Power Xpert 4000/6000/8000 Graphic Display (Option) Features
A menu-driven graphical
display with information
organized into a user-friendly
information architecture.
The homepage (see below)
offers:
Graphical level indicator
based on a statistical
analysis for three-phase
line-to-line and line-to-
neutral voltage and per
phase currents to quickly
indicate out of normal
readings
Large easy-to-read average
L-L voltage average phase
currents and system
frequency can be
highlighted and selected
using the navigation
control dial to drill down
for additional detail
Menu selections for meter,
power, quality, events and
setup are shown for ease
of navigation into display
for more detail, or basic
device setup
Homepage
Highlighting a field such as
the avg. current value and
pressing the navigation control
dial brings up a detail screen
like the one below.
Current Summary
Highlighting an individual
reading on the detail
summary level screen and
selecting it drills down to a
level including links to min./
max., historical trend plots,
triggers, harmonic spectral
data and waveform viewing.
Selecting the trend plot for
a given parameter displays
a historical graph of the
selected parameter over
the last 16 hours. The zoom
buttons change the time
scale to one of several data
views based on historical
averages with min./max. The
Pan button allows scrolling
within the selected view.
Trend Plot
Waveforms can be displayed
for currents and voltages.
The waveforms can be
viewed on demand for
steady-state conditions.
Triggered waveforms can
also be displayed to view
sag/swell or transient data.
Waveform Viewer
Harmonic Spectrum
The harmonic spectral plot
displays both harmonics and
interharmonics up to the
85th order. A detailed table
also includes individual
magnitudes and angles
of current and voltage
harmonics, as well as a
harmonic power calculation
at each frequency.
Ethernet Settings
Ethernet and other settings
can be input or verified via
the Power Xpert Meter
LCD display.
Note: Some of the other settings
are specific only to the Web
Browser GUI.
ITIC Plot (Power Xpert 6000/8000)
The Power Xpert Meter
classifies disturbances and
summarizes the results
graphically using the ITIC plot.
The number of ITIC sags and
swells are indicated for each
of nine severity levels.
A pass/fail summary is
shown to indicate how many
events are outside the ITIC
pass zone.