User`s guide

V3-T9-4 Volume 3—Power Distribution and Control Assemblies CA08100004E—November 2013 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Metering Devices, Protective Relays, Software and Connectivity
Power Xpert Architecture
Power Xpert Architecture—Notes
a. Simple Mail Transfer
Protocol (SMTP)—
Device events and
periodic data log file
attachments are sent
to users in the form of
an e-mail from the
following Power Xpert
products: Power
Xpert Software,
Power Xpert Meters
2000/4000/6000/
8000, Power Xpert
Gateway 600 and
Power Xpert Gateway
Cards 1000/2000
Series.
b. Hyper Text Transfer
Protocol (HTTP)—
Web browser access
is available on the
following Power Xpert
products: Power
Xpert Software,
Power Xpert Meters
2000/4000/6000/
8000, Power Xpert
Gateway 600 and
Power Xpert Gateway
Cards 1000/2000
Series.
c. Network Time Server
(NTP)—Network Time
Protocol (Client-side)
is available on the
following Power Xpert
products: Power
Xpert Software,
Power Xpert Meters
2000/4000/6000/
8000, Power Xpert
Gateway 600 and
Power Xpert Gateway
Cards 1000/2000
Series.
d. Modbus TCP/IP—
Modbus TCP/IP over
Ethernet is available
on the following
Power Xpert
products: Power
Xpert Software,
Power Xpert Server
Core Software, Power
Xpert Meters 2000/
4000/6000/8000,
Power Xpert Gateway
600 and Power Xpert
Gateway Cards 1000/
2000 Series. Modbus
register maps are
available online at
www.eaton.com/
powerxpert.
e. Data Export—Data
files consist of
metered data and
event log information
that is exported from
the meter, gateway or
software in the form
of a .csv (comma
separated variable)
file. Supported
products are: Power
Xpert Gateway
PXG600, PXGX1000,
PXGX2000, Power
Xpert Meters 2000/
4000/6000/8000
and Power Xpert
Software.
f. Data Trending—
Viewing trended data
in a standard Web
browser interface in
the form of a graphed
line for one or more
data points is available
for the following
products: Power
Xpert Gateway
PXG600, PXGX1000,
PXGX2000, Power
Xpert Meters 2000/
4000/6000/8000
and Power Xpert
Software.
g. Waveform Capture—
The ability to capture
a waveform and/or
export the waveform
as a standard
comtrade file format
is available on the
following products:
Power Xpert Meters
4000/6000/8000.
h. Waveform Acquisition
and Export—The
ability to acquire a
waveform from
another device that
natively captures a
waveform internally
and then e
x
port that
waveform in a
standard comtrade
file format is
supported by the
following devices:
PXG600 (provides
data acquisition and
comtrade conversion
for: IQ Analyzer,
DT1150 and FP5000).
Note: The Power Xpert Meters
4000/6000/8000 also export
natively captured waveforms as
comtrade file format.
i. Third-Party HMI
Software Integration—
Is achieved through
the Modbus TCP/IP
interface on all Power
Xpert devices. If
PowerNet software is
utilized in the system,
then an OPC Server
is available.
j. Proprietary Serial
Device Protocols over
Ethernet—The ability
to communicate with
third-party equipment
is achieved through a
Power Xpert Gateway
via Modbus 485 or
Modbus Serial.
k. BACnet/WS+ —
Is based upon the
protocol specification
developed by the
ASHRAE standards
group as an
Addendum c to
Standard 135-2004.
Reference: [BACnet—
A Data
Communication
Protocol for Building
Automation and
Control Networks.
Public Review Draft,
ASHRAE Standard.
BSR/ASHRAE
Addendum c to ANSI/
ASHRAE Standard
135-2004. First Public
Review. Released:
October 22, 2004.
32 pages. Copyright
(c) American
Society of Heating,
Refrigerating and
Air-Conditioning
Engineers, Inc.
August 30, 2004.]
This draft shows proposed
changes to the current
BACnet standard.
Note: Eaton has extended this
protocol addendum with a (+) to
signify the addition of an “event-
driven” behavior to the existing
“polled” data acquisition model.
This allows optimization in
communications between Power
Xpert devices and Power Xpert
Software.