Specifications
23
EATON Powerware Series Product Catalogue
Eaton 5115 UPS
1. LED user interface
2. Panel for replacing batteries
3. 1 USB port + 1 serial port
4. Dataline (network) protection
5. 4 to 6 IEC 10A sockets
TECHNICAL SPECIFICATION
Rating 500 VA 750 VA 1000 VA 1400 VA
Part number 05146549-5591 05146555-5591 05146561-5591 05146567-5591
Capacity (VA/watts) 500/320 750/500 1000/670 1400/950
Dimensions WxDxH (mm) 150x268x185 150x333x185 150x333x185 150x388x185
Weight (kg) 8 12 13 17
Input connection IEC320/10A IEC320/10A IEC320/10A IEC320/10A
Output connection 4xIEC320/10A 4xIEC320/10A 6xIEC320/10A 6xIEC320/10A
Typical runtime (full load)
(half load)
5 min
15 min
6 min
17 min
5 min
15 min
5 min
15 min
Operational
Nominal input voltage (Vac) 220/230/240 Vac
Input voltage range 184-276 VAC(± 20% of nominal)
Operating frequency 50/60 Hz auto sensing
Input power factor Same as load
Nominal output voltage 220/230/240 Vac
Output voltage regulation -10%/+6% of selected nominal voltage
Overload capacity 110% 3 min; 150% 10 cycles
Efficiency 95%
User interface
LED Four LEDs; UPS on, UPS on battery, overload, alarm
Standard communication ports RS232 & USB
Optional External SNMP adapter
Environmental
Operating temperature 0°C - +40°C
Storage temperature -15°C -+55°C
Altitude <3000 m
Audible noise at 1 metre <40 dB
Certification
Markings CE
Safety IEC 62040-1-1, UL 1778
EMC IEC 62040-2
EATON 5115 RUNTIMES FOR TYPICAL APPLICATIONS
Load VA / W 500 VA 750 VA 1000 VA 1400 VA
200 VA / 128 W 17 38 41 58
300 VA / 192 W 11 27 28 41
500 VA / 320 W 5 14 15 28
600 VA / 400 W 9 10 19
750 VA / 500 W 6 8 14
900 VA / 600 W 6 10
1000 VA / 670 W 5 8
1200 VA / 800 W 6
1400 VA / 950 W 5
1
2
1
2
5
4
3