2004 Values Digits Current value at the position (can be changed, Cursor = 3) 28 Select value Í Ú Select digit ú í Change value at digit ÍÚ Store entries Retain previous value For more information visit: www.EatonElectrical.
EZ500_700.book Page 29 Tuesday, May 3, 2005 5:15 PM 2 Installation EZ must only be installed and wired up by trained electricians or other persons familiar with the installation of electrical equipment. Danger of electric shock Never carry out electrical work on the device while the power supply is switched on.
EZ500_700.book Page 30 Tuesday, May 3, 2005 5:15 PM Installation 30 For ease of wiring, leave a gap of at least 30 mm between EZ terminals and the wall or adjacent devices. 30 30 30 Figure 1: 1 Clearances to EZ Mounting on top-hat rail XHook EZ to the top edge of the top-hat rail and hinge into place while pressing down slightly. Press the device lightly downwards and against the top-hat rail until it snaps over the lower edge of the top-hat rail.
EZ500_700.book Page 31 Tuesday, May 3, 2005 5:15 PM Mounting Using a mounting plate Mounting on a mounting plate requires the use of fixing brackets which are fixed to the back of EZ. The fixing brackets are available as an accessory. EZ700: Fasten each device with at least three fixing brackets. EZ200-EZ: EZ500: EZ700: Figure 2: MN05013003E Using a mounting plate For more information visit: www.EatonElectrical.
EZ500_700.book Page 32 Tuesday, May 3, 2005 5:15 PM Installation Connecting the expansion device 1 2 4 3 Figure 3: 32 Connecting expansion units For more information visit: www.EatonElectrical.
EZ500_700.book Page 33 Tuesday, May 3, 2005 5:15 PM Terminals XOpen the EZ-LINK connections on the side of both EZ devices. XFit the EZ-LINK data connector EZ-LINK-DS in the opening provided on the expansion device. XPlug the devices together. XProceed in the reverse order to dismantle the device. Terminals Tools Slot-head screwdriver, width 3.5 mm, tightening torque 0.6 Nm. Cable cross-sections • Solid: 0.2 to 4 mm2 • Flexible with ferrule: 0.2 to 2.
EZ500_700.book Page 34 Tuesday, May 3, 2005 5:15 PM Installation Supplying AC units Supplying AC basic units EZ…-AB-RC(RCX), EZ…-AC-R(RC, RCX) L N F1 L Figure 4: N N Power supply on the AC basic units Supplying AC expansion units EZ…-AC-.E L N F1 E+ E- Figure 5: 34 R1 ... R12 L N N Power supply on the AC expansion units For more information visit: www.EatonElectrical.
EZ500_700.book Page 35 Tuesday, May 3, 2005 5:15 PM Connecting the power supply Applies to EZ-AC devices with a power supply greater than 24 V AC: • The voltage terminals for phase L and neutral conductor N have been reversed. • This enables the EZ interface (for memory card or PC connection) to have the full connection voltage of the phase conductor (100 to 240 V AC).
EZ500_700.book Page 36 Tuesday, May 3, 2005 5:15 PM Installation Supplying DC expansion units EZ…-DC-.E L01+ L01F1 E+ E- Figure 7: J R1 ... R12 24V 0V 0V 24 V Power supply on the DC expansion units EZ-DC and EZ-DA are protected against reverse polarity. To ensure that EZ works correctly, ensure that the polarity of each terminal is correct. Cable protection Connect on EZ a cable protection (F1) rated for at least 1 A (slow).
EZ500_700.book Page 37 Tuesday, May 3, 2005 5:15 PM Connecting the inputs Connecting the inputs EZ inputs switch electronically. Once you have connected a contact via an input terminal, you can reuse it as a contact in your EZ circuit diagram as often as you like. L +24 V S1 N 0V I1 I1 Figure 8: i1 Connecting the inputs Connect to the EZ input terminals contacts such as pushbuttons, switches, relay or contactor contacts, proximity switches (three-wire).
EZ500_700.book Page 38 Tuesday, May 3, 2005 5:15 PM Installation Connecting EZ AC digital inputs on the basic unit L N F1 L Figure 9: N N l1 I2 I7 Connecting EZ-AC and EZ-AB digital inputs Connecting AC digital inputs on the expansion device L N F1 E+ E- Figure 10: 38 R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 L N N Connecting EZ...-AC-E digital inputs For more information visit: www.EatonElectrical.
EZ500_700.book Page 39 Tuesday, May 3, 2005 5:15 PM Connecting the inputs Table 1: EZ-AB input signal values Input signal voltage range Input current OFF signal ON signal 0 to 6 V AC 14 to 26.4 V AC 4 mA at 24 V AC EZ500/ EZ700 I1 to I6 I7, I8 greater than 7 V AC or greater than 9.5 V DC 2 mA with 24 V AC and 24 V DC EZ700 I9, I10 14 to 26.4 V AC 4 mA at 24 V AC I11, I12 greater than 7 V AC or greater than 9.
EZ500_700.book Page 40 Tuesday, May 3, 2005 5:15 PM Installation For longer lengths connect in series a diode (e.g. 1N4007) for 1 A, min. 1000 V reverse voltage, to the EZ input. Ensure that the diode is pointing towards the input as shown in the circuit diagram, otherwise EZ will not detect the 1 state. L N F1 L Figure 11: N N I1 AC input with suppression diode for EZ-AC and EZ-AB EZ-AC: Inputs I7 and I8 have a higher input current on the EZ-AC.
EZ500_700.book Page 41 Tuesday, May 3, 2005 5:15 PM Connecting the inputs Increasing the input current The following input circuit can be used in order to prevent interference and also when using two-wire proximity switches: L N F1 100 nF/275 V h L Figure 12: J N N I1 Increasing the input current When using a 100 nF capacitor the drop-off time of the input increases by 80 (66.6) ms at 50 (60) Hz. A resistor can be connected in series with the circuit shown in order to restrict the inrush current.
EZ500_700.book Page 42 Tuesday, May 3, 2005 5:15 PM Installation Complete devices for increasing the input current are available under the type reference EZ256-HCI. L N F1 L N N Figure 14: J 1 I1 N EZ with EZ256-HCI The increased capacitance increases the drop-off time by approx. 40 ms. Connecting EZ DC digital inputs Use input terminals I1 to I12, R1 to R12 to connect pushbutton actuators, switches or 3 or 4-wire proximity switches.
EZ500_700.book Page 43 Tuesday, May 3, 2005 5:15 PM Connecting the inputs Connecting DC digital inputs on the basic unit L01⫹ L01⫺ F1 +...V 0V l1 I2 I7 DC : +24 V DA : +12 V Figure 15: Connecting EZ-DC, EZ-DA digital inputs Connecting DC digital inputs on the expansion device +24 V 0V F1 E+ E- R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 +24V 0V 0V Input 24 V 24 V EZ…-DC-.D Figure 16: MN05013003E Connecting EZ...-DC-E digital inputs For more information visit: www.EatonElectrical.
EZ500_700.book Page 44 Tuesday, May 3, 2005 5:15 PM Installation Table 3: EZ-DC input signals Input signal voltage range Input current OFF signal ON signal 0 to 5 V 15 to 28.8 V 3.3 mA at 24 V DC EZ500/ EZ700 I1 to I6 I7, I8 greater than 8 V DC 2.2 mA at 24 V EZ700 I9, I10 15 to 28.8 V 3.3 mA at 24 V DC I11, I12 greater than 8 V DC 2.2 mA at 24 V R1 to R12 15 to 28.8 V 3.
EZ500_700.book Page 45 Tuesday, May 3, 2005 5:15 PM Connecting the inputs Caution! Analog signals are more sensitive to interference than digital signals. Consequently, greater care must be taken when laying and connecting the signal lines. Incorrect switching states may occur if they are not connected correctly. Safety measures with analog signals XUse shielded twisted pair cables to prevent interference with the analog signals.
EZ500_700.book Page 46 Tuesday, May 3, 2005 5:15 PM Installation Power supply of EZ-AB devices and analog inputs With EZ-AB devices that process analog signals, the device must be fed via a transformer so that the device is isolated from the mains supply. The neutral conductor and the reference potential of the DC power feed of analog sensors must be electrically connected. J Ensure that the common reference potential is grounded or monitored by a ground fault monitoring device.
EZ500_700.book Page 47 Tuesday, May 3, 2005 5:15 PM Connecting the inputs Analog setpoint potentiometer, EZ-AB, EZ-DA, EZ-DC ~ F1 0V +...V L Figure 18: 0V N +12 V I7 0V N Analog setpoint potentiometer with own power feed Use a potentiometer with a resistance of 0.25 W. 1 kΩ, e.g. 1 kΩ, EZ-DC analog setpoint potentiometer L01⫹ L01⫺ 1.3 kO/0.25 W F1 1 kO/0.25 W +...
EZ500_700.book Page 48 Tuesday, May 3, 2005 5:15 PM Installation Brightness sensor, EZ-AB, EZ-DA, EZ-DC ~ 12 V 0...10 V F1 0V 0V +...V L 0V N Figure 20: +12 V I7 0V N Connection of a brightness sensor, analog input Temperature sensor, EZ-DA, EZ-DC +24 V –0 V Out 0...10 V F1 +...V L Figure 21: 48 0V N 0V N –35...55 ˚C I7 Connection of the temperature sensor, analog input For more information visit: www.EatonElectrical.
EZ500_700.book Page 49 Tuesday, May 3, 2005 5:15 PM Connecting the inputs 20 mA sensor 4 to 20 mA (0 to 20 mA) sensors can be connected easily without any problem using an external 500 Ω resistor. L01⫹ L01⫺ 햲 F1 4...20 mA 500 +...V 0V 0V I7 DC : +24 V DA : +12 V Figure 22: Connection 0 (4) to 20 mA sensor output, analog input Analog sensor The following values apply: • 4 mA = 1.9 V • 10 mA = 4.8 V • 20 mA = 9.5 V (Based on U = R × I = 478 Ω × 10 mA ~ 4.8 V).
EZ500_700.book Page 50 Tuesday, May 3, 2005 5:15 PM Installation • I3 = C15 frequency counter • I4 = C16 frequency counter Pulse shape of count signals: EZ processes square wave signals. Mark-to-space ratio of count signals: We recommend a mark-to-space ratio of 1:1. If this is not the case: The minimum pulse or pause duration is 0.5 ms. tmin = 0.5 × (1/fmax) tmin = minimum time of the pulse or pause duration fmax = maximum count frequency (1 kHz) L01 + L01 – L02 + F1 ...
EZ500_700.book Page 51 Tuesday, May 3, 2005 5:15 PM Connecting the outputs J Inputs that are used as high-speed counter inputs should not be used in the circuit diagram as contacts. If the counter frequency is high: Not all the signals of the high-speed counter can be monitored for processing in the circuit diagram. EZ will only process a randomly logged state. Connecting the outputs The Q outputs function inside EZ as isolated contacts.
EZ500_700.book Page 52 Tuesday, May 3, 2005 5:15 PM Installation Connecting relay outputs EZ512-..-R.. 1 2 1 Q1 1 2 2 Q3 Q2 1 2 L R Q4 24 V H 8 A 115 V h 8 A 230 V h 8 A 10 000 000 2A 2A 2A 1000 W 0 V H, N 10 x 58 W 25 000 F 8 A/B 16 L1, L2, L3 (115/230 V h) + 24 V H Figure 25: EZ512-..-R.. relay outputs EZ7..-..-R..
EZ500_700.book Page 53 Tuesday, May 3, 2005 5:15 PM Connecting the outputs EZ618-..-RE 1 2 S1 1 2 S2 1 2 S3 1 2 1 2 S4 S5 1 2 S6 10 000 000 R 24 V H 8 A 115 V h 8 A 230 V h 8 A 2A 2A 2A 1000 W 0 V H, N 10 x 58 W 25 000 F 8 A/B 16 L1, L2, L3 (115/230 V h) + 24 V H Figure 27: EZ618-..-RE.. relay outputs Unlike the inputs, the outputs can be connected to different phases. Warning! Do not exceed the maximum voltage of 250 V AC on a relay contact.
EZ500_700.book Page 54 Tuesday, May 3, 2005 5:15 PM Installation Connecting transistor outputs EZ512-..-T.. +24 VQ 0 VQ Q1 Q2 Q3 Q4 F10 A 0VH f 2.5 A + 24 V H 20.4 – 28.8 V H Figure 28: 24 V R L 0.5 A 0.5 A 5 W/24 V EZ512-..-T.. transistor outputs EZ7..-..-T.. +24 VQ 0 VQ Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 F10 A 0VH R f 2.5 A + 24 V H (20.4 – 28.8 V H) 24 V H 0.5 A 0.5 A 5 W/24 V Figure 29: 54 EZ7..-..-T.. transistor outputs For more information visit: www.EatonElectrical.
EZ500_700.book Page 55 Tuesday, May 3, 2005 5:15 PM Connecting the outputs EZ620-..-TE S1 S2 S3 S4 S5 S6 S7 S8 +24 VQ 0VQ F10 A 0VH R + 24 V H (20.4 – 28.8 V H) 24 V H 0.5 A 0.5 A f 2.5 A 5 W/24 V Figure 30: EZ620-..-TE transistor outputs Parallel connection: Up to four outputs can be connected in parallel in order to increase the power. The output current will increase in this case to a maximum of 2 A.
