Chapter 10 Parallel Bypass
To switch the parallel UPS to maintenance bypass from Normal mode:
1. From any UPS, set the system to internal Bypass mode:
S Using the button on the front panel display, scroll to the Control
menu option and press the
button.
S Press the button to select the Go to Bypass Mode option.
The
indicator illuminates and the indicator extinguishes,
indicating the UPS system is operating in Bypass mode.
2. Switch the bypass breaker (may be designated MBP or CBP) in the
parallel tie cabinet to the ON position.
3. If present, switch the maintenance isolation breaker (MIS) on the
parallel tie cabinet to the OFF position; otherwise, switch the UPS
breakers (may be designated MOB or UPS) on the parallel tie
cabinet to the OFF position.
To return to Normal mode from maintenance bypass:
1. Verify that the maintenance isolation breaker (if present) on the Tie
Cabinet is in the OFF position or all of the UPS breakers are in the
OFF position.
2. Switch on utility power where the UPSs are connected.
In a parallel capacity system (N+0 or N+1), apply utility to the
minimum number of UPSs required for capacity.
The
indicator illuminates, indicating the UPS system is
operating in Bypass mode.
The display indicates On Manual/Maintenance Bypass.
3. Verify voltage is present on the UPS output by checking that an
output voltage reading present on the front panel LCD display.
The load is now powered by utility power.