User`s guide

PARALLEL BYPASS
Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.com/powerquality
66
4. If present, switch the maintenance isolation breaker (MIS) on the
wall-mounted bypass cabinet to the ON position; otherwise, switch
the UPS breakers (may be designated MOB or UPS) on the
wall-mounted bypass cabinet to the ON position.
5. Switch the bypass breaker (may be designated MBP or CBP) in the
wall-mounted bypass cabinet to the OFF position.
The UPS is now powering the load in Bypass mode.
NOTE Use the same UPS that was used to set internal bypass to return the parallel system
to Normal mode.
6. On the same UPS front panel, set the UPS to Normal mode:
S Press the button to select the Go to Normal Mode option.
S Each UPS goes to Normal mode.
The UPS is now powering the load in Normal mode.