User`s guide
VERSION 2 TIE CABINET PARALLEL INSTALLATION
Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.com/powerquality
32
11. Verify that each UPS battery circuit breaker is in the OFF position
(see Figure 25).
12. From each UPS, remove the UPS wiring access cover and one of
the conduit landing plates and retain.
13. Punch two holes in the conduit landing plate for the input and
output conduit using a Greenlee punch or similar device.
Battery Circuit Breaker
UPS Wiring
Access Cover
Conduit Landing Plates
Figure 25. UPS Rear View (3-High Shown)