Restarting the Parallel System
To restart the parallel system:
1. Verify that the maintenance isolation breaker (if present) on the Tie
Cabinet is in the OFF position or all of the UPS breakers are in the
OFF position.
2. Switch on utility power where the UPSs are connected.
3. Wait for the front panel LCD to illuminate.
The
indicator flashes on each UPS.
4. Switch all battery circuit breakers to the ON position.
The
indicator stops flashing on each UPS.
5. Switch the UPS breakers on the parallel tie cabinet to the ON
position.
6. If present, switch the maintenance isolation breaker (MIS) on the
wall-mounted bypass cabinet to the ON position; otherwise, switch
the UPS breakers (may be designated MOB or UPS) on the
wall-mounted bypass cabinet to the ON position.
If the indicator is flashing, do not proceed until all alarms are
clear. Check the UPS status from the front panel to view the active
alarms. Correct the alarms and restart if necessary.
7. Press the
ESC
button once and then press the button to select
the TURN UPS ON/OFF menu.
8. Press the
button to select the System On option; press the
button.
9. Confirm the selection. Press and hold the
button for three
seconds, until the UPS stops beeping.
The UPS goes to Bypass mode for five seconds, and then the
indicator illuminates. Each UPS should be in Normal mode.
10. Press the
ESC
button until the Eaton logo appears.