Powerware Series ® Eaton 9355 Parallel UPS 10/15 kVA User's Guide
Powerware Series ® Eaton 9355 Parallel UPS 10/15 kVA User's Guide
Class A EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives: S Harmonized Standards: IEC 62040-1-1 and IEC 62040-2; IEC 60950 Third Edition S EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits 93/68/EEC, Amending Directive 73/23/EEC 89/336/EEC, Council Directive relating to electromagnetic compatibility 92/31/EEC, Amending Directive 89/336/EEC relating to EMC The EC Dec
Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol. CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for additional information, such as important operating and maintenance instructions. This symbol indicates that you should not discard the UPS or the UPS batteries in the trash.
Table of Contents 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 UPS Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Inspecting the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS 10 Parallel Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 11 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Typical Alarms and Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Silencing the Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1 Introduction A parallel system with up to four uninterruptible power supplies (UPSs) can be installed to provide a parallel capacity and/or redundant system. This load sharing system provides more capacity than a single UPS and can provide backup, depending on the load and configuration. In addition, when one UPS is taken out of service for maintenance or is not operating properly, a redundant UPS continues to supply uninterrupted power to the critical load.
INTRODUCTION 2 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
Chapter 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference. DANGER This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
SAFETY WARNINGS Consignes de Sécurité CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ IMPORTANTES DANGER! Cet onduleur contient des TENSIONS MORTELLES. Toute opération d'entretien et de réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ. AUCUNE PIÈCE RÉPARABLE PAR L'UTILISATEUR ne se trouve dans l'onduleur. WARNING S Cet onduleur renferme sa propre source d'énergie (batteries).
SAFETY WARNINGS Advertencias de Seguridad INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD IMPORTANTES PELIGRO Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico deben ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO AUTORIZADO. No hay NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE. WARNING S Este SIE contiene su propia fuente de energía (las baterías).
SAFETY WARNINGS 6 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
Chapter 3 UPS Setup This chapter describes: S Equipment inspection S Floor loading and clearances S Unloading the cabinet(s) The instructions are intended for the chief operator/system supervisor, electrical consultants, and installation electricians. Local regulations and electrical code must be followed during the UPS installation.
UPS SETUP Floor Loading When planning the installation, consider the UPS weight for floor loading. The strength of the installation surface must be adequate for point and distributed loadings. The approximate weights are shown in the following table. Standard Model Floor Loadings (2-High/3-High Cabinets) Eaton 9355 UPS Maximum Weight Point Loading lb/in2 (kg/cm2) 2-High UPS 381 lb (173 kg) 95 (6.7) 3-High UPS-32 587 lb (266 kg) 147 (10.3) 3-High UPS-64 619 lb (281 kg) 155 (10.
UPS SETUP Unloading the Cabinet(s) The following tools are required for unloading the cabinet(s): S 15 mm wrench or socket S 7 mm nut driver or socket CAUTION The UPS and Extended Battery Module (EBM) are heavy (see page 8). Unloading the cabinets requires at least two people to safely remove the cabinets from the pallet. To unload three-high cabinets or two-high EBMs, continue to the following section. To unload two-high UPS cabinets, proceed to page 13.
UPS SETUP 2. Remove the four M4 screws securing the stabilizing bracket to the cabinet rear panel and remove the bracket (see Figure 3). Retain the hardware for later use. NOTE Retain the stabilizing bracket and hardware for later re-assembly onto the cabinet. 3. Remove the front cover from the bottom cabinet to access the front shipping bracket. Press and release the handle latch at the bottom of the cover and then lift the cover up and off the cabinet. 4.
UPS SETUP NOTE Hold the back of the cabinet so that the bolts can be removed easily without the cabinet rolling backward. 5. Remove the two M10 bolts securing the front shipping bracket and remove the bracket. If needed, adjust the leveling feet to release the bracket. Front Shipping Bracket M10 Bolts Stabilizing Bracket M10 Bolts M4 Screws Shipping Pad Figure 3. Removing the Brackets and Shipping Pad 6. Reinstall the front cover removed in Step 3.
