User`s guide

V3-T9-82 Volume 3—Power Distribution and Control Assemblies CA08100004E—November 2013 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.3
Metering Devices, Protective Relays, Software and Connectivity
Metering Devices
If zero time delay is
programmed, any disturbance
lasting two cycles (less if
magnitude is sufficient to
effect rms readings) will
trigger a voltage disturbance
event/alarm.
Sub-cycle transient
capture/excess dv/dt on
V
A-N
, V
B-N
, V
C-N
Note: 6600 series only.
Sub-cycle voltage
interruption on V
A-N
,
V
B-N
, V
C-N
Note: 6600 series only.
Maximum Threshold Exceeded
Currents —þphases A, B,
C, Neutral and Ground
Voltage—Neutral to
Ground
System Power—Watts,
VA, VARs
System Power Factor—
Displacement and
Apparent
Demand
Currents—Phase A, B, C
and AVG
System Power—Watts,
VARs, VA
Frequency
Percent Total Harmonic
Distortion or Magnitude
Total Harmonic Distortion:
Currents—Phases A, B,
C, Neutral
VoltageV
A-N
, V
B-N
,
V
C-N
, V
A-B
, V
B-C
, V
C-A
Minimum Threshold Exceeded
Currents—Phases A, B, C
System Power—Watts,
Vars, VA
System Power Factor—
Displacement and
Apparent
Frequency
Voltage Phase Unbalance
V o l t a g e L- L , L- N
Current Phase Unbalance
Current—Phases A, B, C
Discrete Input Energized
Input 1, 2, 3
Remote command through
communications port or
front panel
All trigger conditions have
programmable time delays
from 0.1–60 seconds in
0.1 second increments
(except Voltage Disturbances
—programmable from
2–3600 cycles in two-cycle
increments, and Eaton’s
Power Management
Software commands—no
programmable delay).
Demand Recording
Peak Demands are date and
time stamped for:
Current Phases A, B, C
and Average
System Power:
Real (watts)
Reactive (VARs)
Apparent (VA)
Input/Output
Extensive input/output
capability is standard on the
IQ Analyzer. In addition to
monitoring three-phase
currents and voltages,
separate inputs
are provided
for both ground and neutral
currents. Voltage of neutral-
to-ground is also monitored to
indicate the presence of
harmonics and potential
downstream grounding
problems. Analog and digital
I/O provide interfaces for
transducers, relays, PLCs
and control systems.
Current Inputs
Five ampere secondary CT
connections for:
Phases A, B, C
Ground
Neutral
Separate ground and
neutral CT inputs
CT range 5:5–10,000: 5
(any integer)
Voltage Inputs
Phases A, B, C (from
120 Vac–500 kV AC)
120/240 Vac control power
input standard—not
required with optional line
power module
Separate ground-to-neutral
voltage reference
PT range 120:120–
500,000:120 (any integer)
External 120-volt secondary
PTs are required above
600 Vac, optional from
120–600 Vac.
Discrete Contact Inputs
Three dry contact discrete
inputs may be programmed
by the user to:
Trigger Event Analysis—
the information described
in “Event Analysis
Screens,” including
Harmonic Analysis
information, can be
recorded when external
devices trip or change state
by wiring their auxiliary
contacts into these inputs
Act as a synch.-pulse
input to synchronize
power demand windows
with utility provided
synch. pulse
Actuate a relay output
Reset relay output, peak
demands, Trend Analysis
records and Event
Analysis records
With communications
option, provide remote
status indication on Eatons
communication network
Status of input contacts is
displayed in the Meter
Menu Custom screen
Relay Output Contacts
Four Form-C (NO/NC)
relay contacts may
be independently
programmed to:
Act as a kWh, kVARh or
kVAh pulse initiator output
Actuate on one or more
event conditions—including
discrete input software
commands (through
communications port)
Reverse sequence alarm
Each relay may be set for
Auto or Manual Reset with
0–30 minute release delay
(one second increments).
Relays are Form-C NO/NC.
Relay(s) programmed to
actuate on undervoltage
also have a programmable
0–30 minute delay on power-
up for transfer applications.
Analog Input and Outputs
One analog input and four
analog outputs may be
configured as 0–20 or
4–20 mA. The analog input is
displayed at the device as a
percentage and is accessible
through the communications
port. The analog input
provides an interface with gas
flow meters, temperature
transducers or other analog
devices.
The analog outputs may be
programmed
to reflect any of
the following:
Current—Phases A, B, C,
Average, N, G
Voltage—L-L, L-N, N-G
Power:
Real (watts)
Reactive (VARs)
Apparent (VA)
Phases A, B, C and
System
% THD:
Current (Phases A, B, C, N)
Voltage (L-L, L-N)
Frequency–System
Power Factor:
System Displacement PF
System Apparent PF
Standards and Certifications
UL listed, File E62791,
NKCR File E185559
(CE versions)
cUL listed #1010.1 C22.2
CE mark EN61010-1 (1993)
EN50082-2 (1994)
Measurement Canada
Electricity Meter AE-0782
CSA approved