Metering Devices, Protective Relays, Software and Connectivity
Metering Devices
Technical Data and Specifications
IQ Analyzer 6400/6600 Series
Fuses
Self-powered units
with IQMSSPM have
3/4 ampere, 600 volts
Bus Type KTK-R-3/4 fuses
(three required).
Separate source dual-
voltage units with
IQMSSPM have a single
5 x 20 mm 1/4 ampere fuse
Separate source DC units
with IQMDCPM do not
have user replaceable
fuses
Environmental Conditions
Operating temperature:
–20°–70°C
Storage temperature:
–30°–85°C
Operating humidity:
5–95% relative humidity
Current Inputs
(Each Channel)
Conversion: true rms, 32
sample/cycle (all samples
used in all rms calculations)
CT input: 5 ampere
secondary (any integer
5:5 to10,000:5)
Burden: 0.05 VA
Overload withstand:
40 amperes AC continuous,
300 amperes AC 1 second
Range: 8 x CT continuous
Accuracy: 0.1% of CT
primary rating, 0.2% of
reading above 150% of
rating, sinusoidal (see
accuracy below for non-
sinusoidal specifications)
Input impedance:
0.002 ohm
Voltage Inputs
(Each Channel)
Conversion: True rms, 32
sample/cycle (all samples
used in all rms calculations)
PT input: direct or any
integer 120:120–
500,000:120
Range: 30–660 Vac
(separate source and
DC source)
Nominal full scale:
100–600 Vac
Burden: 21 VA (self-
powered only)
Overload withstand:
635 Vac, continuous
700 Vac, 1 second
Input impedance:
1 megohm
Frequency Range
20–66 Hz fundamental
(up to 50th harmonic)
Harmonic Response
(Voltages, Currents)
50th harmonic
Accuracy (in Percent
Full Scale)
Accuracy from 3–300% of Full
Scale and
from –0.5. to 1.00
to 0.5 power factor
Current and voltage:
±0.20%
Power, energy and
demand: 0.40%
Frequency: 0.04%
Power factor: 0.80%
THD: 1.00%
Specific Current Accuracies
±0.20% of full scale to
200% of full scale and
150% crest factor
±0.20% of full scale to
150% of full scale and
200% crest factor
±0.20% of full scale to
100% of full scale and
300% crest factor
±0.40% of reading for
currents to 800% of full
scale
Power and energy: Start
recording with an average
of 3 mA secondary current
Discrete Inputs
(Dry Contact)
+30 Vdc differential across
each discrete input pair of
terminals. Minimum pulse
width: 1.6 msec
Optically isolated inputs
to protect IQ Analyzer
circuitry
Analog Outputs (4)
0–20 mA/4–20 mA into
maximum 750 ohm load.
Accuracy: 1%
Analog Input (1)
0–20 mA/4–20 mA into
200 ohm load.
Accuracy: 1%
Relay Output Contacts (4)
Form C Dry Contact:
10 amperes at 120/240 Vac
(Resistive) 10A at 30 Vdc
(Resistive) 30A make
(50 mS) at 240 Vac/240 Vdc
Minimum pulse width:
4 cycles (68 mS)
Withstand rating: 1000 Vac,
1 minute across contacts
5000 Vac (contacts to coil,
1 minute) 10,000 Vac
(contacts to coil, surge
voltage)
Relay Response Time
(Excluding programmed
time delays):
Two line cycles for Discrete
Input, Eatons software
commands
(communications port)
Four to five line cycles for
Voltage Disturbance,
Voltage Unbalance
Nine to 10 line cycles for
all others
IQ Analyzer Auxiliary
Power Supply
Input voltage: 100–250 Vac
Input frequency: 50/60 Hz
Output voltage/current:
+24 Vdc at 0–0.45A
Output ripple: 100 mV
maximum (peak to peak)
Rated output power:
10.8 watts
Turn on/turn off overshoot
5% maximum
Turn on delay: 0.5 second
maximum
Operating temperature:
0°–40°C
Storage temperature:
–40°–80°C
Control Power Input
Note
1
When directly wired to 480 Vac, IQ Analyzer can ride through a continuous sag that is 20% of rated voltage.
Description Separate Source Self Powered
1
DC Source
Input range, AC
Frequency range
110
240 Vac ±10%
45
66 Hz
110
600 Vac ±10%
45
66 Hz
N/A
N/A
Input range, DC
Burden
110
250 Vdc ±10%
21 VA
N/A
21 VA
2448 Vdc ±20%
21 VA