User`s guide

V3-T9-26 Volume 3—Power Distribution and Control Assemblies CA08100004E—November 2013 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.3
Metering Devices, Protective Relays, Software and Connectivity
Metering Devices
Metering Selection Chart, continued
Notes
1
From 3–300% of FS.
2
At unity power factory and 5–300% of FS.
3
At a power factor <±0.5 and 5–300% of FS.
4
At computer only.
Legend: PG = Programmable
FS = Full scale
RV = Read value
Device Name
Accessories
See Page V3-T9-131
IQ Analyzer 6000 Series
IQ DP-4000 Series
IQ 230 Series
Section Page Number V3-T9-79 V3-T9-87 V3-T9-93
Electrical Parameters
Volts ±0.2% FS
1
±0.3% FS ±0.5% FS
Amperes ±0.2% FS
1
±0.3% FS ±0.5% FS
Current range (% of nominal) 3–800% 10–250% 1–200%
Watts 0.4% FS, 6 RV
2
±0.6% FS ±1.0% FS
VARs 0.4% FS, 6 RV
3
±0.6% FS ±1.0% FS
VA 0.4% FS, 6 RV
2
±0.6% FS ±1.0% FS
PF-apparent 0.8% FS
1
±1.0% FS ±2.0% FS
PF-displacement 0.8% FS
1
±1.0% FS ±2.0% FS
Frequency 0.04%
1
or 0.01 Hz ±0.17% FS ±0.1% Hz
THD-voltage 50th 31st
THD-current 50th 31st
Watthours 0.5% RV
2
±0.6% FS ±1.0% per ANSI C12
Varhours 1% RV
3
±0.6% FS ±1.0% per ANSI C12
VA-hours 0.5% RV
2
±0.6% FS ±1.0% per ANSI C12
Ampere-demand ±0.2% FS
1
±0.3% ±0.5% per ANSI C12
Watt-demand ±0.4% FS
1
±0.6% ±1.0% per ANSI C12
VAR-demand ±0.4% FS
1
±0.6% ±1.0% per ANSI C12
VA-demand ±0.4% FS
1
±0.6% ±1.0% per ANSI C12
Revenue accuracy ANSI C12.20 (0.5%) ANSI C12.1 (1%)
Individual ampere harmonics 50th
Individual voltage harmonics 50th
Interharmonics —
Minimum and/or Maximum Values
Volts L-L, L-N L-L, L-N L-L, L-N
Current A, B, C, N, G A, B, C A, B, C
Power Watt, VAR, VA Watt, VAR, VA Watt, VAR, VA
Power factor Apparent/displacement Apparent/displacement Apparent/displacement
Frequency Hertz Hertz Hertz
THD Amperes/volts Amperes/volts
Demand values All All All
Trend analysis Time/date 2 alarms
4
Event logging 504 events w/timestamp
44
Disturbance recording 10 waveform events