Metering Devices, Protective Relays, Software and Connectivity
Protective Relays
Technical Data and Specifications
Control Power
Nominal rating:
120 Vac or 240 Vac
+10%, –25%
Operating range:
120 Vac: 90 132 Vac
240 Vac:180 264 Vac
Frequency: 50 or 60 Hz
Power use:
20 VA maximum
URTD: 6 VA maximum
IPONI: 1 VA maximum
Ride-through time:
30 cycles from nominal Vac
Current Inputs
Nominal (I
n
): 1A or 5A
CT rating:
2 x I
n
continuous
50 x I
n
for 1 second
Burdens:
< 0.25 VA at 5A
< 0.05 VA at 1A
Voltage Inputs
Nominal: 120 Vac
Operating range: 69 to
150 Vac
Burden: 2 VA
Metering Accuracy
Phase current: ±1% of I
n
(5–100%)
Ground current: ±1.5% of I
n
(0–55%)
Discrete Inputs
Number of inputs: two
programmable
Ratings:
1.2 VA at 120 Vac
Maximum off = 36 Vac
Minimum on = 86 Vac
Output Contacts
Number of outputs: four
Form C, programmable.
Momentary:
Make 30A AC/DC for
0.25 seconds
Break 0.25A at 250 Vdc
(Resistive)
Break 5A at 120 240 Vac
Continuous:
5A at 120/240 Vac
5A at 30 Vdc
Analog Output
Rating: ± 4–20 mA
programmable
Maximum load: 1K ohm
Accuracy: 1%
Motor Overload Protection (I
2
t)
Full load amperes:
10–3000
Locked rotor current:
300–1200% FLA
Locked rotor time:
1–120 seconds
Ultimate trip current:
85–150% FLA
Phase CT ratio:
10–4000 (I
n
)
Ground CT ratio:
10–4000 (I
n
)
Timing accuracy: ±
2.5% or
±30 mS
for I > 1.1x U.T.C.
Trip Setting Range
Ground fault (GF): Off,
2–55% CT ratio
GF start time delay:
2–60 cycles
GF run time delay:
0–60 cycles
Timer accuracy: ± 20 mS
Instantaneous O.C.: Off,
300–1600% FLA
IOC start time delay:
2–60 cycles
Timer accuracy: ±20 mS
JAM trip: Off, 100–
1200% FLA
Underload trip: Off,
1–90% FLA
Current unbalance trip:
Off, 4–40% I
neg
/I
pos
Start delay timers:
0–120 seconds
(underload and phase
unbalance)
0–1200 seconds (jam)
Run delay timers:
0–240 seconds
Timer accuracy: ±0.5%
+100 mS
Voltage unbalance: Off,
1 to 100V
% V2/V1: 4% + 40%
Voltage unbalance time
delay: 0 to 1200 sec.
Under/overvoltage time
delay: Off, 10 to 150V
Under/overvoltage time
delay: 0 to 1200 sec
Under/overfrequency:
Off, 15 to 60 Hz
Under/overfrequency time
delay: 0 to 60 sec
Power protection: Off,
0.06 to .90 + FLA VT
Power time delay: 0 to
1200 sec
Power factor: Off, 0.05 lag
to 0.99 lead
Power factor time delay:
0 to 60 sec
Alarm Setting Range
Ground fault: Off,
2–55% CT ratio
Overload I
2
t: Off,
60–99% I
2
t
JAM: Off, 100–1200% FLA
Underload: Off,
1–90% FLA
Phase unbalance: Off,
4–40% I
neg
/I
pos
Run delay timers:
0–240 seconds
Start Control Functions
Starts per time: 1–10 starts
Time for starts per time:
Off, 1–240 minutes
Time between starts:
Off, 1–240 minutes
Number of cold starts:
1–5 starts
Motor transition current:
10–300% FLA
Time for transition:
0–1200 seconds
Inc. sequence timer:
Off, 1–240 seconds
Long acceleration timer:
Off, 1–1200 seconds
Anti-Backspin timer:
Off, 1–3600 minutes
RTD Inputs (Requires
URTD module)
Sensor types:
10 ohm copper
100 ohm nickel
120 ohm nickel
100 ohm platinum
URTD Module Communications
Interface:
Electrical (three-wire)
Fiber optic (preferred)
Fiber optic cable: Type
HBFR-ERS or EUS
Clock
Accuracy: ±1 minute/
month at 77ºF (25°C)
PONI Communications
Type: two-wire, FSK
Baud rate: 1200 or
9600 baud
Protocol: INCOM
Functions:
Read/write set points
Read metered values
Read trip/alarms
Read events/history
View starting profile
MPONI Communications
Type: five-wire, 485
Baud rate: 1200 or
9600 baud
Protocol: Modbus RTU
Functions:
Read metered values
Read trip/alarms
DPONI Communications
Type: J-wire
Baud rate: 500k,
250k, 125k
Protocol: DeviceNet
Functions:
Read metered values
Read trip/alarms
Logging
Log book: 100 events
Log event: 20 trips
and alarms
Log start: last four starts
Start profile: last four starts
(communication only)
History records: motor,
trips, alarms and total
records
Environmental Conditions
Operating temperature:
–4ºF to +140ºF (
–20°C to +60°C)
Storage temperature:
–49ºF to +185ºF
(–45°C to +85°C)
Humidity: 0–95%
noncondensing