EZ500_700.book Page 56 Tuesday, May 3, 2005 5:15 PM Installation If inductive loads are not suppressed, the following applies: Several inductive loads should not be switched off simultaneously to avoid overheating the driver blocks in the worst possible case.
EZ500_700.book Page 57 Tuesday, May 3, 2005 5:15 PM Expanding inputs/outputs Expanding inputs/outputs You can add expansion units to the following EZ models in order to increase the number of inputs and outputs: Expandable EZ basic units Expansion units EZ7..-..-R.. EZ7..-..-T.. EZ618-..-RE 115/230 V AC power supply • 12 AC inputs, • 6 relay outputs 24 V DC power supply • 12 DC inputs, • 6 relay outputs EZ620-..
EZ500_700.book Page 58 Tuesday, May 3, 2005 5:15 PM Installation Warning! The following electrical isolation is implemented between the EZ7..-..-.C.
EZ500_700.book Page 59 Tuesday, May 3, 2005 5:15 PM Expanding inputs/outputs E+ E– EZ6…-RE EZ6…-TE EZ719-… EZ721-… EZ200-EZ E+ E– Ue = 300/500 V EZ…-AC-…E Figure 33: J MN05013003E Connecting remote expansion units to EZ Terminals E+ and E- of the EZ200-EZ are protected against short-circuits and polarity reversal. Functionality is only ensured if “E+” is connected with “E+” and “E-” with “E-”. For more information visit: www.EatonElectrical.
EZ500_700.book Page 60 Tuesday, May 3, 2005 5:15 PM Installation Connecting bus systems The EZ-LINK connection is designed to allow bus connections, apart from I/O expansions. Special bus connection devices are available for the bus systems in use. J Only one device (expansion device or bus connection) can be connected to the EZ-LINK connection.
EZ500_700.
EZ500_700.book Page 62 Tuesday, May 3, 2005 5:15 PM Commissioning Setting the menu language ENGLISH DEUTSCH å FRANCAIS ESPANOL When you switch on EZ for the first time, you will be asked to select the menu language. XUse the cursor buttons Í or Ú to select the language required. – English – German – French – Spanish – Italian – Portuguese – Dutch – Swedish – Polish – Turkish – Czech – Hungarian XPress OK to confirm your choice and press ESC to exit the menu. EZ will then switch to the Status display.
EZ500_700.book Page 63 Tuesday, May 3, 2005 5:15 PM EZ operating modes EZ operating modes EZ has two operating modes - RUN and STOP. In RUN mode EZ continuously processes a stored circuit diagram until you select STOP or disconnect the power. The circuit diagram, parameters and the EZ settings are retained in the event of a power failure. All you will have to do is reset the real-time clock after the back-up time has elapsed. Circuit diagram entry is only possible in STOP mode.
EZ500_700.book Page 64 Tuesday, May 3, 2005 5:15 PM Commissioning Creating your first circuit diagram The following small circuit diagram takes you step by step through wiring up your first EZ circuit diagram. In this way you will learn all the rules, quickly enabling you to use EZ for your own projects. As with conventional wiring, you use contacts and relays in the EZ circuit diagram. With EZ, however, you no longer have to connect up components individually.
EZ500_700.book Page 65 Tuesday, May 3, 2005 5:15 PM Creating your first circuit diagram L01+ L01F1 S1 +24V 0V S2 I1 I2 Q1 2 1 H1 L01- Figure 2: ........... I MO 02:00 .......STOP J MN05013003E Lamp controller with EZ Starting point: the Status display When you switch on EZ, it opens the Status display immediately to show the switching state of the inputs and outputs. It also indicates whether EZ is already running a circuit diagram.
EZ500_700.book Page 66 Tuesday, May 3, 2005 5:15 PM Commissioning PROGRAM... STOP å RUN PARAMETER INFO J XPress OK to switch to the main menu. Press OK to switch to the next menu level, and press ESC to move one level back. OK has two other functions: • Press OK to save modified settings. • In the circuit diagram, you can also press OK to insert and modify contacts and relay coils. In this case EZ must be in STOP mode.
EZ500_700.book Page 67 Tuesday, May 3, 2005 5:15 PM Creating your first circuit diagram From the first contact to the output coil With EZ, you work from the input to the output. The first input contact is I1. XPress OK. I1 êê êê êêê EZ inserts the first contact I1 at the cursor position. XThe I flashes and can be changed, for example, to a P for a button input by using the cursor buttons Í or Ú. However, nothing needs to be changed at this point.
EZ500_700.book Page 68 Tuesday, May 3, 2005 5:15 PM Commissioning Wiring EZ displays a small arrow in the circuit diagram for creating the wiring. Press ALT to activate the arrow and press the cursor buttons ÍÚ ú í to move it. J ALT also has two other functions depending on the cursor position: • From the left contact field, press ALT to insert a new, empty rung. • The contact under the cursor can be changed between a make and break contact by pressing the ALT button.
EZ500_700.book Page 69 Tuesday, May 3, 2005 5:15 PM Creating your first circuit diagram I1-I2----ÄQ1 I1-I2----ÄQ1 XPress OK. EZ will insert relay coil Q1. The specified coil function Ä and the output relay Q1 are correct and do not have to be changed. Your first working EZ circuit diagram now looks like this: Press ESC to leave the circuit diagram display. The menu shown appears. SAVE XPress OK. CANCEL The circuit diagram is now automatically saved. CANCEL exits the circuit diagram.
EZ500_700.book Page 70 Tuesday, May 3, 2005 5:15 PM Commissioning PROGRAM....Æ STOP RUN å PARAMETER.. INFO... æ 12.......... I MO 02:00 1....... RUN XPress OK. The tick changes to STOP RUN å The Status display shows the current mode and the switching states of the inputs and outputs. XChange to the Status display by pressing ESC and press pushbutton actuator S1. The contacts for inputs I1 and I2 are activated and relay Q1 picks up. Power flow display EZ allows you to check rungs in RUN mode.
EZ500_700.book Page 71 Tuesday, May 3, 2005 5:15 PM Creating your first circuit diagram Deleting the circuit diagram XSwitch EZ to STOP mode. The display shows STOP å RUN. J PROGRAM DELETE PROG EZ must be in STOP mode in order to extend, delete or modify the circuit diagram. XUse PROGRAM... to switch from the main menu to the next menu level. XSelect DELETE PROGRAM EZ will display the prompt DELETE? XPress OK to delete the program or ESC to cancel. Press ESC to return to the Status display.
EZ500_700.
EZ500_700.book Page 73 Tuesday, May 3, 2005 5:15 PM 4 Wiring with EZ By working through the example in chapter 3 you should now have gained an initial impression of just how simple it is to create a circuit diagram in EZ. This chapter describes the full range of EZ functions and provides further examples of how to use EZ.
EZ500_700.book Page 74 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Operation The cursor buttons in the EZ circuit diagram perform three functions. The current mode is indicated by the appearance of the flashing cursor. • Move • Enter • Connect â In Move mode you can use ÍÚ ú í to move the cursor around the circuit diagram in order to select a rung, contact or relay coil. I 1 change a value at the current cursor position.
EZ500_700.book Page 75 Tuesday, May 3, 2005 5:15 PM Operation of EZ Circuit diagram The circuit diagram is that part of the program where the contacts are connected together. In RUN mode a coil is switched on and off in accordance with the current flow and the coil function specified. Function relays Function relays are program elements with special functions. Example: timing relays, time switches, counters. Function relays are elements provided with or without contacts and coils as required.
EZ500_700.book Page 76 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Coils Coils are the actuating mechanisms of relays. In RUN mode, the results of the wiring are sent to the coils, which switch on or off accordingly. Coils can have seven different coil functions.
EZ500_700.
EZ500_700.book Page 78 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Relays EZ display EZ500 EZ700 Coil function Parame ters Conditional jump : :1…:8 :1…:8 – Year time switch Y Y1…Y8 Y1…Y8 – Master reset, (central reset) Z Z1…Z3 Z1…Z3 – You can set the switching behavior of these relays by means of the coil functions and parameters selected. The options for setting output and marker relays are listed with the description of each coil function.
EZ500_700.book Page 79 Tuesday, May 3, 2005 5:15 PM Operation of EZ Contact fields Coil field I1-I2uT1-ÄQ1 Rungs/ Current paths Q1-Ö1kêê êêê êê êê êê êêê êê êê êê êêê Rungs • Connections are used to produce the electrical contact between switch contacts and the coils. They can be created across several rungs. Each point of intersection is a connection. J MN05013003E The circuit diagram display performs two functions: • In STOP mode it is used to edit the circuit diagram.
EZ500_700.book Page 80 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Saving and loading circuit diagrams There are two ways of saving circuit diagrams in EZ externally: • By saving to a memory card • By saving to a PC running EZSoft. Once they have been saved, programs can be reloaded into EZ, edited and run. All circuit diagram data is saved in EZ. In the event of a power failure the data will be retained until the next time it is overwritten or deleted.
EZ500_700.book Page 81 Tuesday, May 3, 2005 5:15 PM Working with contacts and relays Conventional circuit EZ circuit diagram EZ terminal S1 K1 S2 K1 H1 Connect make contact S1 to input terminal I2 Connect make contact S2 to EZ input terminal I3 Connect load H1 to EZ output Q4 S1 or S2 switches on H1. EZ circuit diagram I2u------ÄQ4 I3k Input and output contacts First specify which input and output terminals you wish to use in your circuit.
EZ500_700.book Page 82 Tuesday, May 3, 2005 5:15 PM Wiring with EZ J A full list of all the contacts and relays is given in the overview starting on page 76. I1 The value to be changed flashes. Values for contacts and coil fields are changed in Entry mode. J If the field is empty, EZ will enter contact I1 or the coil ÄQ1. XMove the cursor using the buttons ú í ÍÚ to a contact or coil field. XPress OK to switch to Entry mode.
EZ500_700.book Page 83 Tuesday, May 3, 2005 5:15 PM Working with contacts and relays Change ÄQ1 to ÄQ8 in the coil field Change I1 to I2 in the contact field I1 Q í or M OK I1 2 3 Í I2 ÄQ1 Å è N 4 È Ö . S A Y C T O P : D S R 5 ä . R . . ú ÄQ1 M í or 2 N OK 3 T 5 C O : Ú ÄQ8 4 . . D . Z 1 S 1 ÄQ1 . 2 2 í or OK í or OK Z EZ will leave Entry mode when you press ú í or OK to leave a contact field or coil field.
EZ500_700.book Page 84 Tuesday, May 3, 2005 5:15 PM Wiring with EZ XSwitch to Entry mode and move the cursor over the contact name. XPress ALT. The make contact will change to a break contact. XPress OK 2 × to confirm the change. I2u------ÄQ4 I3k I2u------ÄQ4 i3k I2u------ÄQ4 i3kê 2× Figure 39: l Changing contact I3 from make to break Creating and modifying connections Switch contacts and relay coils are connected with the wiring arrow in Connect mode.
EZ500_700.book Page 85 Tuesday, May 3, 2005 5:15 PM Working with contacts and relays I1-Q4-i3o z-----k hI2-I4-ÄQ2 I1-Q4-i3-ÄM1 I2-I4-M1-ÄQ2 Never work backwards. You will learn why wiring backwards does not work in section “Example: Do not wire backwards” from page 233. When wiring more than three contacts in series, use an M or N marker. Deleting connections XMove the cursor onto the contact field or coil field to the right of the connection that you want to delete.
EZ500_700.book Page 86 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Inserting and deleting a rung The EZ circuit diagram shows four of the 128 rungs in the display at the same time. If you move the cursor past the top or bottom of the display, EZ automatically scrolls up or down the display to show hidden rungs – even empty ones.
EZ500_700.book Page 87 Tuesday, May 3, 2005 5:15 PM Working with contacts and relays Switching with the cursor buttons With EZ, you can also use the four cursor buttons as hardwired inputs in the circuit diagram. P2 P1 P3 P4 The buttons are wired in the circuit diagram as contacts P1 to P4. The P buttons can be activated and deactivated in the System menu. The P buttons can also be used for testing circuits or manual operation.
EZ500_700.book Page 88 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Checking the circuit diagram EZ contains a built-in measuring device enabling you to monitor the switching states of contacts and relay coils during operation. I2---u---ÄQ4 I3---k XComplete the small parallel connection and switch EZ to RUN mode via the main menu. XReturn to the circuit diagram display. You are now unable to edit the circuit diagram.
EZ500_700.book Page 89 Tuesday, May 3, 2005 5:15 PM Working with contacts and relays Coil functions You can set the coil function to determine the switching behavior of relay coils.
EZ500_700.book Page 90 Tuesday, May 3, 2005 5:15 PM Wiring with EZ The coil functions Ä, Å, è, È, (contactor, contactor negated, cycle pulse negative, rising edge) must only be used once for each relay coil. The last coil in the circuit diagram determines the status of the relay. J When controlling a contactor or relay, the control coil is only present once. If you are creating parallel circuits, use Set, Reset as a coil function.
EZ500_700.book Page 91 Tuesday, May 3, 2005 5:15 PM Working with contacts and relays Contactor function with negated result (inverse contactor function) Å The output signal is simply an inversion of the input signal; the relay operates like a contactor with contacts that have been negated. If the coil is triggered with the 1 state, the coil switches its make contacts to the 0 state.