UPS SETUP NOTE Support the front and back of the cabinet when rolling it off the pallet to prevent tipping. 7. Slowly roll the cabinet toward the rear of the pallet. Once the pallet tilts, continue rolling the cabinet down the pallet until the cabinet touches the floor (see Figure 4). If needed, adjust the leveling feet so that the cabinet rolls freely. Figure 4. Unloading the Cabinet 8. With the cabinet supported, slowly pull the pallet away from the cabinet (see Figure 5). Figure 5.
UPS SETUP Two-High UPS Cabinets To remove a two-high UPS from the shipping pallet: 1. Remove the M10 bolt securing the vertical bracket to the pallet (see Figure 6). 2. Remove and retain the three M4 screws securing the vertical bracket to the UPS. Remove the vertical bracket. M4 Screws M10 Bolt Figure 6. Removing the Vertical Bracket 3. Reinstall the M4 screws to the UPS (see Figure 7). M4 Screws Figure 7.
UPS SETUP 4. Repeat Steps 1 through 3 to remove the vertical bracket on the other side. 5. Remove the front cover from the bottom cabinet to access the front shipping bracket. Press and release the handle latch at the bottom of the cover and then lift the cover up and off the cabinet. 6. Remove the three M10 bolts securing the rear shipping pad to the pallet and remove the shipping pad (see Figure 8).
UPS SETUP 8. Reinstall the front cover removed in Step 5. Hang the top edge of the cover on the cabinet first, then lower the bottom edge and snap into place. NOTE Support the front and back of the cabinet when rolling it off the pallet to prevent tipping. 9. Slowly roll the cabinet toward the rear of the pallet. Once the pallet tilts, continue rolling the cabinet down the pallet until the cabinet touches the floor (see Figure 9). If needed, adjust the leveling feet so that the cabinet rolls freely.
UPS SETUP 10. With the cabinet supported, slowly pull the pallet away from the cabinet (see Figure 10). Figure 10. Removing the Pallet 11. Roll the cabinet to the desired location. 16 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
Chapter 4 Version 1 Tie Cabinet Parallel Installation The Eaton 9355 UPS UPS has the following power connections: S 3‐phase (L1, L2, and L3), neutral, and ground connection for rectifier/bypass input S 3‐phase (L1, L2, and L3), neutral, and ground connection for load output The nominal input/output voltages are: S 120/208 or 127/220 Vac Output overcurrent protection and disconnect switch must be provided by others. Figure 19 and Figure 20 beginning on page 25 show the oneline diagrams.
VERSION 1 TIE CABINET PARALLEL INSTALLATION 4. Determine your equipment's grounding requirements according to your local electrical code. 5. Remove the parallel tie cabinet front cover (see Figure 11). Figure 11. Version 1 Parallel Tie Cabinet Front Cover 6. Remove the internal cover to gain access to the breakers (see Figure 12). Internal Cover Figure 12. Version 1 Internal Cover 18 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
VERSION 1 TIE CABINET PARALLEL INSTALLATION 7. Punch holes for the conduit (AC input, UPS output, load connection, and maintenance bypass contact wires) using a Greenlee® punch or similar device. 8. Verify that the parallel bypass breaker is in the OFF position (see Figure 13). 9. Mount the parallel tie cabinet to the wall and install the conduit. Figure 13. Version 1 Parallel Bypass Breaker 10. Verify that each UPS battery circuit breaker is in the OFF position (see Figure 14). 11.
VERSION 1 TIE CABINET PARALLEL INSTALLATION Battery Circuit Breaker UPS Wiring Access Cover Conduit Landing Plates Figure 14. UPS Rear View (3-High Shown) 20 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
VERSION 1 TIE CABINET PARALLEL INSTALLATION 13. Hardwire the UPS input terminations. See Table 1 for specifications and Figure 15 for a detailed view of the UPS terminal block. NOTE Input neutral must be wired for proper operation. Failure to connect an input neutral will void the warranty. If the optional input transformer is installed, an input neutral is not required. NOTE The Eaton 9355 UPS UPS is a single-feed UPS only. Table 1.
