User`s guide

Volume 3—Power Distribution and Control Assemblies CA08100004E—November 2013 www.eaton.com V3-T9-299
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.5
Metering Devices, Protective Relays, Software and Connectivity
Connectivity Options
IMPCABLE
Conductors
Tinned
Copper
Braid
PVC
Outer Jacket
Polyethylene Filler
Drain Wire
Aluminum
Shield
Polyethylene Insulator
Contents
Description Page
Power Xpert Gateways . . . . . . . . . . . . . . . . . . . . . . V3-T9-259
Power Xpert Ethernet Switches . . . . . . . . . . . . . . . V3-T9-272
Power Xpert Gateway
Series 1000 Card—Power Distribution Unit . . . . . . V3-T9-276
Power Xpert Gateway
Series 2000 Card—Uninterruptible Power Supplies V3-T9-279
mMINT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V3-T9-282
MINTII RS-232 Converter. . . . . . . . . . . . . . . . . . . . V3-T9-284
IPONI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V3-T9-285
DPONI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V3-T9-286
MPONI
I/O Devices Digital Input Module (DIM) . . . . . . . . . V3-T9-288
Addressable Relay II. . . . . . . . . . . . . . . . . . . . . . . . V3-T9-290
Breaker Interface Module II (BIM II) . . . . . . . . . . . V3-T9-293
Sub-Network Master Local Display (SMLD) . . . . . . V3-T9-297
IMPCABLE
IMPCABLE
Product Description
The IMPCABLE is an 18 AWG
cable with a 100 ohm
impedance at 100 kHz tuned
to work optimally with the
FSK signal from Eaton’s
devices. The cable has been
designed with characteristics
that allow up to 1000 devices
or distances up to 10,000 feet
(3048m) from the master.
Please refer to Eaton’s wiring
specification for instructions
on cable runs and calculating
maximum distances and
devices on a given network.
Application Description
Eaton’s IMPCABLE was
designed to be run in
switchgear where codes
require a 600 volt insulation
rating. Typical “blue hose”
cables are rated at 300 volts.
Features
Physical Characteristics
Twisted shielded pair with
drain wire
600 volt at 80°C
18 AWG, 20 AWG drain
UL AWM 20253
Standards and Certifications
UL AWM 20253
NECT CM
CSA
PCC-FT1
P-MSHA
Product Selection
IMPCABLE
Technical Data and
Specifications
INCOM signal: attenuation
1.6 db/1000 feet (305m)
Long communication runs
600 volt required ratings
Description
Catalog
Number
IMPCABLE IMPCABLE