User`s guide
OPERATION
Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.com/powerquality
58
User Settings
The following table displays the options that can be changed by the user.
NOTE Changes to the output voltage or frequency options should be made before turning
on the UPS; otherwise, the changes do not take effect.
Table 4. User Settings
Description Available Settings Default Setting
Set Date and Time Set Month
Date: mm/dd/yyyy
Time: 24:00
01/01/2003
00:00
Display Contrast Adjust contrast with up/down arrow buttons Moderate
Change Language Select Language: <English>
Elegir idioma <Español>
English
Set NominalOutput Voltage Output:
[120V/208V] [127V/220V]
120V/208V
Relay Config Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or
[X-Slot 2-1/2/3/4]
Setup: [Battery Low] [On Battery] [On
Bypass] [UPS ok] [custom] [empty]
Alarm 1: empty
X-Slots (1 or 2)
#1: UPS ok
#2: On Bypass
#3: Summary Alarm
#4: On Battery
Signal Inputs [empty] [Logic]
Signal Input must be wired to the CAN Bridge
Card (see Figure 36 on page 44).
For more information, refer to “Programmable
Signal Inputs” in the Eaton 9355 UPS
(10/15 kVA) User's Guide.
<empty>
Serial Port Config Port: [X-Slot-1] [X-Slot-2/Serv]
Speed: [19200] [9600] [2400] [1200]
19200
Modem Config
Modem Installation <Not Installed>
Set Modem Call Events Event #0
Call modem: no
Set Modem Init String ATZ0
Set Modem Call Command None
Set Modem Communication Password None