User guide
C
HAPTER
3: U
SING THE
9
lower row of the display panel will jump to the lowest outlet number affected by the circuit
breaker error, and the upper row will display these three letters
CbE
which means circuit breaker error.
You will still be able to switch between outlets on the Revelation PDU’s display panel. Outlets
affected by the error will show CbE. Unaffected outlets will show the current and voltage
readings as described above.
To reset the breakers in the event of an overload: On the 1U and 2U products unclip the front
molding to access the breaker(s). On the zero-U product the breaker(s) can be accessed by lifting
the hinged cover over the breaker element.
+
The Revelation PDU includes a beeper. It will ring if any of the circuit breakers is trips or if the
control board temperature sensor exceeds 80 degrees Celsius.
The beeper will cease ringing when the broken circuit breaker conditions disappear or the control
board temperature sensor drops below 70 degrees Celsius.