EZ500_700.book Page 92 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Representation in EZ: • Markers M, N: èM1 to èM16, èN1 to èN16 • Jumps: è:1 to è:8 J Physical outputs should not be used as a cycle pulse is generated. Rising edge evaluation (cycle pulse) È This function is used if the coil is only meant to switch on a rising edge. With a change in the coil state from 0 to 1, the coil switches its make contacts to the 1 state for one cycle.
EZ500_700.book Page 93 Tuesday, May 3, 2005 5:15 PM Working with contacts and relays Impulse relay ä The relay coil switches whenever the input signal changes from 0 to 1. The relay behaves like an impulse relay.
EZ500_700.book Page 94 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Latching relay The “latch” and “unlatch” relay functions are used in pairs. The relay picks up when latched and remains in this state until it is reset by the “unlatch” function.
EZ500_700.book Page 95 Tuesday, May 3, 2005 5:15 PM Function relays J Function relays A latched relay is automatically switched off if the power fails or if the device is in STOP mode. Exception: Retentive coils retain signal 1 (J section “Retention (non-volatile data storage)”, page 226). Function relays allow you to simulate the functions of different conventional control engineering devices in your circuit diagram.
EZ500_700.book Page 96 Tuesday, May 3, 2005 5:15 PM Wiring with EZ EZ circuit diagram symbol Function relays T3, Timing relay, flashing TT3, RT3, HT3 Ü :2, Jump Y3 Year time switch, date Z1, Z3 Master reset, central reset of outputs, markers Ä:2 A function relay is started via its relay coil or by evaluating a parameter. It switches the contact of the function relay according to its function and the set parameters.
EZ500_700.book Page 97 Tuesday, May 3, 2005 5:15 PM Function relays L01+ P1 S2 S1 K1T R C P1 H1 K1T L01– 2s Counter Value 10 Figure 46: I5-------CC1 I6-------RC1 C1-------TT1 T1-------ÄQ1 Hard-wiring with relays The wiring of the EZ relay looks as follows. L01+ L01– S1 +24 V 0 V 1 S2 I5 I6 2 Q1 H1 L01– Figure 47: EZ wiring and circuit diagram The counter P1 is called C1 in EZ. The timing relay K1T is called T1 in EZ. MN05013003E For more information visit: www.EatonElectrical.
EZ500_700.book Page 98 Tuesday, May 3, 2005 5:15 PM Wiring with EZ I5-------CC1 J XComplete the circuit diagram up to CC1. CC1 is the count coil of the counter 1 function relay. Press OK to call up the EZ parameter display. XMove the cursor onto the 1 of CC1 and press OK. The parameter set for the counter is displayed. C1 N S C1 N S 00000 + C1 N + C1 N + S S 98 +0 + 00010 00010 XPress the cursor button until the cursor is on the plus sign on the right of the S (setpoint).
EZ500_700.book Page 99 Tuesday, May 3, 2005 5:15 PM Function relays I5-------CC1 ê J I5-------CC1 I6-------RC1 XPress ESC to return to the circuit diagram, the setpoint 0010 will be stored. EZ has specific parameter displays for function relays. The meaning of these parameters is explained under each relay type. XEnter the circuit diagram up to coil TT1 of the timing relay. Set the parameter for T1.
EZ500_700.book Page 100 Tuesday, May 3, 2005 5:15 PM Wiring with EZ T1 Ü I1 I2 T: T1 Ü I1 I2 T: S 01.000 + +0 S 01.000 XUse the Í Ú ú í buttons to enter the value 01.000. XConfirm with OK. The time setpoint I1 for the pause time is 1 s + 00.500 XUse the Ú button to enter the value of the second setpoint I2. XSet this value to 0.5 s. This is the time value for the pulse time. XPress ESC to leave the parameter entry. The values are now stored. I5-------CC1 XComplete the circuit diagram.
EZ500_700.book Page 101 Tuesday, May 3, 2005 5:15 PM Function relays C1 N S + 0010 This is represented in the EZ parameter display. In the last line C: 0007 the counter actual value is = 7. # C:0007 C1 N S + 0010 If the actual value is greater than or equal to the setpoint (10), the left character on the bottom row will change to â. The contact of counter C1 switches. The counter contact triggers the timing relay. This causes the warning light to flash at output Q1.
EZ500_700.book Page 102 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Analog value comparator/ threshold value switch EZ provides 16 analog comparators A1 to A16 for use as required. These can also be used as threshold value switches or comparators. An analog value comparator or threshold value switch enables you to compare analog input values with a setpoint, the actual value of another function relay or another analog input.
EZ500_700.
EZ500_700.
EZ500_700.book Page 105 Tuesday, May 3, 2005 5:15 PM Analog value comparator/threshold value J If the value of a control relay exceeds the value 9999, the value of the counter is shown in the display of the analog value comparator minus 10000. Example: Counter actual value =10233 Display of the analog value comparator: 233 (10000 is displayed as 0).
EZ500_700.book Page 106 Tuesday, May 3, 2005 5:15 PM Wiring with EZ U [V] 10.0 5.0 0 Figure 48: 512 1023 Resolution of the analog inputs Function of the analog value comparator J The GT, GE, LT, and LE comparison functions only differ in the fact that GE and LE also switch when the value is equal to the setpoint. EZ500 and EZ700 feature five comparison modes so that all analog value comparators are compatible between models.
EZ500_700.book Page 107 Tuesday, May 3, 2005 5:15 PM Analog value comparator/threshold value A1-------ÄQ1 J Circuit diagram with analog value comparator. The values F1 +0, F2 +0 and OS +0 were not defined. A gain is not used with any values. No offset is used.
EZ500_700.book Page 108 Tuesday, May 3, 2005 5:15 PM Wiring with EZ A2-------ÄQ1 J Circuit diagram with analog value comparator. The values F1 +0, F2 +0 and OS +0 were not defined. No values are used with a gain factor, and no offset is used.
EZ500_700.book Page 109 Tuesday, May 3, 2005 5:15 PM Analog value comparator/threshold value A8-------ÄQ3 J Circuit diagram with analog value comparator. The values F2 +0 and OS +0 were not defined. No values are used with a gain factor, and no offset is used. A gain factor of 10 is used with the analog value at I8. The hysteresis is adjusted accordingly.
EZ500_700.book Page 110 Tuesday, May 3, 2005 5:15 PM Wiring with EZ A5 GE + I1 I7 Æ I2 0100 æ F1 F2 OS +0 +0 Example: Function of the Greater than/equal to comparison Parameter display and parameter set for Greater than/equal to analog value comparator. +0 A5-------ÄQ1 J Circuit diagram with analog value comparator. The values F1 +0, F2 +0 and OS +0 were not defined. No values are used with a gain factor, and no offset is used.
EZ500_700.book Page 111 Tuesday, May 3, 2005 5:15 PM Analog value comparator/threshold value A4 GT + I1 I7 Æ I2 0100 æ F1 F2 OS HY +0 +0 Example: Function of the Greater than comparison Parameter display and parameter set for Greater than analog value comparator. +0 0025 A4-------ÄQ1 J Circuit diagram with analog value comparator. The values F1 +0, F2 +0 and OS +0 were not defined. No values are used with a gain factor, and no offset is used.
EZ500_700.book Page 112 Tuesday, May 3, 2005 5:15 PM Wiring with EZ I5uA1----SQ1 hA2u---RQ1 i5---k Example: Analog value comparator as two-step controller If, for example, the temperature goes below a value, A1 switches on the output Q1 with the enable input I5. If the temperature exceeds the set value, A2 will switch off. If there is no enable signal, output Q1 will always be switched off by I5.
EZ500_700.book Page 113 Tuesday, May 3, 2005 5:15 PM Analog value comparator/threshold value A6-------ÄN1 A7-------ÄN2 A8-------ÄN3 Example: analog value comparator, detection of operating states Several analog value comparators can be used to evaluate different operating states. In this case 3 different operating states are evaluated.
EZ500_700.book Page 114 Tuesday, May 3, 2005 5:15 PM Wiring with EZ A1-------ÄM9 A1 LT + I1 I7 Æ I2 I8 æ F1 F2 OS HY +0 +0 Example: analog value comparator, comparison of two analog values To compare two analog values, you can use the following circuit. In this case, the comparison determines whether I7 is less than I8. Parameter settings of the analog value comparator +0 0025 Counters EZ provides 16 up/down counters C1 to C16 for use as required.
EZ500_700.book Page 115 Tuesday, May 3, 2005 5:15 PM Counters Table 11: Counter modes Counters Mode C1 to C12 N Up/down counters C13, C14 N or H Up/down counters or high-speed up counters (EZ-DA, EZ-DC) C15, C16 N or F Up/down counters or frequency counters (EZ-DA, EZ-DC) Wiring of a counter You integrate a counter into your circuit in the form of a contact and coil. The counter relay has different coils.
EZ500_700.book Page 116 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Coil Contact C2 N S 00000 + CC1 to CC16 Counter input, rising edge counts DC1 to DC16 Counting direction • Coil not triggered: up counting. • Coil triggered: down counting. RC1 to RC16 Reset, coil triggered: actual value reset to 00000 Parameter display and parameter set for the counter relay: C2 Counter function relay number 2 N • Mode N: up/down counter • Mode H: high-speed up/down counter.
EZ500_700.book Page 117 Tuesday, May 3, 2005 5:15 PM Counters Parameter display in RUN mode: C1 N S 00309 # C:00042 + Current setpoint, constant (0309) # Contact has not switched. â Contact has switched. Actual value (00042) Retention Counter relays can be operated with retentive actual values. You can select the retentive counter relays in the SYSTEM… J RETENTION… menu. C5 to C7, C8 and C13 to C16 can be selected.
EZ500_700.book Page 118 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Example The maximum cycle time is tc = 4000 µs (4 ms). fc = 1 2 × 4 ms × 0.
EZ500_700.book Page 119 Tuesday, May 3, 2005 5:15 PM Counters Example: counters, counting unit quantities, manual counter value reset The input I6 contains the necessary counter information and controls the count coil CC1 of counter 1. Q4 is activated if the setpoint is reached. Q4 remains switched on until I7 resets counter C1 to zero with the RC1 coil.
EZ500_700.book Page 120 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Example of a two counter cascade Another counter is added to the previous example. As the contact of counter C2 is only set to 1 for one program cycle, the carry of counter C2 is transferred to counter C3. The counter C3 prevents further counting when its setpoint is reached.
EZ500_700.book Page 121 Tuesday, May 3, 2005 5:15 PM Counters comparator A6 resets marker N2. The direction coil DC6 of counter C6 is reset. The counter C6 only operates as an up counter. Circuit diagram display I6-------CC6 C6-------SN2 N2-------DC6 Parameter settings of counter C6 C6 N S 01000 + A6-N2----RN2 Parameter settings of analog value comparator A6 A6 EQ C6 Æ I2 0000 æ F1 F2 OS HY J + I1 +0 +0 +0 +0 The above example scans the value zero.
EZ500_700.book Page 122 Tuesday, May 3, 2005 5:15 PM Wiring with EZ M 9 - M12 Æ M13 - M16 The example shows the counters C5 to C7 as retentive counters. Circuit diagram display N 9 - N16 C 5 - C 7 åæ I6-------CC5 C13 - C16 I8-Q3----RC5 C 8 T 7 T 8 C5-------ÄQ3 Parameter settings of counter C5 C5 N S 00565 + The counter has the value 450 before the power supply is switched off.
EZ500_700.book Page 123 Tuesday, May 3, 2005 5:15 PM High-speed counters, EZ-DA, EZ-DC The frequency counter allows you to enter an upper threshold value as a comparison value. The C15 and C16 frequency counters are not dependent on the cycle time. Counter frequency and pulse shape The maximum counter frequency is 1 kHz. The minimum counter frequency is 4 Hz. The signals must be square waves. We recommend a markto-space ratio of 1:1. If this is not the case: The minimum mark-to-space ratio is 0.5 ms.
EZ500_700.book Page 124 Tuesday, May 3, 2005 5:15 PM Wiring with EZ J ---------CC15 C15-------SQ3 I8-------- If you use C15 or C16 as frequency counters, coils DC15 or DC16 will have no function. The counter signals are transferred directly from the digital inputs I3 and I4 to the counters. A frequency counter measures the actual value and does not measure a direction. You only integrate a frequency counter into your circuit in the form of a contact and enable coil.
EZ500_700.book Page 125 Tuesday, May 3, 2005 5:15 PM High-speed counters, EZ-DA, EZ-DC In the parameter display of a counter relay you change the mode, the setpoint and the enable of the parameter display. Value range The counter relay counts between 4 and 1000 [Hz]. Parameter display in RUN mode: C15 F S 00200 # C:00153 + Current setpoint, constant (0309) # Contact has not switched. â Contact has switched.
EZ500_700.book Page 126 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Function of the frequency counter 1 2 B A D C 3 4 5 tg tg tg tg Figure 56: tg tg tg tg tg Signal diagram of the frequency counter 1: counter input I3 or I4 2: upper setpoint 3: enable coil CC… 4: reset coil RC… 5: contact (make contact) C... upper setpoint value reached. tg: gate time for the frequency measurement • Range A: the counter is enabled.
