Paragon II use requires P2CIM-PWR and straight CAT5 cable. You can associate up to four
outlets to a target; all four outlets can be from separate Revelation PDU strips, if necessary.
Use Raritan’s Paragon Manager Application to configure associations:
15. In Paragon Manager, select the target.
16. Click on the target icon and drag-and-drop it on the desired outlets.
17. The outlets will be renamed to the associated target’s name automatically.
18. To turn on, turn off, or recycle power to the target, click on the target and press the F3 key;
select On, Off, or Recycle power from the drop-down menu.
How to add an Revelation PDU Strip in Paragon II
Add an Revelation PDU strip exactly as you would add any second-tier device. Your Paragon II
unit auto-detects the power strip and changes the device type to PCR8, PCS12, PCS20, or PCR20.
On the Channel Configuration screen, press F5, select the channel and change the channel name
from the default name to an identifying name for the Revelation PDU strip.