The System Setup Menu
From the System Setup menu, use the Menu button to return to the Main Menu. When
altering settings under the System Setup menu, the Select button saves a change and
the Menu button cancels the change (unless otherwise indicated). An asterisk (*)
displayed on the left side of the item indicates that the item is currently selected.
The System Setup menu contains the following options:
1. Select Type
2. H. W. Modules
3. Sync Range
4. Adj Out Volts
5. Comm Setup
6. Relay Setup
7. Set Language
8. Set Time & Date
9. Contrast Adj
10. Horn Volume
11. Clr Alarm Queue
12. Set User Pwd
13. Battery Config
Use the up and down arrow buttons to display the System Setup options. Press the
Select button to enter one of the submenus.
  
Use the Select Type option to select the output voltage and output frequency type for
the UPS. The UPS kVA rating is displayed for information only, it cannot be changed.
Use the right and left arrow buttons to display all options for each category. Press the
Select button to save an option. In this submenu, pressing the Menu button does not
cancel changes; it returns the cursor to the previous menu.
The UPS must be off and the output breaker must be open (O) in order to change the
Select Type setting. If the UPS not turned off and the output breaker is closed(I),you
can only view the type setting.
After selecting a new type option, press the Menu button to exit the Select Type
submenu before turning on the UPS.