EZ500_700.book Page 127 Tuesday, May 3, 2005 5:15 PM High-speed counters, EZ-DA, EZ-DC Example: frequency counter Frequency counters with different switch points The frequency measured at input I3 is to be classified in different value ranges. The analog value comparator is used as an additional comparison option. The counter is enabled via marker N3. The value 900 or higher is detected by frequency counter C15 as the upper limit value. This triggers the coil of marker N4.
EZ500_700.book Page 128 Tuesday, May 3, 2005 5:15 PM Wiring with EZ High-speed counter You can use the high-speed counters to count high frequency signals reliably. EZ provides two high-speed up/down counters C13 and C14 for use as required. The high-speed counter inputs are permanently connected to the digital inputs I1 and I2. These counter relays allow you to count events independently of the cycle time. The high-speed counters allow you to enter an upper threshold value as a comparison value.
EZ500_700.book Page 129 Tuesday, May 3, 2005 5:15 PM High-speed counters, EZ-DA, EZ-DC J ---------CC13 C13-------SN3 I6-------DC13 I8-C13----RC13 If you use C13 or C14 as high-speed counters you must enable them with the coil CC13 or CC14 accordingly. You integrate a high-speed counter into your circuit in the form of a contact and coil. .
EZ500_700.book Page 130 Tuesday, May 3, 2005 5:15 PM Wiring with EZ In the parameter display of a counter relay you change the mode, the setpoint and the enable of the parameter display. Value range The counter relay counts between 0 and 32000. Behavior when value range is reached The EZ control relay is in RUN mode. The value is retained if the counter reaches 32000. If the counter counts down and reaches 0, this value is retained.
EZ500_700.book Page 131 Tuesday, May 3, 2005 5:15 PM High-speed counters, EZ-DA, EZ-DC Function of the high-speed counter function block 1 ......... ......... .........
EZ500_700.book Page 132 Tuesday, May 3, 2005 5:15 PM Wiring with EZ 7: contact of the counter, C13 (C14) • Range A: The relay contact C13 (C14) of the counter with setpoint value 512 switches as soon as the actual value is 512. • Range B: When new count pulses or the counter enable are not present, the actual value is retained. • Range C: If the count direction is reversed DC13 (DC14), the contact is reset when the actual value is 511.
EZ500_700.book Page 133 Tuesday, May 3, 2005 5:15 PM High-speed counters, EZ-DA, EZ-DC Example running motors or spindles in parallel. Applications may involve motion control with the parallel control of two drives. Only certain deviations are permissible so that the mechanical system does not jam. These tasks can be implemented with the following solution. I8 starts the drives. I7 and I6 carry the feedback signals of the motor-protective circuit-breakers.
EZ500_700.book Page 134 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Parameter settings of the counter C14 C14 H S +0 + Parameter setting of analog value comparators A1 and A2 A1 LT I1 Æ C14 æ F1 +0 F2 +0 I2 OS HY + C13 +0 0015 A2 LT + I1 C14 Æ I2 C13 æ F1 F2 OS HY +0 +0 +0 0015 Parameter settings A3 A1 EQ I1 C13 Æ I2 C14 æ F1 F2 OS HY Text display 134 + +0 +0 +0 0020 EZ500 and EZ700 can display up to 16 user-defined texts.
EZ500_700.book Page 135 Tuesday, May 3, 2005 5:15 PM Text display Wiring a text display i5-------ÄD2 You integrate a text display into your circuit in the form of a contact and coil. D2u------ÄT5 The coils and contacts have the following meanings: i6-------ÄD3 D3k Contact D1 Coil to D16 Coil of the corresponding text display is triggered Ä, Å, è, ^, ä, S, R D1 to D16 If a coil is triggered, the text is shown in the display.
EZ500_700.book Page 136 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Example of a text display: SWITCH; The text display can display the following: CONTROL; DISPLAY; EASY! EASY! RUNTIME M:S T1 :012:46 C1 :0355 PRODUCED ST Line 1, 12 characters Line 2, 12 characters, a setpoint or actual value Line 3, 12 characters, a setpoint or actual value Line 4, 12 characters Scaling The values of the analog inputs can be scaled.
EZ500_700.book Page 137 Tuesday, May 3, 2005 5:15 PM Text display • The OK or DEL + ALT buttons are used to switch to a menu. • A setpoint is entered. • The text for D1 is displayed. D1: D1 is designed as an alarm text. If D1 is activated, the text assigned to it will be displayed until • • • • The coil D1 is reset to 0. STOP mode is selected. EZ's power supply is no longer present. The OK or DEL + ALT buttons are used to switch to a menu.
EZ500_700.book Page 138 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Entering a setpoint in a display A text can contain two values such as actual values and setpoints of function relays, analog input values and time and date. The position of setpoints and actual values is fixed to the center of lines 2 and 3. The length depends on the value to be displayed. Setpoint entries in the text display are useful if the PARAMETER menu is not available for display or entry.
EZ500_700.book Page 139 Tuesday, May 3, 2005 5:15 PM Text display STIR S : M:S 012:00 XPressing the ALT button will cause the cursor to jump to the first editable value. ACT: 008:33 In this operating mode, you can use the cursor buttons ÍÚ to move between different editable constants. STIR XPress the OK button, the cursor will jump to the highest digit of the constant to be modified. S : M:S 012:00 BREAD ROLLS In this operating mode use the cursor buttons ÍÚ to modify the value.
EZ500_700.book Page 140 Tuesday, May 3, 2005 5:15 PM Wiring with EZ 7-day time switch EZ500 and EZ700 with type suffix EZ…-..-.C. are provided with a real-time clock. The time switches can only be used effectively in these devices. J The procedure for setting the time is described under section “Setting date, time and daylight saving time” on page 209. EZ offers eight 7-day time switches Ö1 to Ö8 for up to 32 switch times.
EZ500_700.book Page 141 Tuesday, May 3, 2005 5:15 PM 7-day time switch The parameter display for a 7-day time switch is used to modify the weekdays, the on time, the off time and enable of the parameter display.
EZ500_700.book Page 142 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Ö1 B 11:30 + D SA OFF 15:00 â ON 06:45 XPress the Í button to move the cursor to channel B. Press the í button to reach any value that can be edited. Function of the 7-day time switch The following examples illustrate the function of the 7-day time switch. Work days example The time switch Ö1 switches on Monday to Friday between 6:30 and 9:00 and between 17:00 and 22:30.
EZ500_700.book Page 143 Tuesday, May 3, 2005 5:15 PM 7-day time switch Figure 60: Weekend switching signal diagram Night switching example Time switch Ö3 switches on at 22:00 on Monday and switches off at 6:00 on Tuesday. Ö3 D D MO OFF 06:00 ON 22:00 Figure 61: J + Night switching signal diagram If the off time is before the on time, EZ will switch off on the following day. Time overlaps example The time settings of a time switch overlap.
EZ500_700.book Page 144 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Figure 62: J Time overlaps signal diagram On and off times always follow the channel which switches first. Power failure example The power is removed between 15:00 and 17:00. The relay drops out and remains off, even after the power returns, since the first off time was at 16:00.
EZ500_700.book Page 145 Tuesday, May 3, 2005 5:15 PM Operating hours counter Operating hours counter EZ provides 4 independent operating hours counters. These operating hours counters enable you to record the operating hours of systems, machines and machine parts. An adjustable setpoint can be selected within the value range. In this way, maintenance times can be logged and reported. The counter states are retained even when the device is switched off.
EZ500_700.book Page 146 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Parameter display in RUN mode: O1 + S 001000 # O:000309 Set time in hours Actual time in hours # Contact has not switched. â Contact has switched. Value range of the operating hours counter The operating hours counter counts in the range from 0 hours to way over 100 years. Accuracy of the operating hours counter The operating hours counter counts in seconds. When the device is switched off, up to 999 ms can be lost.
EZ500_700.book Page 147 Tuesday, May 3, 2005 5:15 PM Operating hours counter J Operating mode change RUN, STOP, power On, Off, Delete program, Change program, Load new program. All these functions do not clear the actual value of the operating hours counter. Example: operating hours counter Operating hours counter for the operating time of a machine. The time in which a machine (EZ) is energized is to be measured.
EZ500_700.book Page 148 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Parameter settings of operating hours counter O3 O3 S 000800 + Example maintenance meter for different machine sections, with text output The entire machine operating time is to be counted. Machine areas have to be maintained after different times have elapsed. Markers N1 and N2 are the On markers of two different machine areas. These markers control the associated operating hours counters.
EZ500_700.book Page 149 Tuesday, May 3, 2005 5:15 PM Operating hours counter Parameter settings of operating hours counter O2 O2 S 000500 + Parameter setting of timing relay T1 T1 Ü I1 I2 S 02.000 + 01.
EZ500_700.book Page 150 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Timing relays EZ provides 16 timing relays T1 to T16 for use as required. A timing relay is used to change the switching duration and the make and break times of a switch contact. The delay times can be configured between 2 ms and 99 h 59 min. You can use positive values, values of analog inputs, actual values of counter relays and timing relays. You can also use EZ as a multi-function relay in the application.
EZ500_700.book Page 151 Tuesday, May 3, 2005 5:15 PM Timing relays I1 Time setpoint 1: • Positive value, I7, I8, I11, I12 • Actual value T1 to T16, C1 to C16 I2 Time setpoint 2 (with timing relay with 2 setpoints): • Positive value, I7, I8, I11, I12 • Actual value T1 to T16, C1 to C16 T: Display of actual value in RUN mode In the parameter display of a timing relay you can change the mode, the time base, the time setpoint 1, time setpoint 2 (if necessary) and the enable of the parameter display.
EZ500_700.book Page 152 Tuesday, May 3, 2005 5:15 PM Wiring with EZ J When EZ is restarted, the status of the trigger pulse must be the same as on disconnection. Status 1 with all operating modes: • on-delayed, • single pulse, • flashing. Status 0 with all operating modes: off-delayed.
EZ500_700.book Page 153 Tuesday, May 3, 2005 5:15 PM Timing relays J Minimum time setting: If a time value is less than EZ's cycle time, the elapsed time will not be recognized until the next cycle. This may cause unforeseeable switching states. Variable values as time setpoint (I7, I8, I11, I12, actual value T1 to T16, C1 to C16) J If the value of the variable is greater than the maximum permissible value of the configured time range, the maximum value of the time range will be used as the setpoint.
EZ500_700.book Page 154 Tuesday, May 3, 2005 5:15 PM Wiring with EZ M:S time base Rule: Time setpoint = Value divided by 60, Integer result = Number of minutes, remainder is the number of seconds Value, e.g. analog input Time setpoint in [M:S] 0 00:00 100 01:40 300 05:00 500 08:20 1023 17:03 Time base H:M Rule: Time setpoint = Value divided by 60 Integer result = Number of hours, remainder is the number of minutes 154 Value, e.g.
EZ500_700.book Page 155 Tuesday, May 3, 2005 5:15 PM Timing relays Function of the timing relay function block Timing relay, on-delayed with and without random switching Random switching: The contact of the timing relay switches randomly within the setpoint value range.
EZ500_700.book Page 156 Tuesday, May 3, 2005 5:15 PM Wiring with EZ 1 2 3 4 ts Figure 64: tF ts D E ts F Signal diagram of timing relay, on-delayed (with and without random switching) • Range D: The Stop coil is inoperative after the time has elapsed. • Range E: The Reset coil resets the relay and the contact. • Range F: The Reset coil resets the time during the timeout sequence. After the Reset coil drops out, the time elapses normally. 156 For more information visit: www.EatonElectrical.
EZ500_700.book Page 157 Tuesday, May 3, 2005 5:15 PM Timing relays Timing relay, off-delayed with and without random switching Random switching: The contact of the timing relay switches randomly within the setpoint value range.
EZ500_700.book Page 158 Tuesday, May 3, 2005 5:15 PM Wiring with EZ 1 2 3 4 t1 E Figure 66: ts Signal diagram of timing relay, off-delayed (with/without random switching with retriggering) Range E: The Trigger coil drops out twice. The actual time t1 is cleared and the set time ts elapses completely (retriggerable switch function). 158 For more information visit: www.EatonElectrical.
EZ500_700.book Page 159 Tuesday, May 3, 2005 5:15 PM Timing relays Timing relay, on-delayed and off-delayed with and without random switching Time value I1: On-delayed time Time value I2: Off-delayed time Random switching: The contact of the timing relay switches randomly within the setpoint value ranges.
EZ500_700.book Page 160 Tuesday, May 3, 2005 5:15 PM Wiring with EZ 1 2 3 4 ts1 t1 + t2 = ts2 E Figure 68: ts1 t F ts1 G ts2 Signal diagram of timing relay, on- and off-delayed 2 • Range E: The Stop coil stops the timeout of the off-delay. • Range F: The Reset coil resets the relay after the on delay has elapsed • Range G: The Reset coil resets the relay and the contact while the on delay is timing out. After the Reset coil drops out, the time elapses normally.
EZ500_700.book Page 161 Tuesday, May 3, 2005 5:15 PM Timing relays Timing relay, single pulse 1 2 3 4 ts ts B A Figure 70: t1 + t2 = ts C Signal diagram of timing relay, single pulse 1 1: trigger coil TTx 2: Stop coil HTx 3: Reset coil RTx 4: switch contact (make contact) Tx • Range A: The trigger signal is short and is lengthened • Range B: The Trigger signal is longer than the set time. • Range C: The Stop coil interrupts the timing out of the set time.
