System information
CA08104001E For more information visit: www.eaton.com
2.2-13
February 2009
Power Management Systems & Products
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Sheet 02
Network Connectivity
Trip Units and Protective Relays
021
Ethernet-Enabled Circuit
Breaker Trip Units and
Protective Relays
Electronic Trip Units
General Description
Up to a combination of 64 INCOM trip
units and protective relays may be
connected to a single PXG400/600 and
deployed in various power distribution
and motor control applications and
made accessible to an Ethernet
network using the PXG600.
Equipment
■ Digitrip 3000/3200
■ FP-4000/5000
■ MP-3000/4000
■ Digitrip 520MC
■ IQ 500
■ MPCV Relay
■ Digitrip 1150/DT1150V
■ Digitrip 810/910
■ Digitrip MV
■ Digitrip OPTIM 1050/750/550
■ BIM II (Breaker Interface Module)
Options
■ PXG400 — Up to 64 IQ meters may
be connected for Web Browser
access and INCOM translation for
Power Xpert Software.
■ PXG600 — Up to 96 IQ meters may
be connected for Web Browser
access, data logging, alarm notifica-
tion, control commands, and INCOM
translation for Power Xpert Software.
Note: Both PXG400/600 support a maximum
of 64 INCOM devices while not to exceed
the total PXG device limit.
PXG400 — 64 Total
PXG600 — 96 Total
Communication Interfaces
■ Modbus RTU (RS-485) or INCOM
downstream
■ Modbus TCP/IP (with PXG400/600)
■ HTTP (with PXG400/600) (with ECC)
■ SMTP (with PXG600)
■ SNMP (with PXG600)
■ XML/SOAP (with PXG400/600)
Metering/Monitoring Applications
■ Real-time viewing of power/energy
readings (PXG400/600)
■ View trended power/energy
readings (PXG600)
■ User-defined events (PXG600)
■ E-mail notification (PXG600)
Installation Applications
■ Low Voltage Switchgear
■ Medium Voltage Switchgear
■ Low Voltage Motor Control Centers
■ Medium Voltage Motor Starters
Communications Applications
■ Building Management System
(BMS)
■ HMI
■ Energy Management Systems
■ Network Management Systems
(NMS)
■ Power Xpert Server Core Software
■ Power Xpert Foreseer Class
Software
Viewing an Eaton FP-5000 Protective Relay
through the Power Xpert Gateway
Figure 2.2-7. Power Xpert Gateway PXG400/600 Trip Unit and Relay Application
Note: When using Modbus RTU over an RS-485 communications network, the data rate, data
protocol (data bit, stop bit and parity) and wiring topology (two-wire or four-wire) must be the
same for each of the devices.
eolr
24 Vdc
Power Supply Required
3
rd
Party
Motor Relay
3
rd
Party
Motor Relay
3
rd
Party
Portective
Relay
eoltr
3
rd
Party
Motor Relay
3
rd
Party
Motor Relay
3
rd
Party
Motor Relay
3
rd
Party
Motor Relay
eolr eolr
eoltr
3
rd
Party
Portective
Relay
3
rd
Party
Portective
Relay
FP4000
FP5000
DT3000
BIM II
1150/DT1150
Optim 1050
FP4000
FP5000
DT3000
BIM II
1150/DT1150
OPTIM 1050
Ethernet Network
QCPort Network
INCOM Network
RS-485 Network
eolr = End of line resistor
eoltr = End of line termination resistor