VERSION 1 TIE CABINET PARALLEL INSTALLATION Maintenance Bypass Contacts TB2 Ground Figure 15. UPS Terminal Block (3-High Shown) 14. Hardwire the output terminations from the UPS to the parallel tie cabinet (see Figure 16). Ground Neutral Line 1 Line 2 Line 3 Figure 16. Version 1 UPS Output to Parallel Tie Cabinet Wiring 22 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
VERSION 1 TIE CABINET PARALLEL INSTALLATION 15. Hardwire the load to the parallel tie cabinet (see Figure 17). 16. Wire the maintenance bypass contacts and terminate to the maintenance bypass wires in the parallel tie cabinet (see Figure 15). Connect the black and the red wire to TB2 on the UPS. Cap the blue wire. NOTE The maintenance bypass contacts are normally-open. To ensure proper bypass operation, DO NOT use the blue wire (it is normally-closed). 17.
VERSION 1 TIE CABINET PARALLEL INSTALLATION 19. Wire the AC input to the bypass breaker (see Figure 18). Line 2 Line 3 Line 1 Figure 18. Version 1 Bypass AC Input Wiring 20. Verify the phase rotation for each UPS and the bypass input. 21. Reinstall the internal cover removed in Step 6. 22. Reinstall the parallel tie cabinet front cover removed in Step 5. 23. Continue to “Installing Options” on page 41. 24 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
VERSION 1 TIE CABINET PARALLEL INSTALLATION Red Wire (open when breaker is open) 225A Breaker Auxiliary Contacts 225A Black Wire (common) Blue Wire (closed when breaker is open) Bypass Input 80A (4X) LOAD From UPS 1 Output From UPS 2 Output From UPS 3 Output From UPS 4 Output Figure 19. Version 1 Parallel Wiring Diagram Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
* VERSION 1 TIE CABINET PARALLEL INSTALLATION Figure 20. Version 1 Parallel UPS Schematic 26 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
Chapter 5 Version 2 Tie Cabinet Parallel Installation The Eaton 9355 UPS UPS has the following power connections: S 3‐phase (L1, L2, and L3), neutral, and ground connection for rectifier/bypass input S 3‐phase (L1, L2, and L3), neutral, and ground connection for load output The nominal input/output voltages are: S 120/208 or 127/220 Vac Output overcurrent protection and disconnect switch must be provided by others. Figure 30 and Figure 32 beginning on page 39 show the oneline diagrams.
VERSION 2 TIE CABINET PARALLEL INSTALLATION 4. Determine your equipment's grounding requirements according to your local electrical code. 5. Unfasten the bypass cabinet front door latch and swing the door open (see Figure 21). 6. Follow the instructions on the inside of the door to open or remove the front cover (see Figure 21 and Figure 22). Front Cover Door Latch Door Figure 21.
VERSION 2 TIE CABINET PARALLEL INSTALLATION Internal Cover Front Cover Figure 22. Version 2 Parallel Tie Cabinet Front Cover Open Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
VERSION 2 TIE CABINET PARALLEL INSTALLATION 7. Remove the internal cover to gain access to the breakers (see Figure 23). Internal Cover Figure 23. Version 2 Parrel Tie Cabinet Internal Cover 30 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
VERSION 2 TIE CABINET PARALLEL INSTALLATION 8. Punch holes for the conduit (AC input, UPS output, load connection, and maintenance bypass contact wires) using a Greenlee® punch or similar device. 9. Verify that the parallel bypass breaker is in the OFF position (see Figure 24). 10. Mount the parallel tie cabinet to the wall and install the conduit. Figure 24. Version 2 Parallel Tie Cabinet Bypass Breaker Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
VERSION 2 TIE CABINET PARALLEL INSTALLATION 11. Verify that each UPS battery circuit breaker is in the OFF position (see Figure 25). 12. From each UPS, remove the UPS wiring access cover and one of the conduit landing plates and retain. 13. Punch two holes in the conduit landing plate for the input and output conduit using a Greenlee punch or similar device. Battery Circuit Breaker UPS Wiring Access Cover Conduit Landing Plates Figure 25.
VERSION 2 TIE CABINET PARALLEL INSTALLATION 14. Hardwire the UPS input terminations. See Table 2 for specifications and Figure 26 for a detailed view of the UPS terminal block. NOTE Input neutral must be wired for proper operation. Failure to connect an input neutral will void the warranty. If the optional input transformer is installed, an input neutral is not required. NOTE The Eaton 9355 UPS UPS is a single-feed UPS only. Table 2.