EZ500_700.book Page 162 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Timing relay, flashing You can set the mark-to-space ratio to 1:1 or ≠ 1:1.
EZ500_700.book Page 163 Tuesday, May 3, 2005 5:15 PM Timing relays Timing relay examples Example: timing relay, on-delayed In this example a conveyor starts 10 s after the system is powered up. Circuit diagram display I5-------TT1 T1-------ÄQ1 Parameter settings of timing relay T1 T1 X I1 I2 S 10.000 + Example: timing relay, off-delayed The off-delayed function is used to implement a rundown time on the conveyor if required.
EZ500_700.book Page 164 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Example: timing relay, single pulse The input pulses present may vary in length. These pulses must be normalized to the same length. The Single pulse function can be used very simply to implement this. Circuit diagram display I7-------TT4 T4-------ÄQ4 Parameter settings of timing relay T4 T4 ü I1 I2 S 10.000 + Example: timing relay, flashing This example shows a continuous flash pulse function.
EZ500_700.book Page 165 Tuesday, May 3, 2005 5:15 PM Timing relays M 9 - M12 åÆ M13 - M16 N 9 - N16 C 5 - C 7 C 8 C13 - C16 T 7 T 8 T13 - T16 D 1 - D 8 æ å å XSelect the required timing relay in the SYSTEM…J RETENTION… menu. The example shows the timing relays T7, T8 as retentive timing relays. Markers M9 to M12 were also selected as retentive.
EZ500_700.book Page 166 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Jumps Jumps can be used to optimize the structure of a circuit diagram or to implement the function of a selector switch. Jumps can be used for example to select whether manual/ automatic operation or other machine programs are to be set. I2-------Ä:1 ---------Ä:2 :1 T1-------ÄQ3 You integrate :1 jumps into your circuit in the form of a contact and coil. Jumps consist of a jump location and a jump label.
EZ500_700.book Page 167 Tuesday, May 3, 2005 5:15 PM Jumps Attention! The states of jumped rungs are retained. The time value of timing relays that have been started will continue to run. Power flow display Jumped sections are indicated by the coils in the power flow display. All coils after the jump coil are shown with the symbol : of the jump coil. Example A selector switch allows two different sequences to be set. • Sequence 1: Switch on Motor 1 immediately.
EZ500_700.book Page 168 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Circuit diagram: Power flow display: I1 selected: I1-------Ä:1 I1-------Ä:1 :1 :1 I2-------Ä:2 --------uÄQ1 hRQ2 ---------Ä:8 :2-------ÄQ2 Q2-I3----TT2 T2-------ÄQ1 :8 i12-------ÄD1 168 I2------- : --------uÄQ1 hRQ2 ---------Ä:8 :2------- : Q2-I3---- : T2------- : :8 i12-------ÄD1 Section from jump label 1 processed. Jump to label 8. Section to jump label 8 skipped.
EZ500_700.book Page 169 Tuesday, May 3, 2005 5:15 PM Year time switch Year time switch EZ500 and EZ700 devices with the type designation EZ...-..-.C. are equipped with an integrated real-time clock that you can use as a 7-day time switch and year time switch. If you have to implement special on and off switching functions on public holidays, vacations, company holidays, school holidays and special events, these can be implemented easily with the year time switch.
EZ500_700.book Page 170 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Y1 A ON + --.--.-- OFF --.--.-- Parameter display and parameter set for the year time switch: Y1 Year time switch function relay 1 A,B, C,D Time switch channels + • • ON On date: day, month, year (two-digit 2004 = 04) OFF Off date: day, month, year (two-digit 2004 = 04) + - appears in the PARAMETER menu. does not appear in the PARAMETER menu.
EZ500_700.book Page 171 Tuesday, May 3, 2005 5:15 PM Year time switch Changing time switch channel You can change time switch channel in either RUN or STOP mode by selecting the channel required with the cursor buttons ÍÚ. Y4 A ON + 01.01.04 OFF 31.03.04 Example: The display on the left shows the parameter display of a year time switch. The cursor is flashing on channel A. â Y4 B ON + 01.10.04 OFF 31.12.04 XPress the Í button to move the cursor to channel B.
EZ500_700.book Page 172 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Y1 ON A + --.XX.-- Rule 2 ON: Month OFF --.XX.-- OFF: Month Y1 Rule 3 ON: Year ON A + --.--.XX OFF --.--.XX OFF: Year Y1 Rule 4 ON: Day/month ON A + XX.XX.-- OFF XX.XX.-- OFF: Day/month Y1 Rule 5 ON: Month/year ON A + --.XX.XX OFF --.XX.XX OFF: Month/year Y1 Rule 6 ON: Day/month/year ON A + XX.XX.XX OFF XX.XX.XX OFF: Day/month/year Y1 Rule 7 Two-channel ON A + XX.XX.-- OFF --.--.
EZ500_700.book Page 173 Tuesday, May 3, 2005 5:15 PM Year time switch Y1 ON B + XX.XX.XX OFF --.--.XX Y1 ON D + --.--.XX OFF XX.XX.XX Rule 8 Two-channel Channel ON: Day/month/year Channel D OFF: Day/month/year With this rule, the same year number must be entered in each channel in the ON and OFF entry area. Rule 9 Overlapping channels: The first ON date switches on and the first OFF date switches off.
EZ500_700.book Page 174 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Example : Selecting year range The year time switch Y1 is required to switch on at 00:00 on 1 January 2004 and switch off at 23:59 on 31 December 2005. Circuit diagram display Y1-------ÄQ1 Parameter settings for the year time switch Y1 Y1 ON A + --.--.04 OFF --.--.05 Example: Selecting month ranges The year time switch Y2 is required to switch on at 00:00 on 1 March and switch off at 23:59 on 30 September.
EZ500_700.book Page 175 Tuesday, May 3, 2005 5:15 PM Year time switch Example : Selecting public holidays The year time switch Y4 is required to switch on at 00:00 on day 25.12 of each year and switch off at 23:59 on day 26.12 of each year. “Christmas program” Circuit diagram display Y4-------ÄQ1 Parameter settings for the year time switch Y4 Y4 A ON + 25.12.-- OFF 26.12.-- Example: Selecting a time range The year time switch Y1 is required to switch on at 00:00 on day 02.
EZ500_700.book Page 176 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Circuit diagram display Y1-------ÄQ1 Parameter settings for the year time switch Y1 Y1 ON C + 03.05.-- OFF 25.10.-- Y1 ON D + 02.06.-- OFF 17.12.-- Total number of channels and behavior of the contact Y1: The time switch will switch on at 00:00 from 3 May and off at 23:59 on 25 May. In June, July, August, September, October, the time switch will switch on at 00:00 on day 2 of the month and switch off at 23:59 on day 17.
EZ500_700.book Page 177 Tuesday, May 3, 2005 5:15 PM Master reset Operating modes The different coils of the master reset have different operating modes • Z1: For Q outputs: controls outputs Q1 to Q8 and S1 to S8. • Z2: For markers M, N: controls the marker range M1 to M16 and N1 to N16. • Z3: for outputs and markers: controls Q1 to Q8, S1 to S8, M1 to M16 and N1 to N16.
EZ500_700.book Page 178 Tuesday, May 3, 2005 5:15 PM Wiring with EZ I8-------ÈZ3 I5-------ÄQ1 I2-M1-T1-SS3 M3uC1----SQ3 M4b Example: resetting outputs and markers All outputs and markers that you have used can be reset to 0 with one command. A rising edge at the coil of Z3 will cause all Q and S outputs and all M and N markers to be reset.
EZ500_700.book Page 179 Tuesday, May 3, 2005 5:15 PM Basic circuits Negation (coil) Negation means in this case that the coil opens when the make contact is actuated (NOT circuit). I1-------ÅQ1 In the EZ circuit diagram example, you only change the coil function Table 15: Negation I1 Q1 1 0 0 1 Maintained contact ---------ÄQ1 To energize a relay coil continuously, make a connection of all contact fields from the coil to the leftmost position.
EZ500_700.book Page 180 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Table 17: Series circuit I1 I2 I3 Q1 Q2 0 0 0 0 1 0 0 1 0 0 0 1 0 0 0 0 1 1 0 0 1 0 0 0 0 1 0 1 0 0 1 1 0 0 0 1 1 1 1 0 Parallel circuit I1u------ÄQ1 Q1 is controlled by a parallel circuit consisting of several make contacts (OR circuit). I3k A parallel circuit of break contacts controls Q2 (NAND circuit).
EZ500_700.book Page 181 Tuesday, May 3, 2005 5:15 PM Basic circuits Parallel circuit operating like a series connection of make contacts I1u------ÅQ1 i2s I3s I4s I5k A series circuit with more than three contacts (make contacts) can be implemented with a parallel circuit of break contacts on a negated coil. In the EZ circuit diagram you can switch as many rungs in parallel as you have rungs available.
EZ500_700.book Page 182 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Parallel circuit operating like a series connection of break contacts I1u------ÅQ1 I2s I3s A series circuit with more than three contacts (break contacts) can be implemented with a parallel connection of make contacts on a negated coil. In the EZ circuit diagram you can switch as many rungs in parallel as you have rungs available.
EZ500_700.book Page 183 Tuesday, May 3, 2005 5:15 PM Basic circuits Table 21: Two-way circuit (XOR) I1 I2 Q1 0 0 0 0 1 1 1 0 1 1 1 0 Self-latching I1uI2----ÄQ1 Q1k S1 make contact at I1 S2 break contact at I2 A combination of a series and parallel connection is used to wire a latching circuit. Latching is established by contact Q1 which is connected in parallel to I1. If I1 is actuated and reopened, the current flows via contact Q1 until I2 is actuated.
EZ500_700.book Page 184 Tuesday, May 3, 2005 5:15 PM Wiring with EZ S2 breaks the connection to the control voltage in order to switch off the machine. This ensures that the machine can be switched off, even in the event of a wire break. I2 is always closed when not actuated. I1-------SQ1 i2-------RQ1 S1 make contact at I1 S2 break contact at I2 A self-latching circuit with wire break monitoring can alternatively be wired using the Set and Reset coil functions. If I1 is activated, coil Q1 latches.
EZ500_700.book Page 185 Tuesday, May 3, 2005 5:15 PM Basic circuits Table 24: Cycle pulse on rising edge I1 Status of Q1 cycle n Status of Q1 cycle n + 1 0 0 0 1 1 0 0 0 0 Cycle pulse on falling edge I1-------èQ1 You can create a cycle pulse on a falling edge if you use the appropriate coil function. This is very useful for count pulses, jump pulses.
EZ500_700.book Page 186 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Example circuits Star-delta starting You can implement two star-delta circuits with EZ. The advantage of EZ is that you can select any changeover time between star and delta contactors and any wait time between switching off the star contactor and switching on the delta contactor. L S1 S2 K1M K3M K1M K1T K1M K1T K5M K3M K3M K5M N Figure 74: 186 Star-delta circuit with conventional contactors For more information visit: www.
EZ500_700.book Page 187 Tuesday, May 3, 2005 5:15 PM Example circuits L N S1 K1M S2 I1 L N Q2 Q1 1 K1M 2 K3M 1 2 K5M N Figure 75: MN05013003E Star-delta circuit with EZ For more information visit: www.EatonElectrical.
EZ500_700.book Page 188 Tuesday, May 3, 2005 5:15 PM Wiring with EZ I1u------TT1 dt1----ÄQ1 dT1----TT2 hT2----ÄQ2 Function of the EZ circuit diagram: Start/stop of the circuit with the external pushbutton actuators S1 and S2. The mains contactor starts the timing relay in EZ.
EZ500_700.book Page 189 Tuesday, May 3, 2005 5:15 PM Example circuits Table 26: Pulse Shift register Value Storage position 1 2 3 4 1 1 1 0 0 0 2 0 0 1 0 0 3 0 0 0 1 0 4 1 1 0 0 1 5 0 0 1 0 0 0 0 0 0 Reset = 1 Assign the information “bad” to value 0. If the shift register is cleared accidentally, no bad parts are used further.
EZ500_700.
EZ500_700.book Page 191 Tuesday, May 3, 2005 5:15 PM Example circuits In the second cycle break contact M7 is open. The series circuit is opened. The contact M8 is activated from the result of the first cycle. Now, all the storage locations are either set or reset in accordance with the series circuit. If the relay coils were activated, EZ transfers the result to the contacts. M8 is now open again. No new pulse can be formed until I1 has opened, since M7 is open for as long as I1 is closed.
EZ500_700.book Page 192 Tuesday, May 3, 2005 5:15 PM Wiring with EZ How are all the storage locations cleared? When I3 is activated, all the R coils of storage locations M1 to M4 are reset, i.e. the coils are deactivated. Since the reset was entered at the end of the circuit diagram, the reset function has priority over the set function.
EZ500_700.
EZ500_700.book Page 194 Tuesday, May 3, 2005 5:15 PM Wiring with EZ Stairwell lighting For a conventional circuit you would need at least five space units in the distribution board, i.e. one impulse relay, two timing relays and two auxiliary relays. EZ requires only four space units. A fully functioning stairwell lighting system can be set up with five terminals and the EZ circuit diagram.
