System information
2.2-14
For more information visit: www.eaton.com CA08104001E
February 2009
Power Management Systems & Products
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Sheet 02
Network Connectivity
Ethernet-Enabled MCC
022
Ethernet-Enabled MCC
Electronic Motor Starters and Variable
Frequency Drives
General Description
IT Cover Controls, Advantage Starters
and Eaton Variable Frequency Drives
may be connected to a single Power
Xpert Gateway 400 (not to exceed
64 total) or Power Xpert Gateway
600 (not to exceed 96 total) deployed
in various low-voltage motor control
center applications and made accessi-
ble to an Ethernet network.
Equipment
■ IT Starter
■ IT Starter with QSNAP
■ S811 (MV811) Soft Starter
■ SVX9000/MVX9000 Variable
Frequency Drives
■ Advantage Starter
■ Advantage ACM Starter
Options
■ PXG400 — Up to 64 IQ meters may be
connected for Web Browser access
and INCOM translation for Power
Xpert Software.
■ PXG600 — Up to 96 IQ meters may be
connected for Web Browser access,
data logging, alarm notification,
control commands and INCOM trans-
lation for Power Xpert Software.
Note: Both PXG400/600 support a maxi-
mum of 64 INCOM devices while not to
exceed the total PXG device limit.
PXG400 – 64 total
PXG600 – 96 total
Communication Interfaces
■ Modbus RTU (RS-485) or
INCOM (FSK)
■ Modbus TCP/IP (with PXG400/600)
■ HTTP (with PXG400/600)
■ XML/SOAP (with PXG400/600)
■ SMTP (with PXG600)
■ SNMP (with PXG600)
Metering/Monitoring Applications
■ Real-time viewing of power/energy
readings (PXG400/600)
■ View trended power/energy
readings (PXG600)
■ User-defined events (PXG600)
■ E-mail notification (PXG600)
Installation Applications
■ Low Voltage Switchgear
■ Medium Voltage Switchgear
■ Low Voltage Motor Control Centers
■ Medium Voltage Motor Starters
Communications Applications
■ Building Management System
(BMS)
■ Energy Management Systems
■ Network Management Systems
(NMS)
■ HMI
■ Power Xpert Server Core Software
■ Power Xpert Foreseer Class Software
Figure 2.2-8.
Ethernet-Enabled MCC Trip Unit and Relay Application
24 Vdc
Power Supply Required
IT. MCC
IT. Starter
Network
with QSNAP
Cover
Controls
S811 Soft
Starter
Advantage
Starter
CMU
Advantage
Starter
Advantage MCC Advantage MCC
IT. MCC
IT Starter
Network
with QSNAP
Cover
Controls
S811 Soft
Starter
SVX9000
Drive
SVX9000
Drive
eoltr
Advantage
Starter
CMU
Advantage
Starter
Ethernet Network
QCPort Network
INCOM Network
RS-485 Network
eolr = End of line resistor
eoltr = End of line termination resistor
eolr
eolr