VERSION 2 TIE CABINET PARALLEL INSTALLATION Maintenance Bypass Contacts TB2 Ground Figure 26. UPS Terminal Block (3-High Shown) 34 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
VERSION 2 TIE CABINET PARALLEL INSTALLATION 15. Hardwire the output terminations from the UPS to the parallel tie cabinet (see Figure 27). Neutral Ground Line 1 Line 2 Line 3 Line 1 Line 2 Line 3 Figure 27. Version 2 Tie Cabinet UPS Output to Parallel Tie Wiring Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
VERSION 2 TIE CABINET PARALLEL INSTALLATION 16. Hardwire the load to the parallel tie cabinet (see Figure 28). 17. Wire the maintenance bypass contacts and terminate to the maintenance bypass wires in the parallel tie cabinet (see Figure 26). Connect the black and the red wires from the terminal block on the Tie Cabinet to TB2 on the UPS. NOTE The maintenance bypass contacts are normally-open. To ensure proper bypass operation, DO NOT use the blue wire (it is normally-closed). 18.
VERSION 2 TIE CABINET PARALLEL INSTALLATION Line 1 Line 2 Line 3 Neutral Ground Maintenance Bypass Wiring to UPS TB2 Figure 28. Version 2 Tie Cabinet Load Connections Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
VERSION 2 TIE CABINET PARALLEL INSTALLATION 20. Wire the AC input to the bypass breaker (see Figure 29). Line 1 Line 2 Line 3 Figure 29. Version 2 Tie Cabinet Bypass AC Input Wiring 21. Verify the phase rotation for each UPS and the bypass input. 22. Reinstall the internal cover removed in Step 7. 23. Reinstall the parallel tie cabinet front cover removed in Step 5. 24. Continue to “Installing Options” on page 41. 38 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
VERSION 2 TIE CABINET PARALLEL INSTALLATION Red Wire (open when breaker is open) 225A Breaker Auxiliary Contacts 225A Black Wire (common) Blue Wire (closed when breaker is open) Bypass Input 80A (4X) LOAD From UPS 1 Output From UPS 2 Output From UPS 3 Output From UPS 4 Output Figure 30.
* VERSION 2 TIE CABINET PARALLEL INSTALLATION Figure 32. Version 2 Tie Cabinet Parallel UPS Schematic 40 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
Chapter 6 Installing Options This section describes the Powerware Hot Sync CAN Bridge Card. For other options, such as additional X-Slot® cards, LanSafe® Power Management Software, remote emergency power-off (REPO), relay output contacts, or programmable signal inputs, refer to the Eaton 9355 UPS (10/15 kVA) User's Guide. Figure 33 shows the location of the communication options and control terminals on the UPS.
INSTALLING OPTIONS Powerware Hot Sync CAN Bridge Card The Powerware Hot Sync CAN Bridge Card, shown in Figure 34, can be installed to provide connectivity for operational mode control and metering of a parallel system at any UPS in the system. Plug-In Terminal Block Figure 34. Powerware Hot Sync® CAN Bridge Card To install the Powerware Hot Sync CAN Bridge Card: 1. Remove the front covers of all cabinets, starting with the top cabinet.
INSTALLING OPTIONS 2. Strip shielded, four-wire, twisted-pair wire for CAN Bridge Card wiring. Recommended wire size is 18 AWG maximum. 3. Install the CAN Bridge Card wiring between each UPS (see Figure 36). Verify correct polarity for Pins 8 and 9: S Connect SHIELD Pin 10 on all cards together. S Connect CAN H Pin 9 and CAN L Pin 8 (twisted pair) on all cards together. S Connect COM Pin 4 and NC Pin 3 (twisted pair) on all cards together. 4.
INSTALLING OPTIONS SHIELD 1 2 10 CAN H 9 CAN L 8 TX 7 1 TX 6 2 NO 5 COM 4 NC 3 ALM RTN 2 ALARM 1 1 2 1 2 J3 J5 UPS #1 UPS #2 UPS #3 UPS #4 Figure 36. CAN Bridge Card Wiring 44 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
INSTALLING OPTIONS 5. On the bottom cover (and also the middle cover if 3-high), remove a knockout tab in the top edge of the cover for each cable: With wire cutters, cut either side of the tab and twist down to remove the tab (see Figure 37). Figure 37. Removing Knockout Tabs 6. Route the cable(s) to the approximate location of the cover access holes. Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
INSTALLING OPTIONS 7. Reinstall the front covers, starting with the bottom cabinet (see Figure 38). Hang the top edge of the cover on the cabinet first, then lower the bottom edge and snap into place. Verify that the cables fit in the access holes in the covers. Figure 38. Reinstalling the Front Covers 8. Continue to “Stabilizing the Cabinet” on page 47 to complete the parallel UPS installation.
