System information
CA08104001E For more information visit: www.eaton.com
2.6-3
February 2009
Power Management Systems & Products
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Sheet 02
for Third-Party Integration
Ethernet/Modbus NetLink
051
Modbus NetLink
Modbus NetLink
General Description
Communications
■ Ethernet-Based (TCP/IP via
10Base-T).
■ INCOM.
■ E-PONI.
■ Modbus RTU slave communications
through RS-232 port.
Physical Characteristics
■ Suitable for panel mounting.
■ Powered via 120/240 Vac.
■ 10Base-T connection.
Dimensions
■ Height: 7.8 inches (198 mm).
■ Width: 4.5 inches (114 mm).
■ Depth: 9.6 inches (244 mm).
■ Weight: 6 lbs. (2.7 kg.).
Application Description
Applications
■ Bridge multiple Cutler-Hammer
Power Management Software
devices to an Ethernet network.
■ Modbus RTU output for multiple
Cutler-Hammer Power Management
Software devices.
■ Historical data logging.
■ Event storage.
Metered/Monitored Parameters
Provides remote access over Ethernet
or Modbus to the protective and moni-
toring parameters of any supported
communicating Cutler-Hammer meter,
protective relay, breaker or motor
starter.
Features, Benefits and Functions
General Description
The NetLink translates INCOM Fre-
quency Shift Key (FSK) to standard
Ethernet TCP/IP messages or Modbus
RTU or to both.
The Modbus NetLink (NetLink M) con-
verts data from as many as 200 meters
and protective relays into Modbus
RTU registers. Configuration can be
done remotely and is stored in non-
volatile RAM. The Modbus NetLink
uses a register mapping technique to
map up to 10,000 read registers for
real-time data and read/write registers
for control commands for 200 devices.
Note: All 200 devices cannot be high-end
devices such as an IQ Analyzer or Protective
Relay. Call factory for details.
The Modbus NetLink is a server for
Cutler-Hammer device information to
Modbus master equipment via Mod-
bus RTU registers over an RS-232
communication medium. The Modbus
NetLink enables the following func-
tionality:
■ Connection of up to 200 Cutler-
Hammer meters and protective
relays into Modbus RTU registers.
■ A register mapping technique to
map up to 10,000 read registers
for real-time data and read/write reg-
isters for control commands.
■ A 10Base-T port for direct configura-
tion which is stored in non-volatile
memory.
■ Available for purchase with either
one or two INCOM ports.
Dual Ethernet/Modbus NetLink
The Dual Ethernet/Modbus NetLink
combines the functionality of the
Ethernet and Modbus NetLinks into
one package. This enables remote
monitoring of all connected equip-
ment via the Power Management
Software suite, as well as local com-
munications to a Modbus master
sharing the available information
for two completely separate and
independent functions.
Mounting Information
The most common location for the
NetLink is in a wall-mounted enclosure
near a patch panel, a network hub, or a
wall-mounted network port. Modbus
NetLinks should be mounted in close
proximity to the Modbus Master. The
distance between the Modbus Master
and the RS-232 output should not
exceed 50 feet (15 m) without the use
of external line drivers between serial
ports. The NetLink may be equipped
with up to two INCOM device network
ports. There will be an additional RJ11
jack and terminal for each INCOM
device network. Each additional port
will increase network performance in a
linear fashion. A 2-port NetLink will
deliver the same amount of data from
a fixed number of devices in half the
time of a 1-port NetLink. NetLinks will
communicate with 200 devices regard-
less of the number of ports.
Catalog Information
Table 2.6-1. Building the NetLink Catalog
Numbering System
CSA is a registered trademark of the Canadian Stan-
dards Association. Explorer is a registered trademark
of Microsoft Corporation. Modbus is a registered trade-
mark of Modicon, a division of Schneider Electric
Industries SA. NEMA is the registered trademark and
service mark of the National Electrical Manufacturers
Association. UL and cUL are registered trademarks of
Underwriters Laboratories Inc. Windows and Microsoft
are registered trademarks of Microsoft Corporation.
Cutler-Hammer is a federally registered trademark of
Eaton Corporation.
N L
Number of Ports
1 = 1 INCOM Port
Communica-
tions Network
(standard)
2 = 2 INCOM Ports
Output
E = Ethernet
Output
M = Modbus
Output
D = Dual Com-
munications
Ethernet and
Modbus
($1000 Adder)
Port Type
T = 10Base-T
Ethernet
Port/AUl