9.3
Metering Devices, Protective Relays, Software and Connectivity
Metering Devices
Power Xpert Meter 4000/6000/8000, continued
Notes
These specifications are subject to change without notice and represent the maximum capabilities of the product with all options installed. This is not a complete feature list. Features and functionality
may vary depending on selected options, firmware version and product model. Please refer to the technical data sheet and User Manual for detailed specifications.
Power Xpert Meter
Feature 4000 6000 8000 Benefit
Highlights, continued
Event severity counters
■■
An ITIC (CBEMA) event counter keeps track of the number of all sags, swells and
transients
ITIC (Information Technology Industry Council), previously CBEMA
performance curve
■■
ITIC (Information Technology Industry Council), previously CBEMA performance curve for
easy power problem evaluation
Custom ITIC (CBEMA) plot with individual event magnitude and duration
■■
Review custom ITIC (CBEMA) plots of individual events showing you the actual
magnitude, duration and hit are in a simple graphical representation
Event calendar view
■ ■ The Events Timeline calendar view provides instant insight to the frequency of power
events and helps detect reoccurring problems
Events timeline view
■ ■ View and understand the sequence of events that have occurred during a period of time
Sequence of events and events plot on waveform
■ ■ Plot color-coded events on a captured waveform to gain insight into the sequence of
events cycle per cycle
Power quality index—premium (at-a-glance “thermometer” view of
power quality)
■ Complex power quality data put into simple graphic format (includes ITIC events and
flicker calculations)
High-Speed Transient Capture and Detection
6 MHz capture of impulsive transients
■
Capture impulsive transients by taking 6 samples every millionth of a second
Transient Capture Duration: ~20 ms/6 MHz ~120 ms/1 MHz
■
Record and analyze transients during a longer timeframe
Waveform recorded at 100,000 samples per cycle
■
High-speed ensures impulsive transients are correctly captured (fast rise time)
Three-phase voltage and neutral-to-ground fast transient capture
■
Capture impulsive transients on all 4 channels