EZ500_700.book Page 195 Tuesday, May 3, 2005 5:15 PM Example circuits S1 S2 H1 H2 S3 H3 L N L N I1 Q1 1 Figure 80: 2 Stairwell lighting with EZ Button pressed briefly Light ON or OFF. The impulse relay function will even switch off Continuous lighting. Light off after 6 min. with Continuous lighting this function is not active. Button pressed for more than 5 s MN05013003E Continuous lighting For more information visit: www.EatonElectrical.
EZ500_700.book Page 196 Tuesday, May 3, 2005 5:15 PM Wiring with EZ The EZ circuit diagram for the The enhanced EZ circuit diagram: functions described above looks after four hours, the continuous like this: lighting is also switched off.
EZ500_700.book Page 197 Tuesday, May 3, 2005 5:15 PM Example circuits If you use an EZ with analog inputs, you can optimize the stairwell lighting with a brightness sensor to suit the lighting conditions. MN05013003E For more information visit: www.EatonElectrical.
EZ500_700.
EZ500_700.book Page 199 Tuesday, May 3, 2005 5:15 PM 5 EZ Settings Settings can only be carried out on EZ models provided with buttons and LCD display. EZSoft can be used to set all models via the software. Password protection The EZ can be protected by a password against unauthorized access. In this case the password consists of a value between 0001 and 9999. The number combination 0000 is used to delete a password.
EZ500_700.book Page 200 Tuesday, May 3, 2005 5:15 PM EZ Settings J A password that has been entered in EZ is transferred to the memory card together with the circuit diagram, irrespective of whether it was activated or not. If this EZ circuit diagram is loaded back from the memory card, the password will also be transferred to EZ and is activated immediately. Password setup A password can be set up via the System menu in either RUN or STOP mode.
EZ500_700.book Page 201 Tuesday, May 3, 2005 5:15 PM Password protection Selecting the scope of the password CIRC.DIAG.åÆ PARAMETER CLOCK OPRTNG MODEæ XPress the OK button. XSelect the function or the menu to be protected. XPress the OK button in order to protect the function or menu (tick = protected). INTERFACE DELETE FUNCT J Standard protection encompasses the programs and circuit diagram. At least one function or menu must be protected.
EZ500_700.book Page 202 Tuesday, May 3, 2005 5:15 PM EZ Settings Activating the password You can activate a valid password in three different ways: • automatically when EZ is switched on again • automatically after a protected circuit diagram is loaded • via the password menu XPress DEL and ALT to call up the System menu. XOpen the password menu via the SECURITY… menu EZ will only show this menu if a password is present. CHANGE PW ACTIVATE J Make a note of the password before you activate it.
EZ500_700.book Page 203 Tuesday, May 3, 2005 5:15 PM Password protection Unlocking EZ Unlocking EZ will deactivate the password. You can reactivate password protection later via the Password menu or by switching the power supply off and on again. PASSWORD... STOP RUN å XPress OK to switch to the main menu. The PASSWORD… entry will flash. XPress OK to enter the password entry menu. PASSWORD...
EZ500_700.book Page 204 Tuesday, May 3, 2005 5:15 PM EZ Settings Changing or deleting the password range XUnlock EZ. XPress DEL and ALT to call up the System menu. XOpen the password menu via the menu option SECURITY JPASSWORD… The CHANGE PW entry will flash. CHANGE PW ACTIVATE PW ENTER PASSW XXXX ENTER PASSW 1789 EZ will only show this menu if a password is present. XPress OK to enter the password entry menu. XPress OK to move to the 4-digit entry field.
EZ500_700.book Page 205 Tuesday, May 3, 2005 5:15 PM Changing the menu language After the fourth entry attempt EZ will ask whether you wish to delete the circuit diagram and data. DELETE ? XPress – ESC: Circuit diagram, data or password are not deleted. – OK: Circuit diagram, data and password are deleted. EZ will return to the Status display. J If you no longer know the exact password, you can press OK to unlock the protected EZ.
EZ500_700.book Page 206 Tuesday, May 3, 2005 5:15 PM EZ Settings J Language selection is only possible if EZ is not passwordprotected. XPress DEL and ALT to call up the System menu. XSelect LANGUAGE… to change the menu language. ENGLISH DEUTSCH FRANCAIS å ESPANOL ITALIANO Æ The language selection for the first entry ENGLISH is displayed. æ XUse Í or Ú to select the new menu language, e.g. Italian (ITALIANO). XConfirm with OK. ITALIANO is assigned a tick. XExit the menu with ESC.
EZ500_700.book Page 207 Tuesday, May 3, 2005 5:15 PM Changing parameters T3 Ü T8 X C4 N S + M:S + The following preconditions must be fulfilled in order for a parameter set to be displayed: + • A function relay must have been included in the circuit diagram. • The PARAMETER menu must be available. • The parameter set must have been enabled for access, indicated by the + character at the bottom right of the display.
EZ500_700.book Page 208 Tuesday, May 3, 2005 5:15 PM EZ Settings In RUN mode EZ operates with a new setpoint as soon as it has been modified in the parameter display and saved with OK. Example: Changing switch times for outdoor lighting The outdoor lighting of a building is automatically switched on from 19:00 to 23:30 Mondays to Fridays in the EZ circuit diagram. Ö1 A 15:21 + The parameter set for the time switch function relay 1 is saved in channel A and looks like this.
EZ500_700.book Page 209 Tuesday, May 3, 2005 5:15 PM Setting date, time and daylight saving Ö1 B 15:21 + D SA OFF 22:00 ON 19:00 XSet the switching off time to 22:00. XPress OK. EZ will save the new parameters. The cursor will remain in the contact field on channel identifier B. Press ESC to leave the parameter display. The time switch will now also switch on at 19:00 on Saturdays and switch off at 22:00.
EZ500_700.book Page 210 Tuesday, May 3, 2005 5:15 PM EZ Settings HH:MM: 18:24 DD.MM: 01.05 YEAR : 2004 XSet the values for time, day, month and year. XPress the OK button to access the Entry mode. – ú í Move between the parameters – ÍÚ Change the value of a parameter – OK Save day and time – ESC Retain previous setting. Press ESC to leave the time setting display. Setting summer time start and end Most EZ models are fitted with a real-time clock.
EZ500_700.book Page 211 Tuesday, May 3, 2005 5:15 PM Setting date, time and daylight saving This will open the menu for setting the time. SET CLOCK XSelect the SUMMER TIME menu option. SUMMER TIME Setting summer time start and end EZ shows you the options for the DST change. The standard setting is NONE for automatic DST changeover (Tick at NONE). J NONE RULE... EU åÆ GB æ NONE Æ US RULE... EU GB US å æ The start and end of summer time can only be set in STOP mode.
EZ500_700.book Page 212 Tuesday, May 3, 2005 5:15 PM EZ Settings The following rules normally apply: Table 27: DST setting rule When Weekday ON WD How Date -- J table 28 Rule 1: change on a special date -- -- Rule 2: change on a defined day in the month • • • • • 1st (first) 2nd (second) 3rd (third) 4th (fourth) L.
EZ500_700.book Page 213 Tuesday, May 3, 2005 5:15 PM Setting date, time and daylight saving Table 28: Date parameters Day Month Hour Minute Time difference DD.
EZ500_700.book Page 214 Tuesday, May 3, 2005 5:15 PM EZ Settings Table 30: When Weekday How WD ON L. (last) SU (Sunday) MONTH EU summer time start Day Month Hour Minute Time difference DD.
EZ500_700.
EZ500_700.book Page 216 Tuesday, May 3, 2005 5:15 PM EZ Settings SUMMER START SUMMER END The two SUMMER START (start of summer time) and SUMMER END (end of summer time) menus are shown. SUMMER START: set the DST time for the start of summer. SUMMER END: set the DST time for the end of summer. J If a standard rule has been selected, this will be accepted as the rule. This menu appears for entering the required time settings: DAY WD: L.Æ SU MONTH DD.MM:--.
EZ500_700.book Page 217 Tuesday, May 3, 2005 5:15 PM Setting date, time and daylight saving XPress the OK button to access the Entry mode. – ÍÚ Select required value. – ú í Move between the places. – ÍÚ Change the value of a parameter – OK Save value. – ESC Retain previous setting. Press ESC to leave the DST setting display. The above rule is the EU rule for the start of summer time. J The menu for the end of summer time has the same structure. The values are now entered accordingly.
EZ500_700.book Page 218 Tuesday, May 3, 2005 5:15 PM EZ Settings J Behavior for summer time end on 01.01. If 01.01. is selected for the end of summer time, ensure the following: The DST time minus the time difference should not go into 31.12. Otherwise the time will continue to run until the set time minus the time difference is 0:00 on the 01.01. The time will then continue to run with 0:00.
EZ500_700.book Page 219 Tuesday, May 3, 2005 5:15 PM Activating debounce (input delay) DEBOUNCE P BUTTONS RUN MODE CARD MODE DEBOUNCE P BUTTONS RUN MODE CARD MODE J If EZ is password-protected you cannot open the System menu until you have “unlocked” it. Æ The input delay (debounce) is set with the DEBOUNCE menu item. æ åÆ æ Activating debounce (input delay) If a tick å is next to DEBOUNCE; this means that the Debounce function has been switched on.
EZ500_700.book Page 220 Tuesday, May 3, 2005 5:15 PM EZ Settings Activating and deactivating the P buttons Even though the cursor buttons (P buttons) have been set as pushbutton actuator inputs in the circuit diagram, this function is not activated automatically. This prevents any unauthorized use of the cursor buttons. The P buttons can be activated in the System menu. J If EZ is password-protected you cannot open the System menu until you have “unlocked” it.
EZ500_700.book Page 221 Tuesday, May 3, 2005 5:15 PM Startup behavior Deactivating the P buttons XSelect P BUTTONS å and press OK. EZ changes the display to P BUTTONS and the P buttons are deactivated. J Startup behavior When deleting a circuit diagram in EZ500, the P buttons are deactivated automatically. If a circuit diagram is loaded from the memory card or from EZSoft, the status set there is also transferred. The startup behavior is an important aid during the commissioning phase.
EZ500_700.book Page 222 Tuesday, May 3, 2005 5:15 PM EZ Settings Activating RUN mode Displayed as EZ RUNMODE å, this means that EZ will start in RUN mode when the power supply is switched on. DEBOUNCE åÆ RUN MODE å DEBOUNCE åÆ RUNMODE å P BUTTONS CARD MODE P BUTTONS CARD MODE XOtherwise select RUN MODE and press OK. RUN mode is activated. æ æ XPress ESC to return to the Status display. Deactivating RUN mode XSelect RUN MODE å. Press the OK button. The RUN mode function is deactivated.
EZ500_700.book Page 223 Tuesday, May 3, 2005 5:15 PM Startup behavior Possible faults EZ will not start in RUN mode: • EZ does not contain a program. • You have put EZ in STOP mode (RUN MODE menu displayed). Card mode behavior The startup behavior using a memory card is for applications where unskilled personnel have to change the memory card with EZ de-energized. EZ only starts in the RUN mode if a memory card with a valid program is inserted.
EZ500_700.book Page 224 Tuesday, May 3, 2005 5:15 PM EZ Settings J Card mode only functions with the EZ-M-32K memory card. Previous memory cards did not support this function. DEBOUNCE åÆ Deactivating card mode XSelect CARD MODE å and press the OK button. RUN MODE å The Card mode function is deactivated. P BUTTONS CARD MODE æ EZ is factory set with the display showing CARD MODE, which means that EZ without a memory card starts in RUN mode when the supply voltage is applied.
EZ500_700.book Page 225 Tuesday, May 3, 2005 5:15 PM Setting the cycle time Setting the cycle time EZ allows you to fix the cycle time. To do this, move to the SYSTEM menu and from there to the CYCLE TIME.. menu J P BUTTONS Æ CARD MODE å RUN MODE å CYCLE TIME.æ CYCLE TIME 00 MS CYCLE TIME 35 MS J Factory setting: The cycle time is set to 00 ms. The cycle time can only be set in STOP mode. EZ is in STOP mode. XSelect CYCLE TIME and press OK. The following menu appears: XPress OK.
EZ500_700.book Page 226 Tuesday, May 3, 2005 5:15 PM EZ Settings Retention (non-volatile data storage) It is a requirement of system and machine controllers for operating states or actual values to have retentive settings. What this means is that the values will be retained safely even after the supply voltage to a machine or system has been switched off, and will also be retained until the next time the actual value is overwritten. J Factory setting: The retention function is not activated.
EZ500_700.book Page 227 Tuesday, May 3, 2005 5:15 PM Retention (non-volatile data storage) RUN MODE CARD MODE åÆ CYCLE TIME. RETENTION..æ M 9 - M12 åÆ M13 - M16 N 9 - N16 C 5 - C 7 åæ C 8 C13 - C16 å XSwitch to STOP mode. XSwitch to the System menu. XMove to the SYSTEM menu and continue to the RETENTION… menu. XPress the OK button. The first screen display is the selection of the marker range. XÍÚ Select a range.
EZ500_700.book Page 228 Tuesday, May 3, 2005 5:15 PM EZ Settings Deleting retentive actual values The retentive actual values are cleared if the following is fulfilled (applies only in STOP mode): • When the circuit diagram is transferred from EZSoft or the memory card to the EZ control relay, the retentive actual values are reset to 0. This also applies when there is no program on the memory card. In this case the old circuit diagram is retained in EZ.