Chapter 7 Stabilizing the Cabinet NOTE For seismic installations, you MUST order and install an Eaton 9355 UPS UPS seismic kit; do not use the following instructions. NOTE For non-seismic installations, you MUST install the stabilizing bracket on all 3-high cabinets. The stabilizing bracket is optional for 2-high cabinets. To stabilize the cabinet(s): 1. Lower the leveling feet to prevent the cabinet from rolling. Figure 39. Lowering the Leveling Feet 2.
STABILIZING THE CABINET M4 Screws Figure 40. Stabilizing Bracket with One Cabinet M4 Screws Figure 41. Stabilizing Bracket with Two Cabinets 48 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
STABILIZING THE CABINET M4 Screws Figure 42. Stabilizing Bracket with Three Cabinets Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
STABILIZING THE CABINET 50 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
Chapter 8 Extended Battery Module Installation NOTE A maximum of 22 battery strings can be installed in one configuration, including UPS batteries (4 EBM-64 models or 3 EBM-96 models). UPS-32 models contain 2 strings; UPS-64 models contain 4 strings; EBM-64 models contain 4 strings; and EBM-96 models contain 6 strings. NOTE For non-seismic installations, you MUST install the stabilizing bracket on all 3-high cabinets. The stabilizing bracket is optional for 2-high cabinets.
EXTENDED BATTERY MODULE INSTALLATION EBM Battery Circuit Breaker EBM Battery Connector Rear Ground Strap UPS Battery Connector UPS Battery Circuit Breaker EBM Cable Figure 43. Typical EBM Installation (2-High Cabinets Shown) 52 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
EXTENDED BATTERY MODULE INSTALLATION 8. Remove the top front covers of all cabinets. Press and release the handle latch at the bottom of the cover and then lift the cover up and off the cabinet. 9. Install the remaining ground straps between each cabinet (see Figure 44). 10. Reinstall the top front covers removed in Step 8. Hang the top edge of the cover on the cabinet first, then lower the bottom edge and snap into place. 11. Continue to “Operation” on page 55 to start up the UPS.
EXTENDED BATTERY MODULE INSTALLATION 54 Eaton 9355 Parallel UPS (10/15 kVA) User's Guide S 164201601 Rev B www.eaton.
Chapter 9 Operation This chapter contains information on how to use the Eaton 9355 UPS UPS, including front panel operation, UPS startup and shutdown, and configuring the UPS for Extended Battery Modules (EBMs). Control Panel Functions The UPS has a four-button graphical LCD with backlight. It provides useful information about the UPS itself, load status, events, measurements, and settings (see Figure 45).
OPERATION The following table shows the indicator status and description. Indicator Green Status Description On The UPS is operating normally. Flashing S The UPS is starting up or is shut down and waiting for power to return. S A new information message is active. S Bypass is not available. Off The UPS is turned off and will not turn on automatically. On The UPS is in Battery mode. On The UPS is in Bypass mode. On The UPS has an active alarm. Flashing There is a new UPS alarm condition.
OPERATION The following table shows the basic menu structure. Table 3.
OPERATION User Settings The following table displays the options that can be changed by the user. NOTE Changes to the output voltage or frequency options should be made before turning on the UPS; otherwise, the changes do not take effect. Table 4.
OPERATION Table 4. User Settings (continued) Description Available Settings Default Setting Start Screen Eaton logo Mimic screen Eaton logo User Password Enabled/Disabled If Enabled is selected, the password is USER. Disabled Audible Alarms Normal Sound/Disabled Normal Sound Battery Charging ABM cycling/constant ABM cycling Automatic Battery Tests Enabled/Disabled Enabled automatically runs the battery test once a month.
OPERATION Table 4.
