Metering Devices, Protective Relays, Software and Connectivity
Protective Relays
Features, Benefits and Functions
Applications
●
Provides reliable three-
phase and ground
overcurrent protection
for all voltage levels
●
Primary feeder circuit
protection
●
Primary transformer
protection
●
Backup to differential
protection
●
May be used where
instantaneous and/or time
overcurrent protection is
required
●
Ground element capable
of residual, zero sequence
or external source
connections
Protection Functions
●
Breaker failure (50BF)
●
Phase overcurrent
protection per time-current
curve (51-1, 51-2, 51-3)
●
Calculated ground fault
protection per time-current
curve (51R-1, 51R-2)
●
Independent measured
ground or neutral fault
protection per time-current
curve (51X-1, 51X-2)
●
Phase instantaneous
overcurrent (50-1, 50-2,
50-3)
●
Calculated ground or
neutral instantaneous
overcurrent (50R-1, 50R-2)
●
Independent measured
ground or neutral
instantaneous overcurrent
(50X-1, 50X-2)
●
Curve shapes: ANSI,
IEC, or thermal curves
(11 thermal curves)
●
Instantaneous or time
delay reset
●
True rms or fundamental
sensing of each phase
and ground current
●
Zone selective interlocking
(phase and ground) or
reverse blocking for
bus protection
Note: Refer to the Ordering
Information and Page V3-T9-229
(Catalog Ordering Information)
for optional features.
Metered Values
●
rms and fundamental
phase currents
●
rms and fundamental
ground currents
●
Maximum, minimum
and average rms and
fundamental phase
currents
●
Maximum, minimum
and average rms and
fundamental ground
currents
Monitored and Data
Recording Values
●
Trip circuit monitoring
Note: Refer to the Ordering
Information and Page V3-T9-229
(Catalog Ordering Information)
for optional features.
●
Breaker wear (accumulated
interrupted current)
●
Fault data logs (up to
20 events)
●
Sequence of event
recorders (up to
300 events)
●
Waveform capture
(3600 cycles total)
●
CT supervision
Control Functions
●
Remote open/close
●
Programmable I/O
●
Programmable LEDs
●
Multiple setting groups
(up to four)
Communication
●
Local HMI
●
Front RS-232 port
●
Rear RS-485 port
●
IRIG-B11
●
Protocols
●
Modbus RTU
Standards and Certifications
●
Generic standard:
●
EN 61000-6-2
●
EN 61000-6-3
●
Product standard:
●
EC 60255-6
●
EN 50178
●
UL 508 (Industrial Control
Equipment)
●
CSA C22.2 No. 14-95
(Industrial Control
Equipment)
●
ANSI C37.90
●
UL, CSA, CE