EZ500_700.book Page 229 Tuesday, May 3, 2005 5:15 PM Retention (non-volatile data storage) Changing the operating mode or the circuit diagram When the operating mode is changed or the EZ circuit diagram is modified, the retentive data is normally saved together with their actual values. The actual values of relays no longer being used are also retained. Changing the operating mode If you change from RUN to STOP and then back to RUN, the actual values of the retentive data will be retained.
EZ500_700.book Page 230 Tuesday, May 3, 2005 5:15 PM EZ Settings Displaying device information Device information is provided for service tasks and for determining the capability of the device concerned. This function is only available with devices featuring a display. Exception: Terminal mode with the EZD.
EZ500_700.book Page 231 Tuesday, May 3, 2005 5:15 PM 6 EZ circuit diagram cycle Inside EZ In conventional control systems, a relay or contactor control processes all the rungs in parallel. The speed with which a contactor switches in this case depends on the components used, and ranges from 15 to 40 ms for relay pick-up and drop-out.
EZ500_700.book Page 232 Tuesday, May 3, 2005 5:15 PM Inside EZ The fifth segment is outside the circuit diagram and EZ uses it to establish contact to the “outside world”: The output relays Q1 to Q... are switched and inputs I1 to I.. are read again. EZ also copies all the new switching states to the status image register. EZ only uses this status image for one cycle.
EZ500_700.book Page 233 Tuesday, May 3, 2005 5:15 PM EZ circuit diagram cycle I1uI2----ÄQ1 Q1k Example: switching in the next cycle Start condition: • I1, I2 switched on • Q1 switched off. This is the circuit diagram of a self-latching circuit. If I1 and I2 are closed, the switching state of relay coil ÄQ1 is latched via contact Q1. • 1st cycle: Inputs I1 and I2 are switched on. Coil ÄQ1 picks up. • Contact Q1 remains switched off since EZ evaluates from left to right.
EZ500_700.book Page 234 Tuesday, May 3, 2005 5:15 PM Inside EZ Delay times for inputs and outputs The time from reading the inputs and outputs to switching contacts in the circuit diagram can be set in EZ via the delay time. This function is useful, for example, in order to ensure a clean switching signal despite contact bounce.
EZ500_700.book Page 235 Tuesday, May 3, 2005 5:15 PM Delay times for inputs and outputs An input signal S1 must therefore be 15 V or 8 V (EZ-DA) for at least 20 ms on the input terminal before the switch contact will change from 0 to 1 (range A). If applicable, this time must also include the cycle time (range B) since EZ does not detect the signal until the start of a cycle. The same time delay (range C) applies when the signal drops out from 1 to 0.
EZ500_700.book Page 236 Tuesday, May 3, 2005 5:15 PM Inside EZ Delay time with EZ-AB, EZ-AC basic units The input delay with AC voltage signals depends on the frequency. The appropriate values for 60 Hz are given in brackets.
EZ500_700.book Page 237 Tuesday, May 3, 2005 5:15 PM Delay times for inputs and outputs If a button or switch bounces (A), the delay time may be extended by 40 ms (33 ms) (A). If the debounce delay is switched off, the delay time is reduced. • On delay 20 ms (16.6 ms) • Off delay for I1 to I6 and I9 to I12: 20 ms (16.6 ms) • Off delay for I7 and I8: 100 ms (100 ms) with EZ-AB, EZ-AC S1 Figure 87: 1 1 A B On and off delays EZ switches the contact as soon as it detects a pulse (A).
EZ500_700.book Page 238 Tuesday, May 3, 2005 5:15 PM Inside EZ Monitoring of short-circuit/ overload with EZ..-D.-T.. Depending on the type of EZ in use, it is possible to use the internal inputs I15 and I16, R15, R16 to monitor for shortcircuits or overloads on an output. • EZ512-...-T..: I16 = Group fault alarm for outputs Q1 to Q4. • EZ721.-..-T..: – I16 = Group fault alarm for outputs Q1 to Q4. – I15 = Group fault alarm for outputs Q5 to Q8. • EZ620-D.
EZ500_700.book Page 239 Tuesday, May 3, 2005 5:15 PM Expanding EZ700 I1-m16----ÄQ1 I16-------SM16 M16-------TT8 T8-------RM16 M16-------ÄQ4 Expanding EZ700 Example 3: Automatic reset of error signal The circuit diagram functions in the same way as Example 2. In addition the marker M16 is reset every 60 seconds by timing relay T8 (on-delayed, 60 s). Should I16 remain at 1, M16 will continue to be set. Q1 is set briefly to 1 until I16 switches off again. You can expand EZ700 with EZ618-..
EZ500_700.book Page 240 Tuesday, May 3, 2005 5:15 PM Inside EZ These modules offer considerably more functions than simple I/O expansion modules. Depending on type, all the data of the program can be read and setpoints can be written. The functions of the individual devices are described in the relevant documentation. How is an expansion unit recognized EZ checks cyclically whether a device is sending data on EZ-LINK.
EZ500_700.book Page 241 Tuesday, May 3, 2005 5:15 PM Expanding EZ700 Function monitoring of expansion units If the power supply of the expansion unit is not present, no connection can be established between it and basic unit. The expansion inputs R1 to R12, R15, R16 are incorrectly processed in the basic unit and show status 0. It cannot be assured that the outputs S1 to S8 are transferred to the expansion unit.
EZ500_700.book Page 242 Tuesday, May 3, 2005 5:15 PM Inside EZ Example with LCD output and reset of the outputs I14-m1----Ä:1 ---------SM1 I14--------Ä:1 I2uI3----ÄQ1 Q1k -----------Ä:8 :1------uÄD1 :8 hRQ1 Saving and loading circuit diagrams You can either use the EZ interface to save circuit diagrams to a memory card or use EZSoft and a transmission cable to transfer them to a PC. EZ…-..-..
EZ500_700.book Page 243 Tuesday, May 3, 2005 5:15 PM Saving and loading circuit diagrams DANGER of electric shock with EZ-AC units! If the voltage terminals for phase (L) and neutral conductor (N) are reversed, the connected 230 V/115 V voltage will be present at the EZ interface. There is a danger of electric shock if the plug is not properly connected or if conductive objects are inserted into the socket. Figure 88: Do not touch the interface XCarefully remove the cover with a screwdriver.
EZ500_700.book Page 244 Tuesday, May 3, 2005 5:15 PM Inside EZ Memory card The card is available as an accessory EZ-M-32K for EZ500 and EZ700. Circuit diagrams with all the data can be transferred to the EZ500 and EZ700 from the EZ-M-32K memory card. A transfer, however, in the other direction is not possible. Each memory card can hold one EZ circuit diagram. Information stored on the memory card is “non-volatile” and thus you can use the card to archive, transfer and copy circuit diagrams.
EZ500_700.book Page 245 Tuesday, May 3, 2005 5:15 PM Memory card J With EZ you can insert and remove the memory card even if the power feed is switched on, without the risk of losing data. Loading or saving circuit diagrams You can only transfer circuit diagrams in STOP mode.
EZ500_700.book Page 246 Tuesday, May 3, 2005 5:15 PM Inside EZ J EZ-M-32K The memory card is detected when the card is inserted and you move from the main menu to the program menu. As read access to the EZ-M-32K card is possible, the card can only be removed in the Status display. This ensures that the correct card is always detected. Only the EZ-M-32K memory card can be written to. PROGRAM DELETE PROG CARD XSwitch to STOP mode. XSelect PROGRAM… from the main menu. XSelect the CARD… menu option.
EZ500_700.book Page 247 Tuesday, May 3, 2005 5:15 PM Memory card DEVICE-CARD CARD-DEVICE DELETE CARD Loading a circuit diagram from the card XSelect the CARD J DEVICE menu option. XPress OK to confirm the prompt if you want to delete the EZ memory and replace it with the card content. Press ESC to go back one menu. Attention! Once you have started the CARD J DEVICE transfer, the following operation is initiated: • The RAM of the device is loaded from the card. • The internal program memory is cleared.
EZ500_700.book Page 248 Tuesday, May 3, 2005 5:15 PM Inside EZ EZSoft EZSoft is a PC program with which you can create, store, test (simulate) and manage EZ circuit diagrams. J You should only transfer data between the PC and EZ using the special PC interface cable, which is available as an optional accessory EZ-PC-CAB. DANGER of electric shock with EZ-AC units! Only the EZ-PC CAB cable will guarantee reliable electrical isolation from the interface voltage.
EZ500_700.book Page 249 Tuesday, May 3, 2005 5:15 PM Overview with stand-alone display INVALID PROG If there are transmission problems, EZ will display the INVALID PROG message. XCheck whether the circuit diagram is suitable for the destination device. J If the operating voltage fails during communication with the PC, repeat the last step. It is possible that not all the data was transferred between the PC and EZ.
EZ500_700.book Page 250 Tuesday, May 3, 2005 5:15 PM Inside EZ If a display/operating unit with a keypad is used, EZ can be programmed and assigned parameters from “outside”. J Card mode operation is not possible when using a standalone display/operating unit. The interface can only be used once. The EZD-80 (IP65 display unit), EZD-80-B (IP65 display/ operating unit) with the EZD-CP4-500 power supply/ communication unit are currently available for use as standalone display/operating units.
EZ500_700.book Page 251 Tuesday, May 3, 2005 5:15 PM 7 What Happens If ...? You may sometimes find that EZ does not do exactly what you expect. If this happens, read through the following notes which are intended to help you solve some of the problems you may encounter. You can use the power flow display in EZ to check the logic operations in the EZ circuit diagram with reference to the switching states of contacts and relays.
EZ500_700.book Page 252 Tuesday, May 3, 2005 5:15 PM What Happens If ...
EZ500_700.
EZ500_700.book Page 254 Tuesday, May 3, 2005 5:15 PM What Happens If ...? Event Event Explanation Remedy The actual values are not being stored retentively. Retention has not been switched on. Switch on retention in the SYSTEM menu. The RETENTION... menu is not displayed in the SYSTEM menu. EZ is in RUN mode Select STOP mode The SYSTEM menu is not displayed. This EZ model does not have this menu.
EZ500_700.book Page 255 Tuesday, May 3, 2005 5:15 PM Appendix Dimensions 45 110 90 102 7.5 4.5 M4 7.5 47.5 35.5 56.5 58 Figure 94: MN05013003E Dimensions of EZ200 in mm (for dimensions in inches see page 257, table 34) For more information visit: www.EatonElectrical.
EZ500_700.book Page 256 Tuesday, May 3, 2005 5:15 PM Appendix 45 110 90 50 102 10.75 4.5 M4 47.5 35.75 56.5 71.5 58 Figure 95: 256 Dimensions of EZ512-… in mm (for dimensions in inches see page 257, table 34) For more information visit: www.EatonElectrical.
EZ500_700.book Page 257 Tuesday, May 3, 2005 5:15 PM Dimensions 16.25 75 16.25 45 110 90 102 M4 4.5 47.5 107.5 56.5 58 MN05013003E Figure 96: Dimensions of EZ700 in mm (for dimensions in inches see table 34) Table 34: Dimensions in inches mm inches mm inches 4.5 0.177 56.5 2.22 7.5 0.295 58 2.28 10.75 4.23 71.5 2.81 16.25 0.64 75 2.95 35.5 1.4 90 3.54 35.75 1.41 102 4.01 45 1.77 107.5 4.23 47.5 1.87 110 4.33 50 1.97 For more information visit: www.
EZ500_700.book Page 258 Tuesday, May 3, 2005 5:15 PM Appendix Technical Data General EZ… EZ200 EZ512 EZ700 [mm] 35.5 × 90 × 56.5 71.5 × 90 × 56.5 107.5 × 90 × 56.5 [inches] 1.4 × 3.54 × 2.08 2.81 × 3.54 × 2.08 4.23 × 3.54 × 2.08 2 space units wide 4 SU (space units) wide 6 SU (space units) wide [g] 70 200 300 [lb] 0.154 0.441 0.
EZ500_700.book Page 259 Tuesday, May 3, 2005 5:15 PM Technical Data Oscillations (IEC 60068-2-6) 10 to 57 Hz (constant amplitude 0.
EZ500_700.book Page 260 Tuesday, May 3, 2005 5:15 PM Appendix Backup/accuracy of real-time clock (only with EZ-C) Clock battery back-up 200 180 160 140 120 a 100 80 60 40 20 0 25˚C 55˚C 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 b = backup time in hours = service life in years Accuracy of the real-time clock Normally ± 5 s/day, ~ ±0.
EZ500_700.book Page 261 Tuesday, May 3, 2005 5:15 PM Technical Data Power supply EZ512-AC-…, EZ719-AC-…, EZ512-AB-…, EZ719-AB-… EZ512-AB-…, EZ719-AB-… EZ512-AC-…, EZ719-AC-… 24 V AC 100/110/115/120/230/240 V AC +10/–15 % 20.4 to 26.4 V AC +10/–15 % 85 to 264 V AC Frequency, rated value, tolerance 50/60 Hz, ± 5 % 50/60 Hz, ±5 % Input current consumption EZ512-AB-… EZ719-AB-… EZ512-AB-… EZ719-AB-...