OPERATION Configuring the UPS for EBMs NOTE Each UPS in a parallel system must have its own EBM and the same number of EBMs to ensure consistent runtimes. To ensure maximum battery runtime, configure the UPS for the correct number of EBMs: 1. Press any button on the front panel display to activate the menu options. 2. Using the 3. Press the 4. Using the button, scroll to the Number of Battery Strings option and press the button. 5.
OPERATION Parallel System Shutdown To remove power to the parallel UPS system output: 1. Press any button on the front panel display to activate the menu options. 2. Press the button on the front panel display and then press the button to select the TURN UPS ON/OFF menu. 3. Press the button to select the System Off option. 4. Confirm the selection. Press and hold the seconds, until the UPS stops beeping. button for three The UPS removes power to the parallel UPS system output.
OPERATION Individual UPS Shutdown To shut down a single UPS in the parallel system: 1. Press any button on the front panel display to activate the menu options. 2. Press the button on the front panel display and then press the button to select the TURN UPS ON/OFF menu. 3. Press the button to select the UPS Off option. 4. Confirm the selection. Press and hold the seconds, until the UPS stops beeping. 5. Switch the UPS battery circuit breaker to the OFF position.
OPERATION Restarting the Parallel System To restart the parallel system: 1. Verify that the maintenance isolation breaker (if present) on the Tie Cabinet is in the OFF position or all of the UPS breakers are in the OFF position. 2. Switch on utility power where the UPSs are connected. 3. Wait for the front panel LCD to illuminate. The 4. indicator flashes on each UPS. Switch all battery circuit breakers to the ON position. The indicator stops flashing on each UPS. 5.
Chapter 10 Parallel Bypass To switch the parallel UPS to maintenance bypass from Normal mode: 1. From any UPS, set the system to internal Bypass mode: S Using the button on the front panel display, scroll to the Control menu option and press the S Press the button. button to select the Go to Bypass Mode option. The indicator illuminates and the indicator extinguishes, indicating the UPS system is operating in Bypass mode. 2.
PARALLEL BYPASS 4. If present, switch the maintenance isolation breaker (MIS) on the wall-mounted bypass cabinet to the ON position; otherwise, switch the UPS breakers (may be designated MOB or UPS) on the wall-mounted bypass cabinet to the ON position. 5. Switch the bypass breaker (may be designated MBP or CBP) in the wall-mounted bypass cabinet to the OFF position. The UPS is now powering the load in Bypass mode.
Chapter 11 Troubleshooting The Eaton 9355 UPS is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are preventive alarms intended to alert the user. Use the following troubleshooting chart to determine the UPS alarm condition.
TROUBLESHOOTING Alarm or Condition Possible Cause Action Overtemperature UPS internal temperature is too high or the fan has failed. Turn the maintenance bypass switch to the SERVICE position. Otherwise, shut down the UPS. Clear vents and remove any heat sources. Allow the UPS to cool. Ensure the airflow around the UPS is not restricted. If the alarm disappears, turn the maintenance bypass switch back to the UPS position. If the condition persists, contact your service representative.
TROUBLESHOOTING Alarm or Condition Possible Cause Action Check Parallel Board The UPS is not recognizing another parallel unit. From the UPS Status menu, select the Units on CAN Bus option and verify that all UPSs appear in the list. If any UPS is missing, verify the Powerware Hot Sync® CAN Bridge Card connections and recheck the status from the UPS front panel. If all UPSs appear in the list, check the pull-chain wiring (see page 43). Set the system to internal Bypass mode (see page 65).
TROUBLESHOOTING Service and Support If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative.
Chapter 12 Warranty Limited Factory Warranty Three‐Phase Eaton® 9355 UPS Products WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Corporation, an Ohio Corporation (“Eaton”). LIMITED WARRANTY: This limited warranty (this “Warranty”) applies only to the original end-user (the “End-User”) of the Eaton 9355 UPS Products (the “Product”) and cannot be transferred. This Warranty applies even in the event that the Product is initially sold by Eaton for resale to an End-User.
WARRANTY This Warranty is not valid: if the Product's serial numbers have been removed or are illegible. Any Warranted Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty subject to all the terms thereof. Labor warranty is not provided for Product located outside of the fifty (50) United States or the District of Columbia.
*164201601B* 164201601 B