User guide

8 D
OMINION
PX U
SER
G
UIDE
.
The number of outlets on the back panel depends upon the Revelation PDU model. To the upper
left of each outlet is a small LED. The table below explains how to interpret the different LED
states.
LED S
TATE
O
UTLET
S
TATUS
W
HAT IT
M
EANS
Not lit OFF
The outlet is not connected to power or the
control circuitry’s power supply is broken.
Red ON and LIVE
The outlet is ON (relay closed) and LIVE
(voltage present).
Red flashing ON and LIVE
The outlet is ON and LIVE, but there is overload
and the current has crossed the non-critical
threshold.
Green OFF and LIVE The outlet is OFF (relay open) and LIVE.
Green flashing OFF and NOT LIVE The outlet is OFF but NOT LIVE.
Yellow OFF and LIVE
The outlet was shut down because the current
crossed the critical threshold.
Yellow flashing ON and NOT LIVE
The outlet is ON but NOT LIVE (circuit breaker
open or other high voltage rail error).
-'
The display panel is located on the right of the unit’s back panel. It consists of these components:
A lower row displaying two digits
An upper row displaying three digits
Up and Down buttons
42 2
The lower row shows the outlet number.
2
The upper row shows the current, voltage, and power readings for the outlet indicated in the
lower row.
62 .-'
1. Use the Up and Down buttons to select an outlet. Pressing the Up button once moves up one
outlet number. Pressing the Down button once moves down one outlet number.
2. When an outlet is selected, the outlet number is displayed in the lower row and the current in
the upper row. Current is displayed in the format: XX.X (A)
3. To display the voltage for the selected outlet, press the Up and Down buttons simultaneously.
The voltage reading will replace the current for about 5 seconds, after which the current will
return.
4. To display the power…
Tip: A quick way to distinguish between voltage, current, and power is the placement of the
decimal point in the display. Voltage has no decimal point, current has a decimal point between
the first and second digits, and power has a decimal point between the second and third digits.
$+
The Revelation PDU includes branch circuit breakers (units rated over 20A) that automatically
trip when a power overload is detected. If the circuit breaker switches off the voltage rail, the