EZ500_700.book Page 262 Tuesday, May 3, 2005 5:15 PM Appendix EZ512-DA-…, EZ719-DA-… EZ512-DC-…, EZ719-DC-…, EZ721-DC-… Voltage dips 10 ms, IEC/EN 61131-2 Power loss EZ512-DA-… EZ719-DA-… EZ512-DC-… EZ7..-DC-… Normally 2 mA/3.5 mA Normally 2 W/normally 3.5 W Inputs EZ-512-AB-…, EZ719-AB-… EZ-512-AB-… EZ719-AB-...
EZ500_700.book Page 263 Tuesday, May 3, 2005 5:15 PM Technical Data EZ-512-AB-… EZ719-AB-... Delay time for 0 to 1 and 1 to 0 for I1 to I8, EZ719… also I9 to I12 Debounce ON 80 ms (50 Hz), 662/3 ms (60 Hz) 80 ms (50 Hz), 662/3 ms (60 Hz) Debounce OFF 20 ms (50 Hz), 162/3 ms (60 Hz) 20 ms (50 Hz), 162/3 ms (60 Hz) Max. permissible cable length (per input) I1 to I8, (with EZ719… also I9 to I10) Normally 40 m Normally 40 m EZ-512-AC-…, EZ618-AC-.E, EZ719-AC-… EZ-512-AC-… EZ618-AC-.E, EZ719-AC-...
EZ500_700.book Page 264 Tuesday, May 3, 2005 5:15 PM Appendix EZ-512-AC-… EZ618-AC-.E, EZ719-AC-... Input current with 1 signal R1 to R12, I1 to I6 (EZ71. also I9 to I12) 6 × 0.5 mA at 230 V AC 50 Hz, 6 × 0.25 mA at 115 V AC 60 Hz 10 × (12) 0.5 mA at 230 V AC, 50 Hz 10 × (12) × 0.
EZ500_700.book Page 265 Tuesday, May 3, 2005 5:15 PM Technical Data EZ512-DA-… EZ719-DA-… LCD (if provided) LCD (if provided) To power supply No No Between each other No No To the outputs Yes Yes Rated value 12 V DC 12 V DC 0 signal 4 V DC (I1 to I8) 4 V DC (I1 to I12) 1 signal 8 V DC (I1 to I8) 8 V DC (I1 to I12) 3.3 mA at 12 V DC (I1 to I6) 3.3 mA at 12 V DC (I1 to I6, I9 to I12) 1.1 mA at 12 V DC 1.1 mA at 12 V DC Debounce ON 20 ms 20 ms Debounce OFF Normally 0.
EZ500_700.book Page 266 Tuesday, May 3, 2005 5:15 PM Appendix EZ512-DC-… Status display EZ6..-DC-.E EZ7..-DC-… LCD (if provided) Electrical isolation To power supply No No No Between each other No No No To the outputs Yes Yes Yes Rated value 24 V DC 24 V DC 24 V DC 0 signal < 5 V DC (I1 to I8) < 5 V DC (R1 to R12) < 5 V DC (I1 to I12) 1 signal > 8 V DC (I7, I8) Rated voltage Input current on 1 signal I7, I8 (EZ7..-DC-..
EZ500_700.
EZ500_700.book Page 268 Tuesday, May 3, 2005 5:15 PM Appendix EZ512-AB-…, EZ512-DA-…, EZ512-DC-… EZ719-AB-…, EZ719-DA-…, EZ719-DC-…, EZ721-DC-… Conversion time, analog/digital Debounce ON: 20 ms Debounce OFF: every cycle Input current at 10 V DC 1 mA 1 mA Cable length (shielded) 30 m 30 m Relay outputs EZ512-..-R…, EZ618-..-RE/EZ719-..-R.., EZ202-RE EZ512-…-R… EZ618-..-RE/ EZ719-..-R..
EZ500_700.book Page 269 Tuesday, May 3, 2005 5:15 PM Technical Data EZ512-…-R… Rated operational voltage Ue 250 V AC Safe isolation to EN 50178 between coil and contact 300 V AC Safe isolation to EN 50178 between two contacts 300 V AC EZ618-..-RE/ EZ719-..-R..
EZ500_700.book Page 270 Tuesday, May 3, 2005 5:15 PM Appendix UL/CSA Uninterrupted current at 240 V AC/24 V DC 10/8 A AC Control Circuit Rating Codes (Utilization category) B300 Light Pilot Duty Max. rated operational voltage 300 V AC Max. thermal continuous current cos ϕ = 1 with B300 5A Maximum make/break capacity cos ϕ ≠ 1(Make/break) with B300 3600/360 VA Control Circuit Rating Codes (Utilization category) R300 Light Pilot Duty Max. rated operational voltage 300 V DC Max.
EZ500_700.book Page 271 Tuesday, May 3, 2005 5:15 PM Technical Data EZ512-D.-T… EZ620-DC-.E, EZ72… < 0.1 mA < 0.1 mA On 0 signal with ext. load < 10 MΩ 2.5 V 2.5 V On 1 signal, Ie = 0.5 A U = Ue – 1 V U = Ue – 1 V Residual current at state 0 per channel Max. output voltage Short-circuit protection Yes, thermal (detected via diagnostics input I16, I15; R16;R15) Short-circuit tripping current for Ra 10 mΩ 0.7 A Ie 2 A per output Max.
EZ500_700.book Page 272 Tuesday, May 3, 2005 5:15 PM Appendix EZ512-D.-T… EZ620-DC-.E, EZ72… Number of outputs max. 4 max. 4 Total maximum current 2.0 A, Attention! Outputs must be actuated simultaneously and for the same time duration. LCD display (if provided) Status display of the outputs Inductive load (without external suppressor circuit) General explanations: T0.95 = time in milliseconds until 95 % of the stationary current is reached. T0.95 ≈ 3 × T0.
EZ500_700.book Page 273 Tuesday, May 3, 2005 5:15 PM List of the function relays T0.95 = 15 ms R = 48 Ω L = 0.24 H Utilization factor g = 0.25 Relative duty factor % 100 Maximum switching frequency f = 0.5 Hz Maximum duty factor DF = 50 % Operations/h 1500 Inductive load with external suppressor circuit for each load (see section “Connecting transistor outputs” on page 54) g=1 Utilization factor Relative duty factor % 100 Max. switching frequency Max.
EZ500_700.
EZ500_700.
EZ500_700.book Page 276 Tuesday, May 3, 2005 5:15 PM Appendix Name of function block inputs (constants, operands) Input Meaning of abbreviation Description F1 Factor 1 Gain factor for I1 (I1 = F1 × Value) F2 Factor 2 Gain factor for I2 (I2 = F2 × Value) HY Hysteresis Switching hysteresis for value I2 (Value HY applies to positive and negative hysteresis.
EZ500_700.book Page 277 Tuesday, May 3, 2005 5:15 PM Glossary Analog input The device EZ-AB, EZ-DA and EZ-DC are provided with the two (EZ500) and four (EZ700) analog inputs I7, I8 and I11,I12. The input voltage range is 0 V to 10 V. The measuring data is evaluated with the integrated function relays. Circuit diagram elements As in conventional wiring, the circuit diagram is made up of circuit elements. These include input, output and marker relays, plus function relays and P buttons.
EZ500_700.book Page 278 Tuesday, May 3, 2005 5:15 PM Glossary Impulse relay An impulse relay is a relay which changes its switching state and retains its new state (latched) when a voltage is applied to the relay coil for a short time. Input The inputs are used to connect up external contacts. In the circuit diagram, inputs are evaluated via contacts I1 to I12 and R1 to R12. EZ-AB, EZ-DA and EZ-DC can also receive analog data via the inputs I7, I8 and I11, I 12.
EZ500_700.book Page 279 Tuesday, May 3, 2005 5:15 PM Operating buttons EZ has eight operating buttons. These are used to select menu functions and create circuit diagrams. The large round button in the middle is used to move the cursor. DEL, ALT, ESC and OK all perform additional functions. Output You can connect various loads to the four EZ outputs, such as contactors, lamps and motors. In the EZ circuit diagram the outputs are controlled via the corresponding output relay coils Q1 to Q8 or S1 to S8.
EZ500_700.book Page 280 Tuesday, May 3, 2005 5:15 PM Glossary Remote expansion I/O expansion with the expansion unit (e.g. EZ620-DC-TE) installed up to 30 m away from the basic unit. The EZ200-EZ coupling unit is fitted to the basic unit. The input and output data is exchanged between expansion and basic unit via a two-wire cable.
EZ500_700.book Page 281 Tuesday, May 3, 2005 5:15 PM Index 7-day time switch Compatibility of parameters .......................... 282 MN05013003E A Ambient conditions ............................................... 258 Analog Comparing two values .................................. 114 Input ........................................................44, 277 Input power supply ......................................... 46 Input, resolution ............................................
EZ500_700.book Page 282 Tuesday, May 3, 2005 5:15 PM Index Buttons ................................................................... 18 Buttons for circuit diagram editing .......................... 73 C 282 Cable cross-sections .............................................. 33 Cable lengths ......................................................... 39 Cable protection ...............................................33, 36 Cables ....................................................................
EZ500_700.book Page 283 Tuesday, May 3, 2005 5:15 PM Coil function Contactor ........................................................ 90 Impulse relay .................................................. 93 Latching relay ................................................. 94 Negate ............................................................ 91 Overview ......................................................... 89 Commissioning ...................................................... 61 Comparator functions ....
EZ500_700.book Page 284 Tuesday, May 3, 2005 5:15 PM Index Connecting DC voltage .......................................... 35 Connecting frequency generators .......................... 49 Connecting the brightness sensor ......................... 48 Connecting the setpoint potentiometer .................. 47 Connection cross-sections ..................................... 33 Connections Deleting .......................................................... 85 Contact .........................................
EZ500_700.book Page 285 Tuesday, May 3, 2005 5:15 PM Current Input ..........................................................39, 44 Input current, increasing ................................. 41 Cursor buttons .................................................18, 87 Activate ......................................................... 220 Deactivate ..................................................... 221 See P buttons ............................................... 279 Cursor display ........................
EZ500_700.book Page 286 Tuesday, May 3, 2005 5:15 PM Index Example circuits ................................................... 186 Expanding EZ ...................................................... 239 Expansion ............................................................ 239 Connecting ..................................................... 32 Detecting ...................................................... 240 Local ............................................................. 278 Monitoring ...........
EZ500_700.book Page 287 Tuesday, May 3, 2005 5:15 PM MN05013003E I Improper use .......................................................... 11 Impulse relay ..........................................93, 184, 278 Input ..................................................................... 278 Analog resolution .......................................... 105 Analog, power supply ..................................... 46 Connecting ...............................................37, 42 Connecting analog inputs .
EZ500_700.book Page 288 Tuesday, May 3, 2005 5:15 PM Index 288 M Main menu Overview ......................................................... 22 Selection ......................................................... 19 Maintenance meters ............................................ 147 Make contact ..................................................76, 273 Inverting .......................................................... 83 Marker relay ...................................................89, 233 Markers .
EZ500_700.book Page 289 Tuesday, May 3, 2005 5:15 PM O MN05013003E Operating buttons ..........................................73, 279 Operating hours counter ...................................... 145 Operating modes ................................................... 63 Operating unit ...................................................... 249 Operation ...................................................18, 73, 74 OR circuit ............................................................. 180 Output ......
EZ500_700.book Page 290 Tuesday, May 3, 2005 5:15 PM Index P 290 P buttons .............................................................. 279 Activate ......................................................... 220 Activating and deactivating ........................... 220 Deactivate ..................................................... 221 See Cursor buttons ......................................... 87 Parameter display .................................................. 74 Timing relays ................
EZ500_700.book Page 291 Tuesday, May 3, 2005 5:15 PM R MN05013003E Reaction time for I/O ............................................ 240 Reed relay contacts ............................................... 40 Relay ................................................................75, 80 Connecting analog outputs ............................. 52 Contactor function .......................................... 90 Impulse ........................................................... 93 List of all ................
EZ500_700.book Page 292 Tuesday, May 3, 2005 5:15 PM Index Rungs ................................................................... 280 Add new .......................................................... 68 Change ........................................................... 84 Creating .......................................................... 84 Deleting .......................................................... 86 Insert ...............................................................
EZ500_700.book Page 293 Tuesday, May 3, 2005 5:15 PM MN05013003E T Target readership ................................................... 11 Technical data ...................................................... 258 General ......................................................... 258 Inputs ............................................................ 262 Power supply ................................................ 261 Relay output ................................................. 268 Transistor output ..
EZ500_700.book Page 294 Tuesday, May 3, 2005 5:15 PM Index 294 V Value entry ............................................................. 18 Voltage range, input .........................................39, 44 W Weekday setting .................................................. 209 What happens If ...? ............................................. 251 Wiring ..................................................................... 73 Backwards ....................................................
EZ500_700.
EZ500_700.book Page 2 Tuesday, May 3, 2005 5:15 PM Re-Order from OmegamationTM 1-888-55-66342 1-888-55-OMEGA omegamation.com Eaton Electrical 1000 Cherrington Parkway Moon Township, PA 15108-4312 USA Tel: 1-800-525-2000 www.EatonElectrical.com © 2005 Eaton Corporation All Rights Reserved Printed in USA Publication No.