User`s guide

V3-T9-298 Volume 3—Power Distribution and Control Assemblies CA08100004E—November 2013 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.5
Metering Devices, Protective Relays, Software and Connectivity
Connectivity Options
Product Selection
Ordering Information
Technical Data and Specifications
Frequency Range
50/60 Hz
Power
Power consumption:
200 mA (maximum) at
24 Vac, 24 Vdc
Power connector rating:
24 Vac or 24 Vdc at
1 ampere
Power source: 120 Vac or
24 Vdc, UL Class 2 or CSA
Class III SELV transformer
in accordance with C22.2
No. 1010-1. The volt age
range is 18 to 24 Vac or
Vdc, 200 mA (maximum)
Ratings
Operating temperature:
0°C to 60°C
Storage temperature:
–20°C to 70°C
Operating humidity: 5 to
90% maximum non-
condensing
Altitude: 10,000 feet
(3048m)
Environment: indoor
use only
Mounting Information
4.37 H x 4.37 W x 1.50 D
inches (111.0 H x 111.0 W x
38.1 D mm)
Door mount or panel
mount
Communications
INCOM Frequency Shift
Key (FSK) network
compatible 9600 baud
Non-intrusive arbitration
algorithm
Passive monitoring
automatically enabled by
arbitration algorithm while
host PC is communicating
Master on INCOM network
upon data request from
front panel if host PC is not
communicating
Addresses for sub-network
devices
can be 001–044 hex
(1–255 decimals)
Typical Use Diagram of SMLD
Dimensions
Approximate Dimensions in Inches (mm)
Meter Base Unit
Note
DIN (92 mm x 92 mm) access cutout.
Description
Catalog
Number
Local Display (120 Vac) LDISP120
Local Display (24 Vac or Vdc) LDISP24
Sub-Network Master
Local Display
Digitrip
OPTIM 1050C
IQ
ES or
PS
IQ 200
Computer
with Power
Management
Software
SMLD
Multiple Units as Required
Width Height Depth
4.37 (111.0) 4.37 (111.0) 1.50 (38.1)