User`s guide

Configuring the Card
Eaton Power Xpert Gateway PXGX UPS Card User’s Guide 164202123—Rev 1 33
7. To modify the options for a recipient, select the e-mail address from the Recipients list and select options
for the recipient. See Table 1 for a description of options.
8. Click Apply and then OK to save the settings.
Note: Apply changes before modifying or creating another e-mail recipient.
Collective E-Mail
Use the collective e-mail feature to limit redundant e-mail messages during input power-related events
affecting the UPS. When an input power-related event is detected by one or more gateways, event data is
shared in real time between gateways and consolidated.
Input power related events are:
l
Input AC Over Voltage
l
Input Under Or Over Frequency
l
Utility Not Present
l
Input AC Under Voltage
l
UPS On Battery
l
Utility Out Of Limits
After a delay of about 30 seconds with no event activity, a single e-mail is sent, detailing the list of input
power-related events present and the list of UPSs affected.
Collective e-mail can be configured to send notification from one PXGX UPS Card to some or all recipients, or
from several PXGX UPS Cards to some or all recipients, in any combination. Recipients can be set up into logical
groups and e-mail addresses are displayed so duplication can be avoided.
To configure collective e-mail event messages:
1. Expand the Email folder on the Configuration menu and select Email. The Email configuration page
displays. Verify that the IP address of the SMTP server has been configured and, if applicable, that SMTP
has been configured. See “General E-Mail” on page 32“.
2. Select Collective Email from the Email menu. The Collective Email page displays.
3. Select the Participate in collective notification check box. When this option is selected, your gateway is
visible to peer gateways so that redundant e-mail messages can be combined.
Table 1. E-Mail Options for Receiving Event Notification
Option Description
Send on event active Sends an e-mail message when an event occurs
Send on event clear Sends an e-mail message when an event clears
Attach event log file to event emails Attaches the event log to the event e-mail message (the log is always attached to
status e-mail messages)
Attach data log file to event emails Attaches the data log to the event e-mail message (the log is always attached to status
e-mail messages)
Attach interval log file to event emails Attaches the interval log to the event e-mail message
Attach ID file to event emails Attaches the identification files to the event e-mail message
Send periodic status emails Sends periodic status e-mail messages
Days between periodic status emails Sets the number of days between the periodic status e-mail messages
Time of day (gateway time) for periodic status email
(HH:MM)
Sets the time of day for periodic status e-mail messages to be send (in 24-hour format,
PXGX UPS Card UTC time)